Electrical Connections
Liebert
®
CRV
™
62
Figure 37 Electrical field connections—300mm (12") DX models
A
A
5
7
6
1
B
B
View A-A
13 11
14
8
9
9
15 10
9
12
3
4
Ø 1.75"
(44.5mm) K.O.
Ø 1.13"
(28.6mm) K.O.
Disconnect
handle
and cover
removed
Factory-provided conduit for routing
low-voltage field wiring to unit
electric box. See note below.
Factory-provided
conduit for routing
low-voltage field
wiring to unit
electric box. See
note below.
Quarter-Turn Latch allows
the electric panel to be slid
out; Main Disconnect Switch
must be Off
VIEW B-B
Lower terminals
DPN002810
Pg. 3, Rev. 2
VIEW B-B
Upper terminals
Air, Water and
Glycol units only
Factory
T
erminals
Refer to 9.1.3 Standard Electrical Field Connections—300mm (12") DX
Models and 9.1.4 Electrical Field Connections for Optional Features—
300mm (12") DX Models for keys to numbered components.
Rear
View
See Figure 38 for low-voltage
field wiring routing into the unit
SOME COMPONENTS NOT SHOWN FOR CLARITY
General wire routing paths shown. Wiring must be run in conduit and must be inside
Liebert CRV frame and panels. Attach conduit to inside of rails with cable ties.
Control wiring must be run in separate conduit from power wiring. For top entry routing,
see Figure 44; for bottom entry, see Figure 45.