2            Chapter 1    Overview 

Liebert.CRV+ Condenser    User Manual 

Table 1-1    Mechanical parameters of condenser 

Condenser model 

Dimensions(W X D X H, mm) 

Net weight (kg) 

LSF12-R3 

787

×

352

×

1240 

60 

 

1.3.2   Dimensions of Mounting Base 

The dimensions of mounting holes of the base of the condenser are shown in Figure 1-3. 

787

374

394

680

R6

 

Figure 1-3    Dimensions of mounting holes of the base of the condenser (top view, unit: mm) 

1.3.3   Parameters Of Operating Environment 

The operation environment parameters of the condenser meet GB/T4798.3 and GB/T19413. See Table 1-2 for details. 

Table 1-2    Parameters of operation environment 

Item 

Requirement   

Installation 

position 

The standard equivalent distance between the indoor unit and the condenser is 30m. Vertical difference* 
ΔH: -8m≤ΔH≤30m. 

Installation mode 

Horizontal airflow and vertical airflow 

Ambient 

temperature 

-15°C ~ +45°C. Low temperature kits are required if the temperature is below -15°C 

Ambient humidity 

Outdoor: 5%RH~95%RH 

Operation power 

220V±10%, 50Hz 

Altitude 

≤ 1000m. Derating is required if the altitude exceeds 1000m 

Protection level 

IPX4 

Note*:   

The value is positive if the condenser is installed higher than the indoor unit; otherwise the value is negative  

 

1.3.4   Parameters Of Storage Environment 

The storage environment parameters of the condenser meet GB/T4798.1 and GB/T19413. See Table 1-3 for details. 

Table 1-3    Parameters of storage environment 

Item 

Requirement   

Storage environment 

Clean indoor environment with good ventilation and no dust 

Ambient temperature 

-40°C ~ +70°C 

Ambient humidity 

5%RH ~ 95%RH 

Storage time 

The total storage time should not exceed 6 months. Otherwise, the performance needs to be 

re-calibrated   

 

Summary of Contents for Liebert.CRV+

Page 1: ...tact the nearest Emerson local sales office or service center Copyright 2016 by Emerson Network Power Co Ltd All rights reserved The contents in this document are subject to change without notice Emerson Network Power Co Ltd Address Block B2 Nanshan I Park No 1001 Xueyuan Road Nanshan District Shenzhen 518055 P R China Homepage www emersonnetworkpower com E mail overseas support emerson com ...

Page 2: ......

Page 3: ...rameters Of Operating Environment 2 1 3 4 Parameters Of Storage Environment 2 Chapter 2 Mechanical Installation 3 2 1 Moving Unpacking And Inspection 3 2 2 Installation Notes 3 2 3 Space Requirements 4 2 4 Installation Procedures 4 Chapter 3 Maintenance And Troubleshooting 6 3 1 Maintenance 6 3 2 Troubleshooting 6 Appendix 1 Hazardous Substances or Elements Announcement 7 ...

Page 4: ......

Page 5: ... outdoor unit uses air cooling and the main components include fan and heat exchanger Fan Using axial type low noise blades and high performance single phase motor adapting to wide voltage range and having a high reliability Heat exchanger Using finned tube heat exchanger with a high heat dissipating efficiency and wavy fins convenient for cleaning and maintenance due to less dust accumulation 1 3...

Page 6: ...0m Vertical difference ΔH 8m ΔH 30m Installation mode Horizontal airflow and vertical airflow Ambient temperature 15 C 45 C Low temperature kits are required if the temperature is below 15 C Ambient humidity Outdoor 5 RH 95 RH Operation power 220V 10 50Hz Altitude 1000m Derating is required if the altitude exceeds 1000m Protection level IPX4 Note The value is positive if the condenser is installed...

Page 7: ...er pipes Inspection After receiving the product you should check the accessories against the packing list If any parts are found missing or damaged please report to the carrier immediately If any covert damage is found please report to the carrier and the local office of the product supplier 2 2 Installation Notes 1 The outdoor unit should be installed in the place that is convenient for maintenan...

Page 8: ...ient installation and service space around the installation place 2 4 Installation Procedures Note To ensure the safety before welding the pipeline and patching welding all nitrogen of air condition system must be discharged to release the system pressure Installing pipelines Note 1 The copper pipes should be heat preserved When the copper pipes pass through the wall or other obstacles take isolat...

Page 9: ... by the professional personnel from the manufacturer maintenance department or similar department of the manufacturer The specifications of the power supply cables of the outdoor unit is L N PE the recommended cable diameter is no less than 18AWG 0 75mm 2 Connect one end of the power supply cables from the accessories to the power output terminals of the indoor unit as shown in Figure 2 3 and conn...

Page 10: ... Clean the fin of heat exchanger with compressed air or fin detergent weakly alkaline if the condenser air flow is blocked The direction of inverse air flow is good when the compressed air is used 3 Check for damaged or reversed fins and maintain them in time 4 Avoid snow accumulation around the condenser in winter Fan Check that the fan runs normally and check it for problems such as abnormal noi...

Page 11: ...te the harzardous substances in the products through unremitting efforts in research However limited by the current technical level the following parts still contain harzardous substances due to the lack of reliable substitute or mature solution 1 Reason that the above parts contain lead Some of the copper alloys contain lead high temperature soldering materials contain lead and the high temperatu...

Reviews: