2 Chapter 1 Overview
Liebert.CRV+ Condenser User Manual
Table 1-1 Mechanical parameters of condenser
Condenser model
Dimensions(W X D X H, mm)
Net weight (kg)
LSF12-R3
787
×
352
×
1240
60
1.3.2 Dimensions of Mounting Base
The dimensions of mounting holes of the base of the condenser are shown in Figure 1-3.
787
374
394
680
R6
Figure 1-3 Dimensions of mounting holes of the base of the condenser (top view, unit: mm)
1.3.3 Parameters Of Operating Environment
The operation environment parameters of the condenser meet GB/T4798.3 and GB/T19413. See Table 1-2 for details.
Table 1-2 Parameters of operation environment
Item
Requirement
Installation
position
The standard equivalent distance between the indoor unit and the condenser is 30m. Vertical difference*
ΔH: -8m≤ΔH≤30m.
Installation mode
Horizontal airflow and vertical airflow
Ambient
temperature
-15°C ~ +45°C. Low temperature kits are required if the temperature is below -15°C
Ambient humidity
Outdoor: 5%RH~95%RH
Operation power
220V±10%, 50Hz
Altitude
≤ 1000m. Derating is required if the altitude exceeds 1000m
Protection level
IPX4
Note*:
The value is positive if the condenser is installed higher than the indoor unit; otherwise the value is negative
1.3.4 Parameters Of Storage Environment
The storage environment parameters of the condenser meet GB/T4798.1 and GB/T19413. See Table 1-3 for details.
Table 1-3 Parameters of storage environment
Item
Requirement
Storage environment
Clean indoor environment with good ventilation and no dust
Ambient temperature
-40°C ~ +70°C
Ambient humidity
5%RH ~ 95%RH
Storage time
The total storage time should not exceed 6 months. Otherwise, the performance needs to be
re-calibrated