background image

Keystone

 PED - OPErating anD SafEty inStructiOnS

Resilient seated ButteRfly ValVes

7 m

o

Hazard potentials

• Disregarding of instructions
• Improper use of product
• Insufficiently qualified personnel

Ensure that valve materials are compatible with 
the pipeline fluid.

Valve application to be within the pressure/
temperature limits indicated in the P/T diagram 
of the Product Manual.

If in doubt contact factory.

Check the valve’s functionality on a regular 
basis.

When the valve is used in an end-of-line 
function, PED Cat-I applications are allowed 
only. For other categories, contact factory.

precautions

Warning

For safety reasons, it is important to take the 
following precautions before you start work on 
the valve:
1.  Personnel making any adjustments to the 

valves should utilize suitable equipment. 
All required personal protection means should 
be worn.

2.  The line must be depressurized before 

installing the valve. In case of dangerous 
pipeline fluids, the pipeline should be drained 
and flushed properly with an appropriate 
cleaning fluid.

3.  Personnel trained in all aspects of manual and 

mechanical handling techniques must carry 
out handling of all valves.

4.  Misuse of the valve is not allowed. 

For example: the valve, handles, actuators or 
other parts may not be used as ‘climbing tools’.

5.  Ensure the valve pressure/temperature 

specification as indicated on the identification 
label, is within the pressure/temperature 
limits of the application. A full pressure/
temperature diagram can be obtained from 
the Product Manual. With the use of the figure 
and trim number on the valve’s identification 
label, the correct diagram can be found.

6.  Ensure that valve materials are compatible 

with the pipeline fluid.

Before installation, these instructions must be fully read and understood

installation

1.  Handling and lifting should be performed 

according the Maintenance and Installation 
Instructions.

2.  Keystone valves are bi-directional unless 

fitted with a flow direction arrow. If a 
directional arrow is fitted then the valve 
must be installed with the arrow pointing in 
the direction of the flow.

3.  For detailed installation instructions 

refer to the Maintenance and Installation 
Instructions for the specific product.

4.  Preferred installation position of butterfly 

valves is the shaft horizontal and the lower 
disc-edge opening downstream.

5.  Do not use the valve to spread the flanges.
6.  Instructions whether to use or to omit flange 

gaskets are stated in the Maintenance and 
Installation Instructions.

Product designation

Mass

Identification 

number of 

notified body

Trim number

Nominal 

diameter

flange 

compatibilty

(drilling)

Temperature 

limit in °C

Max. permissible 

working pressure

Body material 

of construction

Year of construction/JOB number

tagplate

7.  In case the valve is used as spool piece 

during erection of piping, do not finish weld 
the flanges to the pipes with the valve bolted 
between the flanges as this will result in 
serious heat-damage to the seat.

8.  Valve operation should be checked for 

open - close positions. The disc should have 
enough clearance from the pipeline in all 
positions.

9.  In case of CompoSeal valves:

a.  Do not overtighten the flange screws. 

See the specific Installation and 
Maintenance Instructions for maximum 
allowable bolting torque.

b.  Do not use CompoSeal valves in area’s 

sensitive to earthquakes.

Vcosi-00754-en 15/07

www.valves.emerson.com

© 2017 Emerson. All rights reserved.