May 2022
Installation, Operation and Maintenance Manual
VCIOM-01493-EN Rev. 0
38
Section 11: Data Exchange Mode
Data Exchange Mode
Data Exchange Mode
Byte
Name
Dim
Range
0
Byte 0
0
Fully open position
1
Opening
2
Closing
3
Actuator moving
4
Fully close
5
Motor stopped
6
Intermediate position
7
Monitor relay
1
Byte 1
0
Hardwired mode
1
Local control
2
Remote control
3
Local configuration
4
-
5
-
6
-
7
-
2
Byte 2
0
Positioner active
1
-
2
-
3
-
4
-
5
-
6
-
7
-
11.2.2
General Data
Table 16.
Slot 1, index 0, length 3 bytes - read only: general data about current
working condition
Table 17.
Slot 1, index 1, length 3 bytes - read only: position and torque
Table 18.
Slot 1, index 2, length 1 byte - read only: temperature
Byte
Name
Dim
Range
EU
0-1
Current position
2 bytes
0 - 1000
0.1%
2
Current torque
1 byte
0 - 100
%
Byte
Name
Dim
Range
EU
0
Internal temperature
1 byte
-128 +127
°C