68 • RLDS I&O Manual
026-1309 Rev 11
11.3. Einstein Setup for RLDS
Set dip switch 8 to OFF and follow the steps for
setting up RLDS units through the Einstein controller
interface:
1. Log on.
2. Press F8 for
ACTIONS
.
3. Press Y for
System Setup
.
4. Press 4 for
Network Status/Setup
.
5. Press 2 for
Connected I/O Boards &
Controllers
to open the
Network Setup
screen.
6. Under
Boards on I/O Network
, set the RLDS
number under
IRLDS Controllers
.
7. Press F9
HOME
to go back to the Home
screen.
8. Set the Gateway to 1. Each Gateway can
handle three RLDS controllers, so if four
RLDS controllers are on the network, two
Gateways are needed. The first Gateway will
be address 1 and the RLDS units are numbered
as 1, 2, 3. The second Gateway will be
addressed as 4, but the RLDS is set to 1
because all units on the Gateway are numbered
sequentially 1 to 3. The RLDS controllers are
always numbered 1 to 3 when connected to the
Gateway.
To see a summary of RLDS controllers on the
network:
1. Press F5 for
MORE
.
2. Press L for
Leak Detection
.
3. The leak detectors are listed under
See Summary
. Press the down arrow to
highlight a unit and press Enter to show the
summary of units listed.
The status screen for the selected RLDS controller is
shown.
4. F8 for
ACTIONS
.
5. Press B for
Setup
--name the RLDS in the
Name
field.
6. Press the down arrow to the
Num Channels
field to add the number of zones.
7. Press F10 to go back and see the current status
of the zones.
8. Press F9
HOME
to go back to the Home
screen.
11.4. Supervisory Controller
Setup for RLDS
1. Click the
Control Inventory
icon.
2. Scroll down to the
Refrigeration
category and
click
Add Control
.
3. Select
RLDS
to add an instance to the
program.
11.4.1. Adding Application
1. Indicate the Name and association, Modbus
port number and the address.Click
Update
or
Save Changes
to save.
Figure 11-4
- Set up RLDS in the Supervisory Controller
Figure 11-5
- Add the RLDS Application to the Supervisory
Controller