Operation Select (OPTION) Screen
Main Screens • 59
Select the desired RLDS by pressing the right
arrow key and selecting the desired RLDS number.
Press the down arrow key to prompt you to the
Operation Select (OPTION) screen.
The WAITING ON READ FROM RLDS
message displays, and after a short delay prompts you
to the Operation Select (OPTION) screen.
10.4. Operation Select
(OPTION) Screen
The Operation Select (OPTION) screen enables the
user to select the following entry points:
Press the right arrow key to enable you to change the
number selection next to
OPTION
. When a right
arrow appears after
OPTION
, press the number key
of the desired screen (1,2, or 3). Press the down arrow
key twice to display the selected screen.
• Select 1 to access the RLDS STATUS screen
See
Section 10.5., STATUS OPTION Screen
• Select 2 to access the RLDS FAULTS screen
See
Section 10.4.2., RLDS FAULTS (SYSTEM
• Select 3 to access the RLDS CONFIG screen
See
Section 10.4.3., RLDS Configuration Option
.
10.4.1. RLDS STATUS (STATUS
OPTION) Screen
The STATUS OPTION screen allows you to check
individual zones, overall controller status, and
to find out more information about
accessing these screens.
• ZONE STATUS gives status on individual
zones
See
Section 10.5.1., Zone Status Screen
• CTRL STATUS is overall controller status
Section 10.5.2., General Controller (CTRL STA
.
• DIAGNOSTICS is diagnostic zone data
See
Section 10.5.3., DIAGNOSTICS Screen 1: Sen
.
10.4.2. RLDS FAULTS (SYSTEM
FAULTS) screen
From the Operation Select (OPTION) screen,
Section 10.4., Operation Select (OPTION) Screen
select
RLDS FAULTS
by pressing the right arrow
key, selecting
2
, and pressing the down arrow key
twice.
The RLDS FAULTS screen will display a list of the
system failures associated with the selected RLDS.
One failure will be displayed on each line.
The following are failure messages that are used:
CLIPPNG FAULT - A/D out of range
ZERO FAULT - Zero voltage outside factory limits
NO FLOW - No flow on any zone
PURGE FLOW - No flow on purge
ZONE FLOW - No flow on one or more zones
TRIGGER FAULT - IR Source clock trigger missing
OPTION: 1
1 = RLDS STATUS
2 = RLDS FAULTS
3 = RLDS CONFIG
NOTE: OPTION: 1 defaults to 1.
STATUS OPTION:
1 = ZONE STATUS
2 = CTRL STATUS
3 = DIAGNOSTICS
NOTE: Once a fault is detected and repaired,
the unit will go through an entire cycle and the
fault will clear itself and return to normal.