14 • RLDS I&O Manual
026-1309 Rev 11
3.4. RLDS Interior Components
3.5. RLDS Electrical Wiring
The RLDS uses a universal power supply that is
capable of accepting inputs of 100 to 240 VAC, 50/60
Hz. The monitor's power consumption is 20 Watts. It
is highly recommended that the monitor be connected
directly to the AC power source, preferably on its own
circuit. The AC power connection should be
completed with UL approved 3-conductor wire
(minimum 16 AWG), rated 300 VAC at 221°F
(105°C).
Locate a convenient service knockout and install
electrical conduit in the typical manner.
Locate the AC Input Terminals and Ground Stud on
the inside of the monitor (
). Secure the
incoming AC power neutral (white/blue) and live
(black/brown) wires to the LINE 1 and LINE 2
terminals.
Using the supplied crimp-on ring terminals, washers,
and nuts, connect the incoming AC power ground
wire (green) to the monitor's AC input ground stud,
and then install a separate wire between the ground
stud and the GND terminal.
Figure 3-6
- Diagram of RLDS Interior
NOTE: The plastic cable ties surrounding the
air pump are to ensure safe handling during
shipment. Remove before operating the unit.
Reinstall a plastic cable around the air pump if
the unit is shipped back to Emerson for service or
repair. This prevents damage during shipment.
NOTE: For more information on power
specifications, contact your Emerson
representative for more information.