Reference Manual
May 2019
00809-0100-3003, Rev AA
18
3.5.2
Wiring configurations
Figure 3-14 Electrical Connection Drawing
Refer to
for descriptions of the cable entries for terminal rows 1 & 2.
For standard 3-wire connection cables should be connected to Terminal Row 1 in pos24 V, 0 V
and current loop output connected to the mA terminal. Maximum loop resistance: 500
Ω
.
Current source is the standard default operation; current sink is an option and should be specified at
time of order.
Relay data: 1.4 A, 30 Vdc switch voltage.
For a full description of fault relays refer to section
for more information.