S600+ Instruction Manual
4-8
I/O
Revised July-2017
Table 4-5. DIGIN Pin Connections for SKT-C
Pin
Function
19
DIGIN-CH7
18
DIGIN-CH8
17
RETURN CH5-8
16
DIGIN-CH9
15
DIGIN-CH10
14
DIGIN-CH11
13
DIGIN-CH12
12
RETURN CH9-12
11
DIGIN-CH13
10
DIGIN-CH14
9
DIGIN-CH15
8
DIGIN-CH16
7
RETURN CH13-16
4.1.4 Digital Outputs (DIGOUT)
The S600+ supports 12 digital output (DIGOUT) channels, which are
open collector type outputs. The maximum current rating is 100
mAmps at 24 Volts dc. Output frequencies up to 0.5 Hz are possible.
Carefully check the DC polarity using an external DC supply in series
with the load. When using inductive loads (such as relay coils), place a
diode across the load. Refer to
Figures 4-11
and
4-12
.
The DIGOUT channels use the connectors labeled SKT-B and SKT-C,
which are located on the backplate of the I/O module. Refer to
Tables
4-6
and
4-7
for the DIGOUT pin connections.
Figure 4-11. Digital Output Schematic (Relay)
Figure 4-12. Digital Output Schematic (24 V Switched Indicator)