Introduction

This installation guide provides instructions for installation, 

startup and adjustment. To receive a copy of the Instruction 

Manual, contact your local Sales Office or view a copy at 

www.fisher.com. For further information refer to: 161 Series 

Instruction Manual, D103232X012.

P.E.D. Categories

This product may be used as a pressure accessory with 

pressure equipment in the following Pressure Equipment 

Directive categories. It may also be used outside of the 

Pressure Equipment Directive using sound engineering 

practice (SEP) per table below. For information on the 

current PED revision see Bulletin: 

D103053X012

.

TYPE

PRODUCT SIZE

CATEGORY

161EB

NPS 1/4

SEP

161AY

DN 15 / NPS 1/2

Specifications

Outlet (Control) Pressure Ranges

See Table 1

Proportional Bands

See Table 1

Maximum Inlet Pressures

(1)

161, 161M, 161EB, 161EBH, 161EBM or 161EBHM: 

103 bar / 1500 psig

161AY, 161AYM or 161AYW: 

10.3 bar / 150 psig

Pilot Flow Coefficients

See Table 2

Options

Type 252 Pilot supply filter

Pilot Sping Case Vent

1/4 NPT (internal)

1. The pressure/temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded.

Installation

!

WARNING

Only qualified personnel shall install or service 

a relief valve/backpressure regulator. Relief 

valves and backpressure regulators should 

be installed, operated and maintained in 

accordance with international and applicable 

codes and regulations and Emerson Process 

Management Regulator Technologies, 

Inc. instructions.

If the regulator vents fluid or a leak develops in 

the system, it indicates that service is required. 

Failure to take the regulator out of service 

immediately may create a hazardous condition.
Personal injury, equipment damage, or leakage 

due to escaping fluid or bursting of pressure 

containing parts may result if this regulator 

is overpressured or is installed where service 

conditions could exceed the limits given in the 

Specifications section, or where conditions 

exceed any ratings of the adjacent piping or 

piping connections.

To avoid such injury or damage, provide 

pressure relieving or pressure-limiting devices 

(as required by the appropriate code, regulation 

or standard) to prevent service conditions from 

exceeding limits. Additionally, physical damage 

to the regulator could result in personal injury 

and property damage due to escaping fluid. 

To avoid such injury and damage, install the 

regulator in a safe location.

PILOT TYPE

OUTLET (CONTROL) PRESSURE RANGE

PROPORTIONAL BAND

(1)(2)(3)

bar

psig

bar

psig

161 or 161M

0.34 to 1.03 

5 to 15 

0.14 

0.69 to 8.62 

10 to 125 

0.14 

8.3 to 20.7 

120 to 300 

0.41 

161AY, 161AYM or 161AYW

15 to 37 mbar

(4)

6 to 15 in. w.c.

(4)

2 mbar

1 in. w.c

0.03 to 0.08

(5)

 

0.5 to 1.2

(5)

2 mbar

1 in. w.c

0.08 to 0.17

(6)

 

1.2 to 2.5

(6)

 

0.03 

0.5 

0.17 to 0.31 

2.5 to 4.5 

0.03 

0.5 

0.31 to 0.48 

4.5 to 7 

0.03 

0.5 

161EB or 161EBM

0.34 to 1.03 

5 to 15 

0.03 

0.5 

0.69 to 2.76 

10 to 40 

0.03 

0.5 

2.07 to 5.17 

30 to 75 

0.04 

0.6 

4.83 to 9.65 

70 to 140 

0.09 

1.3 

8.96 to 13.8 

130 to 200 

0.10 

1.5 

13.8 to 24.1 

200 to 350 

0.21 

161EBH or 161EBHM

17.2 to 31.0

250 to 450

0.24

(7) 

3.5

(7)

27.6 to 48.2

400 to 700

0.48

(7)

 

7

(7)

1. Proportional band includes outlet pressure drop plus hysteresis (friction), but does not include lockup.

2. Proportional band was determined with a pressure drop ranging from 3.4 to 10.3 bar / 50 to 150 psig. Approximately double the proportional band if the pressure drop is less than 3.4 bar / 50 psig

3. With Type 112 restrictor set on 2.

4. The spring ranges for the Type 161AYW is 7.5 to 30 mbar / 3 to 12 in. w.c.

5. The spring ranges for the Type 161AYW is 27 to 62 mbar / 11 to 25 in. w.c.

6. The spring ranges for the Type 161AYW is 0.06 to 0.17 bar / 0.9 to 2.5 psig.

7. Proportional band was determined with a pressure drop ranging from 6.9 to 20.7 bar / 100 to 300 psig. Approximately double the proportional band if the pressure drop is less than 6.9 bar / 100 psi.

Table 1.

 Outlet (Control) Pressure Ranges and Proportional Bands

161 Series

Installation Guide

D103232X014
English - August 2018

Summary of Contents for Fisher

Page 1: ...its given in the Specifications section or where conditions exceed any ratings of the adjacent piping or piping connections To avoid such injury or damage provide pressure relieving or pressure limiting devices as required by the appropriate code regulation or standard to prevent service conditions from exceeding limits Additionally physical damage to the regulator could result in personal injury ...

Page 2: ...re remove the closing cap or loosen the locknut and turn the adjusting screw clockwise to increase outlet pressure or counterclockwise to decrease pressure Monitor the outlet pressure with a test gauge during the adjustment Replace the closing cap or tighten the locknut to maintain the desired setting Taking Out of Service Shutdown WARNING To avoid personal injury resulting from sudden release of ...

Page 3: ...1EBHM 37B2946_B 37B1213 Key Description 49 Connector Seal 50 Backup Ring 51 Washer Type 161AYW only 52 Spring Type 161AYW only 53 O ring Type 161AYW only Key Description 54 Groove Pin Type 161AYW only 55 Restriction Types 161AY and 161AYM only 56 Baffle Plate Types 161AY and 161AYM only 57 Bleed Assembly Type 161AYW only Recommended Spare Part 11 16 17 18 10 1 15 3 2 12 8 9 7 23 4 6 13 17 16 2 18 ...

Page 4: ...019 Emerson Process Management Regulator Technologies Inc All rights reserved 08 19 The Emerson logo is a trademark and service mark of Emerson Electric Co All other marks are the property of their prospective owners Fisher is a mark owned by Fisher Controls International LLC a business of Emerson Automation Solutions The contents of this publication are presented for informational purposes only a...

Reviews: