background image

Y600A Series

3

 

2.  The regulator may be installed in any position as   

      long as the flow through the body is in the direction  

      indicated by the arrow cast on the body.  If  

      continous operation is required during inspection or  

      maintenance, install a three-valve bypass around       

      the regulator.

A regulator may vent some gas to the 

atmosphere.  In hazardous or flammable 

gas service, vented gas may accumulate 

and cause personal injury, death, or 

property damage due to fire or explosion.  

Vent a regulator in hazardous gas service 

to a remote, safe location away from air 

intakes or any hazardous area.  The vent 

line or stack opening must be protected 

against condensation or clogging.

  3.  Be certain that the vent (key 26) is not positioned  

       so that it can collect moisture which may drain into  

       the spring case.  The diaphragm casing (key 4) may  

       be rotated to any of four positions with respect to the  

       body in order to obtain desired positioning.  Perform  

       Body Area Maintenance procedure steps 1 and 4   

       through 8 to rotate the diaphragm casing.

 

4.  The Type Y600AM regulator requires a downstream  

       control line.  Be sure to install this control line before   

       putting the regulator into operation.  The downstream  

       control line pipe should be at least 1/2-inch (12,7mm)  

       in diameter and connected to a straight section of  

              outlet  piping  at  least  5  to  10  pipe  diameters  downstream               

       of the regulator.  If instability due to turbulence exists,   

       a hand valve can be installed in a straight section of  

       the control line.  This hand valve can be throttled down  

       to dampen out pulsations.

Startup and Adjustment

A Y600A Series regulator can be placed in operation by 

slowly introducing inlet pressure.  The regulator takes 

control when downstream pressure is established.

The regulator has been adjusted at the factory to provide 

approximately the reduced pressure requested on the 

order.  With a spring-loaded regulator, the pressure 

setting may be adjusted within the spring range shown 

in Table 1.  To adjust the pressure setting, perform the 

following steps (key numbers are referenced in Figures 3 

through 6):

  1.  Remove the closing cap (key 22).

!

WARnIng

  2.  Use a 1-inch (25,4 mm) hex rod or screwdriver to   

       turn the adjusting screw (key 35) either clockwise to  

       increase outlet pressure or counterclockwise to  

       decrease outlet pressure.

To avoid personal injury, property 

damage, or equipment damage caused 

by bursting of pressure containing parts 

or explosion of accumulated gas, never 

adjust the control spring to produce an 

outlet pressure higher than the upper 

limit of the outlet pressure range for 

that particular spring.  If the desired 

outlet pressure is not within the range 

of the control spring, install a spring 

of the proper range according to the 

Diaphragm and Spring Case Area section 

of the Maintenance procedure.

 

3.  After making the adjustment and replacing the      

      closing cap (key 22), the closing cap can be wired to  

      the spring

 case (key 3) to discourage tampering.

Shutdown

First close the nearest upstream shutoff valve and then 

close the nearest downstream shutoff valve to vent the 

regulator properly.  Next, open the vent valve between 

the regulator and the downstream shutoff valve closest to 

it.  All pressure between these shutoff valves is released 

through the open vent valve, since a Y600A Series 

regulator remains open in response to the decreasing 

downstream pressure.

Maintenance

Regulator parts are subject to normal wear and must be 

inspected and replaced as necessary.  The frequency 

of inspection and replacement of parts depends on 

the severity of service conditions and upon applicable 

codes and government regulations.  Key numbers are 

referenced in Figures 3 through 5 unless otherwise noted.

To avoid personal injury, property damage, 

or equipment damage caused by sudden 

release of pressure or explosion of 

accumulated gas, do not attempt any 

maintenance or disassembly without 

first isolating the regulator from system 

pressure and relieving all internal pressure 

from the regulator.

!

WARnIng

!

WARnIng

Summary of Contents for Fisher Y600A Series

Page 1: ...e Specifications section on page 2 Individual regulator data is stamped on the closing cap as it comes from the factory Installation Personal injury property damage equipment damage or leakage due to escaping gas or bursting of pressure containing parts may result if this Warning regulator is over pressured or is installed where service conditions could exceed the limits given in the Specification...

Page 2: ...37 to 83 mbar Light green 1B537127022 1 2 to 2 5 psig 0 08 to 0 17 bar 0 5 to 2 psig 0 03 to 0 14 bar Light blue 1B537227022 2 5 to 4 5 psig 0 17 to 0 31 bar 0 5 to 3 psig 0 03 to 0 21 bar Black 1B537327052 4 5 to 7 psig 0 31 to 0 48 bar 1 to 4 psig 0 07 to 0 28 bar 1 Minimum outlet pressure setting may be approximately 1 inch w c 2 mbar lower if spring case is below diaphragm Note If the regulato...

Page 3: ...setting may be adjusted within the spring range shown in Table 1 To adjust the pressure setting perform the following steps key numbers are referenced in Figures 3 through 6 1 Remove the closing cap key 22 Warning 2 Use a 1 inch 25 4 mm hex rod or screwdriver to turn the adjusting screw key 35 either clockwise to increase outlet pressure or counterclockwise to decrease outlet pressure To avoid per...

Page 4: ...e performing these steps Note Any Type 662 remote control drive unit used with a Y600A Series regulator must be removed from the spring case key 3 before these steps can be performed 1 Remove the closing cap key 22 and turn the adjusting screw key 35 counterclockwise to remove the compression from the spring key 6 2 If the only maintenance is to change the control spring take out the control sprin...

Page 5: ...7 32 and 33 1 Insert pipe plug key 27 Figure 4 in the diaphragm casing key 4 2 Follow steps 1 through 4 in the Diaphragm and Spring Case Area Maintenance section to remove one machine screw key 33 Figure 3 the stem seal O ring key 30 Figure 4 and the throat seal key 31 Figure 4 blocking the registration port 3 Insert pitot tube key 32 and four machine screws key 33 as outlined in step 5 of the Bod...

Page 6: ...2606992 31 Throat Seal O Ring Type Y600AM only Nitrile NBR 1D682506992 Key Description Part Number 32 Pitot Tube Types Y600A and Y600AR only 304 Stainless steel 17B4479X012 33 Machine Screw Stainless steel Type Y600AM 1 required 18A0703X022 Types Y600A and Y600AR 4 required 19A7151X022 35 Adjusting Screw Zinc 1B537944012 36 Washer 18B3440X012 37 Spring Holder Type Y600AR only Plated steel 1C323114...

Page 7: ...Y600A Series 7 A7142_1 Figure 4 Type Y600AM Regulator Assembly Figure 5 Diaphragm Casing Cap Screw Location A7144 2 ...

Page 8: ...r proper selection use and maintenance of any Emerson Process Management product remains solely with the purchaser Industrial Regulators Emerson Process Management Regulator Technologies Inc USA Headquarters McKinney Texas 75069 1872 USA Tel 1 800 558 5853 Outside U S 1 972 548 3574 Asia Pacific Shanghai China 201206 Tel 86 21 2892 9000 Europe Bologna Italy 40013 Tel 39 051 4190611 Middle East and...

Reviews: