Introduction

This installation guide provides instructions for 

installation, startup, and adjustment.  To receive  

a copy of the instruction manual, contact your  

local Sales Office or view a copy at 

 

www.fisherregulators.com.  For further 

information refer to: T208 Series Tank Blanketing 

Vapor Recovery Regulators Instruction 

Manual, D103752X012.

P.E.D. Categories

This product may be used as a safety accessory 

with pressure equipment in the following Pressure 

Equipment Directive 97/23/EC categories.  It may 

also be used outside of the Pressure Equipment 

Directive using sound engineering practice (SEP) 

per table below

.

PRODUCT SIZE

CATEGORY

FLUID TYPE

DN 20 and 25 / 3/4 and 1 inch

SEP

1

Specifications

Available Configurations

Type T208: 

Tank blanketing vapor recovery 

regulator with control pressure range of 5 mbar 

to 0.48 bar / 2 inches w.c. to 7 psig in six 

different spring ranges and has internal pressure 

registration requiring no control line.

Type T208M:

 Similar to Type T208 but has a 

blocked throat and a control line connection for 

external pressure registration.

Body Sizes and End Connection Styles

See Table 1

Maximum Allowable Inlet (Casing) Pressure

(1)

See Table 1

Maximum Outlet Pressure

(1)

2.4 bar / 35 psig

Maximum Emergency Inlet Pressure to Avoid 

Internal Parts Damage

(1)

 

With Nitrile (NBR) or Fluorocarbon (FKM) 

diaphragm: 

2.4 bar / 35 psig

With Fluorinated Ethylene Propylene (FEP) 

diaphragm: 

1.4 bar / 20 psig

Control Pressure Ranges

(1)

See Table 2

Shutoff Classification per ANSI/FCI 70-3-2004

Class VI (Soft Seat)

Pressure Registration

Type T208: 

Internal

Type T208M: 

External

1.  The pressure/temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded.

2.  See Table 3 for operating temperature ranges for available trim combinations.

Material Temperature Capabilities

(1)(2)

Nitrile (NBR): 

-29 to 82°C / -20 to 180°F

Fluorinated Ethylene Propylene (FEP): 

-29 to 82°C / -20 to 180°F

Fluorocarbon (FKM): 

4 to 149°C /

 

40 to 300°F

Ethylene Propylene Diene (EPDM):

 

-29 to 107°C / -20 to 225°F 

Perfluoroelastomer (FFKM):

 

-18 to 149°C / 0 to 300°F 

Installation

!

WARNING

Only qualified personnel shall install 

or service a regulator.  Regulators 

should be installed, operated, 

and maintained in accordance 

with international and applicable 

codes and regulations, and 

Emerson Process Management 

Regulator Technologies, Inc. 

(Regulator Technologies) instructions.

If the regulator vents fluid or a 

leak develops in the system, it 

indicates that service is required.  

Failure to take the regulator out of 

service immediately may create a 

hazardous condition.
Personal injury, equipment damage, 

or leakage due to escaping fluid 

or bursting of pressure containing 

parts may result if this regulator is 

overpressured or is installed where 

service conditions could exceed the 

limits given in the Specifications 

section, or where conditions exceed 

any ratings of the adjacent piping or 

piping connections.
To avoid such injury or damage, 

provide pressure-relieving or 

pressure-limiting devices (as required 

by the appropriate code, regulation, 

or standard) to prevent service 

conditions from exceeding limits.
Additionally, physical damage to the 

regulator could result in personal 

injury and property damage due to 

escaping fluid.  To avoid such injury 

and damage, install the regulator in a 

safe location.

Summary of Contents for FISHER T208 Series

Page 1: ... VI Soft Seat Pressure Registration Type T208 Internal Type T208M External 1 The pressure temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded 2 See Table 3 for operating temperature ranges for available trim combinations Material Temperature Capabilities 1 2 Nitrile NBR 29 to 82 C 20 to 180 F Fluorinated Ethylene Propylene FEP 29 to 8...

Page 2: ...e a 25 mm 1 inch hex rod or flat screwdriver to turn the adjusting screw key 35 either clockwise to increase control pressure or counterclockwise to decrease control pressure The regulator will go into immediate operation To ensure correct operation always use a pressure gauge to monitor the vapor recovery pressure when making adjustments 3 After making the adjustment replace the closing cap gaske...

Page 3: ...o 0 48 bar 3 8 to 7 psig spring ranges only ERSA02737 ERSA02738 ERSA02737 10 7 45 8 16 12 11 49 42 17 44 L1 L2 L2 L1 L1 9 7 50 36 6 35 14 18 13 41 5 38 10 7 45 8 16 12 30 11 49 42 17 44 9 7 50 36 6 35 14 18 31 34 41 5 38 L1 L1 L1 L1 L1 L2 L2 20 19 35 22 6 L2 TYPE T208 ASSEMBLY WITH INTERNAL PRESSURE REGISTRATION TYPE T208M ASSEMBLY WITH EXTERNAL PRESSURE REGISTRATION EXTERNAL SQUARE HEAD ADJUSTING...

Page 4: ...892 9499 For further information visit www fisherregulators com The distinctive diamond shape cast into every spring case uniquely identifies the regulator as part of the Fisher brand and assures you of the highest quality engineering durability performance and support Table 2 Control Pressure Ranges and Spring Information CONTROL PRESSURE RANGE SPRING PART NUMBER SPRING COLOR SPRING WIRE DIAMETER...