background image

Type T205B

D103750X012

Instruction Manual

March 2013

www.fisherregulators.com

Type T205B Balanced Tank Blanketing Regulator

!

WARNING

Failure to follow these instructions or 

to properly install and maintain this 

equipment could result in an explosion, 

fi re and/or chemical contamination 

causing property damage and personal 

injury or death.
Fisher

®

 tank blanketing regulators must 

be installed, operated, and maintained 

in accordance with federal, state and 

local codes, rules and regulations, 

and Emerson Process Management 

Regulator Technologies, Inc. (Regulator 

Technologies) instructions.

If the regulator discharges process fl uid or 

a leak develops in the system, service to 

the unit may be required.  Failure 

to correct trouble could result in a 

hazardous condition.

Call a qualifi ed service person to service 

the unit.  Installation, operation, and 

maintenance procedures performed by 

unqualifi ed person may result in improper 

adjustment and unsafe operation.  Either 

condition may result in equipment damage 

or personal injury.  Only a qualifi ed person 

must install or service the Type T205B tank 

blanketing regulator.

Introduction

Scope of the Manual

This Instruction Manual provides instruction for 

installation, startup, maintenance, and parts 

ordering information for the Type T205B tank 

blanketing regulator.

Product Description

The Type T205B balanced tank blanketing regulator 

(Figure 1) is a direct-operated regulator with fully 

balanced plug design to reduce inlet pressure sensitivity 

and with large diaphragm to accurately control tank 

pressure at low pressure settings on tank blanketing  

systems.  The regulator prevents a stored liquid 

from vaporizing into the atmosphere, reduces liquid 

combustibility and prevents oxidation or contamination 

of the liquid by reducing its exposure to air.  The 

Type T205B maintains a slightly positive pressure and 

thereby reduces the possibility of tank wall collapse 

during pump out operation.

Contents

Introduction ..................................................................1
Specifications ..............................................................2
Principle of Operation ..................................................3
Installation ...................................................................4
Startup .........................................................................6
Adjustment...................................................................6
Shutdown.....................................................................7
Maintenance ................................................................7
Parts List.................................................................... 11

Figure 1. 

 Type T205B Tank Blanketing Regulator

Summary of Contents for FISHER T205B

Page 1: ... condition may result in equipment damage or personal injury Only a qualified person must install or service the Type T205B tank blanketing regulator Introduction Scope of the Manual This Instruction Manual provides instruction for installation startup maintenance and parts ordering information for the Type T205B tank blanketing regulator Product Description The Type T205B balanced tank blanketing...

Page 2: ...ight 17 7 pounds 8 kg 1 The pressure temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded 2 See Table 4 for operating temperature ranges for available trim combinations Table 2 Outlet Control Pressure Ranges and Spring Information Outlet Control Pressure Range Spring Part Number Spring Color Spring Wire Diameter Spring Free Length Inch...

Page 3: ...space pressure over a stored liquid When liquid is pumped out of the tank or vapors in the tank condense the pressure in the tank decreases Tank pressure is sensed by the actuator diaphragm Spring force pushes the pusher post assembly the valve disk moves away from the orifice allowing the gas flow to increase Type T205B Tank Blanketing Regulator MXXXX November 2012 Type T205B INLET PRESSURE OUTLE...

Page 4: ...damage install the regulator in a safe location Note If the regulator is shipped mounted on another unit install that unit according to the appropriate instruction manual 1 Only personnel qualified through training and experience shall install operate and maintain a regulator For a regulator that is shipped separately make sure there is no damage to or debris in the regulator Also ensure that all ...

Page 5: ...ires a downstream control line Be sure to install the control line before putting the regulator into operation Make the control line as short and straight as possible and do not install it in a location where flow may be turbulent Restrictions in the control line can prevent proper pressure registration When using a hand valve it should be a full flow valve such as a full port ball valve Install t...

Page 6: ... outlet pressure or counterclockwise to decrease outlet pressure Always use pressure Overpressure Protection Warning Personal injury equipment damage or leakage due to escaping accumulated gas or bursting of pressure containing parts may result if this regulator is Overpressured Used with incompatible process fluid Installed where service conditions could exceed the limits given in the Specificati...

Page 7: ...y Regulator Technologies should be used for repairing Fisher regulators Restart gas utilization equipment according to normal startup procedures General Maintenance 1 Visually inspect the regulator and its parts for any damage 2 Ensure tight connections tight seals and safe operation If there is an evidence of leakage or unstable internal motion a rebuild with seal replacement and relubrication ma...

Page 8: ...re to be performed is the replacement of the diaphragm components skip to step 11 5 To replace the lever assembly key 16 remove the machine screws key 17 If the only future maintenance procedure to be performed is the replacement of the lever assembly skip to step 10 6 Remove the guide insert key 18 and stem key 14 assembly carefully from the lower casing key 4 Remove the cotter pin key 15 bias sp...

Page 9: ...the spring case key 3 Follow the order below For internal flat circular adjusting screw a control spring key 6 b adjusting screw key 35 For external square head adjusting screw a control spring key 6 b upper spring seat key 19 c closing cap gasket key 25 d closing cap key 22 e locknut key 20 f adjusting screw key 35 15 Turn the adjusting screw key 35 clockwise until there is enough control spring ...

Page 10: ...6 24 23 4 TORQUE 90 to 126 INCH LBS 10 17 TO 14 24 N m TORQUE 90 TO 126 INCH LBS 10 17 TO 14 24 N m 25 46 47 48 1 2 20 19 6 35 22 L2 10 7 45 8 16 17 15 12 L1 30 L1 11 L1 49 15 9 7 50 36 6 38 35 L2 40 39 37 18 14 13 5 TORQUE 14 TO 19 IN LBS 1 6 TO 2 1 N m TORQUE 60 TO 72 INCH LBS 6 78 TO 8 13 N m TORQUE 340 TO 470 INCH LBS 38 41 TO 53 1 N m L2 17A6570 B TYPE Y602 1 VENT SPRING CASE DOWNWARD 17A5515...

Page 11: ...2 Ethylene Propylene Diene EPDM 1B8855X0022 13 Disk Assembly Stainless steel with Nitrile NBR ERSA01112A0 Fluorocarbon FKM ERSA01112A1 Specify the eleven character part number when ordering new parts from the following parts list Key Description Part Number 13 Disk Assembly continued Stainless steel with Perfluoroelastomer FFKM ERSA01112A2 Ethylene Propylene Diene EPDM ERSA01112A3 14 Stem Stainles...

Page 12: ...Bologna 40013 Italy Tel 39 051 419 0611 Chartres 28008 France Tel 33 2 37 33 47 00 TESCOM Emerson Process Management Tescom Corporation USA Headquarters Elk River Minnesota 55330 2445 USA Tels 1 763 241 3238 1 800 447 1250 Europe Selmsdorf 23923 Germany Tel 49 38823 31 287 Asia Pacific Shanghai 201206 China Tel 86 21 2892 9499 For further information visit www fisherregulators com The distinctive ...

Reviews: