S200 Series

4

Overpressure Protection

The recommended pressure limitations are stamped on
the regulator nameplate.  Some type of overpressure
protection is needed if the actual inlet pressure exceeds the
maximum operating outlet pressure rating.  Overpressure
protection should also be provided if the regulator inlet
pressure is greater than the safe working pressure of the
downstream equipment.

Regulator operation below the maximum pressure limitations
does not preclude the possibility of damage from external
sources or debris in the line.  The regulator should be inspected
for damage after any overpressure condition.

Startup

The regulator is factory set at approximately the midpoint of
the spring range or the pressure requested, so an initial
adjustment may be required to give the desired results.   With
proper installation completed and relief valves properly
adjusted, slowly open the upstream and downstream shutoff
valves.

Type VSX-2 Startup

The Type VSX-2 is shipped in the tripped position and will
need to be reset.  If the Type VSX-2 is a high trip only, it can be
reset before starting the regulator.  If the Type VSX-2 is a high
and low trip, the regulator will have to be started and the
downstream system pressurized before the Type VSX-2 can
be reset.

Adjustment

To change the outlet pressure, remove the closing cap or
loosen the locknut and turn the adjusting screw clockwise
to increase outlet pressure or counterclockwise to decrease
pressure.  Monitor the outlet pressure with a test gauge
during the adjustment.  Replace the closing cap or tighten
the locknut to maintain the desired setting.

Type VSX-2 Trip Adjustment

Note

An adjustment tool is included with the Type VSX-2.
Use only this tool to make adjustments to the unit.
To make adjustments, the overpressure trip spring
is found under the outer adjusting screw and the
underpressure trip spring is found under the inner
adjusting screw.

To adjust the Overpressure Trip Spring:

1. Adjust the overpressure trip setting to its maximum

compression.

2. If present, adjust the underpressure spring to its

minimum compression.

3. Backpressure the unit with the desired trip pressure.

4. Reduce the overpressure trip spring compression until

the Type VSX-2 trips.

To adjust the Underpressure Trip Spring:

1. Adjust the underpressure trip spring back to its minimum

compression.

2. Backpressure the unit with the desired trip pressure.

3. Increase the underpressure trip spring compression until

the Type VSX-2 trips.

Taking Out of Service (Shutdown)

To avoid personal injury resulting from sudden
release of pressure, isolate the regulator from all
pressure before attempting disassembly.

Figure 1. 

 Minimum Inlet Pressure Required to Prevent Shutoff

on all Sizes of S204, S204H, S206, and S206H Regulators at
Indicated Flow

FLOW RATE, SCFH OF 0.6 SPECIFIC GRAVITY NATURAL GAS

FLOW RATE, m

3

/h(n) OF 0.6 SPECIFIC GRAVITY NATURAL GAS

50

40

30

20

10

0

3.0

2.0

1.0

0

0

1000

2000

3000

4000

5000

6000

7000

8000

MINIMUM INLET PRESSURE, PSIG

MINIMUM INLET PRESSURE, 

bar

0

26.8

53.6

80.4

107

134

160

188

214

1-INCH (25,4 mm)
SEAT RING

1/2-INCH (12,7 mm)
SEAT RING

5/8-INCH (15,9 mm)
SEAT RING

1-3/16-INCH (30,2 mm)
SEAT RING

Summary of Contents for Fisher S200 Series

Page 1: ...S202H constructions with a low outlet pressure shutoff with internal relief Available in Cast iron body only S208 S208H S208P S208K S208PK S201 S201H S201P S201K and S201PK constructions with a Type VSX 2 slam shut device to provide over pressure OPSO or over and underpressure UPSO protection Available in Ductile iron body only S209 S209H S209P S202 S202H and S202P constructions with a Type VSX 2 ...

Page 2: ... u n e h t d n a g n i r p s r o t i n o m n o i t c u r t s n o c r o t i n o m e h t f o n o i t c n u f a e r a s e g n a r e r u s s e r p t e l t u o H 3 0 2 S d n a 3 0 2 S s e p y T 1 h c n i 1 r a b m 5 2 y b d e c u d e r e b n a c e g n a r e r u s s e r p t e l t u o f o d n e r e w o l m o t t o b n o s i g n i r p s l o r t n o c o s d e l l a t s n i f I m g a r h p a i d f o p o t n...

Page 3: ...dule into the regulator body Secure theType VSX 2 to the regulator body with the four set screws key 4 The unit may be oriented in any direction with respect to the sensor line connection S E G N A R T N I O P T E S E P Y T T U H S M A L S G N I R P S E V L A V N I A M H T I W E S U R E B M U N 1 M U M I X A M O T M U M I N I M E R U S S E R P P I R T f f o t u h S e r u s s e r p r e v O O S P O ...

Page 4: ...outlet pressure with a test gauge during the adjustment Replace the closing cap or tighten the locknut to maintain the desired setting Type VSX 2 Trip Adjustment Note An adjustment tool is included with the Type VSX 2 Use only this tool to make adjustments to the unit To make adjustments the overpressure trip spring is found under the outer adjusting screw and the underpressure trip spring is foun...

Page 5: ...elf Tapping Screw 60 Spring 61 Screen 62 Snap Ring Figure 2 Type S202 Assembly Figure 3 Type S206 Assembly Type S204 and S206 Parts List Key Description 1 Spring Case 2 Spring 3 Adjusting Screw 4 Closing Cap 5 Closing Cap Gasket 6 Lower Spring Seat 7 Diaphragm Head Assembly 7A Diaphragm 8 Pusher Post S204 8 Ball Stem Assembly S206 9 Lower Casing Assembly 10 Lever 11 Pin 12 Machine Screw 13 Valve S...

Page 6: ...time without notice Printed in U S A www FISHERregulators com T80390 A2 B2517 2 T80388 C B2508 2 T80388 C B2495 2 Figure 4 Type S209 Assembly Type S208 and S209 Parts List Key Description 1 Spring Case 2 Spring 3 Adjusting Screw 4 Closing Cap 5 Closing Cap Gasket 6 Lower Spring Seat 7 Diaphragm and Diaphragm Head 8 Pusher Post 9 Lower Casing Assembly 10 Lever 11 Pin 12 Machine Screw 13 Valve Stem ...

Reviews: