background image

Instruction Manual

D103687X012
June 2018

Type OSE

Slam-Shut Valve

CONTENTS

Introduction  ........................................................................ 

1

Characteristics  ................................................................... 1
Labelling ............................................................................. 

2

Dimensions and Weights  ................................................... 

3

Operation  ........................................................................... 

4

Installation .......................................................................... 

4

Commissioning  .................................................................. 

5

Maintenance  ...................................................................... 

6

Spare Parts ........................................................................ 

7

Figure 1.

 Type OSE Slam-Shut Valve

The Type 

OSE 

is in conformity with the

Pressure Equipment Directive PED 2014/68/UE

and is classified under category IV.

CharaCTEriSTiCS

Material

Body Steel
Bonnet  

Steel

Orifice  

Stainless steel

Valve plug  

Stainless steel

O-rings  

Nitrile

Connections

Inlet/Outlet:  

ISO PN 100 B (ANSI 600 RF)

 

ISO PN 50 B (ANSI 300 RF)

 

ISO PN 20 B (ANSI 150 RF)

 

Other connections available

 

(contact factory)

 

ISO PN 16 B, 25 B, 40 B

Impulse (IS):  

1/4’’ NPT threaded

Mechanism box vent (E):   1/4” NPT threaded
Impulse diameter:  

Tube interior Ø 8/10 mm

Safety contact:  

See D103683X012 manual

iNTrODUCTiON

Scope of the Manual

This manual provides installation, start-up, maintenance, 

and parts ordering information for the Type OSE 

Slam‑Shut Valve. 

Information on other equipment used with this slam-shut 

valve is found in separate manuals.

Product Description

The Type 

OSE

 Slam‑Shut Valve protects transmission and 

distribution networks or pipe lines supplying industries and 

commercial businesses.

It permits the gas flow to be cut off rapidly and totally in the 

case of under or over regulator pressure.

The Type OSE exists in DN 25 (1”) to DN 150 (6”).  

DN 200 (8”) and DN 250 (10”) are covered by the Type OSE LS.

The Type OSE consists of:

•  A body with a removable orifice, enclosed by a bonnet

• 

A valve plug with integral bypass, tightshut by an O-ring

• 

A release relay type OS2 including:

 - A mechanism box (BM)

 - A safety manometric box (BMS) to be connected on 

the outlet side of the pressure regulator.

Summary of Contents for Fisher OSE

Page 1: ...interior Ø 8 10 mm Safety contact See D103683X012 manual INTRODUCTION Scope of the Manual This manual provides installation start up maintenance and parts ordering information for the Type OSE Slam Shut Valve Information on other equipment used with this slam shut valve is found in separate manuals Product Description The Type OSE Slam Shut Valve protects transmission and distribution networks or ...

Page 2: ...bel Figure 2 Accuracy AG 2 5 5 Piston Setpoint range Wdu Wdo 0 010 à 100 bar Response time ta 1 s Max Differential valve closed P max 100 bar Max Differential valve open P max See Table 2 Rearming Manually after rectification of fault Position indicator On mechanism box Fluid Group 1 and 2 according to PED 2014 68 UE 1st and 2nd family gas according to EN 437 or other gases compressed air nitrogen...

Page 3: ...0 62 334 220 124 17 50 20 150 254 76 346 220 152 26 50 300 267 83 346 220 165 29 100 600 287 83 346 220 165 32 80 20 150 298 95 380 220 190 43 50 300 318 105 380 220 210 48 100 600 337 105 380 220 210 55 100 20 150 353 114 420 220 229 74 50 300 368 127 420 220 154 82 100 600 394 137 420 220 273 98 150 20 150 451 140 424 220 357 150 50 300 473 159 424 220 357 166 100 600 508 178 424 220 357 202 C53...

Page 4: ...e of Operation The slam shut valve is installed on the inlet side of the regulator on the horizontal pipeline The mechanism box should be situated on top see above schematic or on top for versions DN 25 50 80 Installation according to EN12186 is recommended Install according to direction of the fluid flow see arrow When assembling with adjacent elements care must be taken not to create pressure fo...

Page 5: ...be checked periodically commissioning warning All interventions on the equipment should only be performed by qualified and trained personnel Preliminary verifications Start up positions Inlet and outlet valves Closed Verify absence of pressure between inlet and outlet valves Slam shut valve plug Closed Impulse isolation valve Closed Impulse atmospheric valve Open Setpoint Verification Using the at...

Page 6: ...operating conditions In the case of BMS 162 or 071 it is highly recommended to check the condition of the diaphragm once yearly Verification Condition of O rings diaphragm and lubrication Replacement O rings diaphragm Tools Spanners 10 13 six sided wrench 6 Spanners According to DN size Emerson spanner ref 197125 bypass and pin disassembly Valve plug closed Close inlet and outlet valves Bleed off ...

Page 7: ...ve closes Operating correctly Observe the evolution of the outlet pressure check tightness If the outlet pressure in the slam shut is decreases External leak Locate and seal the leak or contact after sales If the outlet pressure in the slam shut is constant Bleed off the outlet side of the regulator Observe the evolution of the outlet pressure check tightness If the outlet pressure increases Inter...

Page 8: ...implied regarding the products or services described herein or their use or applicability All sales are governed by our terms and conditions which are available on request We reserve the right to modify or improve the designs or specifications of our products at any time without notice Emerson Process Management Regulator Technologies Inc does not assume responsibility for the selection use or mai...

Reviews: