background image

www.Fisher.com

Fisher

 FIELDVUE

 DVC6200p DTM with

PACT

ware

 4.1

This document takes your through establishing a connection to PROFIBUS PA device DVC6200p in Pact

ware

 4.1

through PROFIusb USB and the installation of the supported DTM.

Notes

The information found in this document can also be used to establish connections to FieldCare™ and FieldMate configuration
tools.

Refer to the DVC6200 Series Quick Start Guide, 

D103556X012

, for DVC6200p installation, connection, and initial configuration

information and the DVC6200p Instruction Manual, 

D103563X012

, for all other information pertaining to the DVC6200p digital

valve controller, including product specifications, reference materials, custom setup information, maintenance procedures, and
replacement part details.

DTM Supported:

DVC6200p_Profibus_DTM

Assumptions and Supported Environment:

The following software and hardware should be installed prior to launching the DVC6200p DTM in PACT

ware

 4.1.

S. No

System

Version

Reference Link

1

PD to PA Coupler (Pepperl and Fuchs)

Compact PROFIBUS
Power Hub and Segment
Coupler KT-MB-GTB-2PS

http://www.pepperl-fuchs.u
s/usa/en/classid_1482.htm?
view=productdetails&prodid
=36114

2.

PROFIusb USB

H/W V1.03
Driver Ver. 5.45.11

Drivers included with
CD/DVD when purchased

3.

PROFIBUS CommDTM

FROFIdtm

PROFIbus DTM

4.

Pactware 4.1

Ver 4.1

PACT

ware

 4.1 from

pepperl-fuchs

Instruction Manual Supplement

D104172X012

DVC6200p Digital Valve Controller

November 2017

Summary of Contents for Fisher FIELDVUE DVC6200p

Page 1: ... controller including product specifications reference materials custom setup information maintenance procedures and replacement part details DTM Supported DVC6200p_Profibus_DTM Assumptions and Supported Environment The following software and hardware should be installed prior to launching the DVC6200p DTM in PACTware 4 1 S No System Version Reference Link 1 PD to PA Coupler Pepperl and Fuchs Comp...

Page 2: ...mber 2017 2 Profibus PA Device DP PA Coupler PROFIusb USB Pactware 4 1 PROFIdtm PACTware 4 1 PROFIdtm 2 11 DEVICE DVC6200p TEST PC 24V POWER P F DP PA COUPLER PROFIusb Note Driver for PROFIusb should be installed and configured as shown in the figure below before launching the DTM ...

Page 3: ... 2017 3 Installing the DTM 1 Download the DVC6200p_Profibus_DTM and exact the folder Navigate to setup exe in the extracted folder 2 Right click on setup exe and click Run as administrator from the context menu 3 DVC6200p device DTM installation will start as shown in the figure below ...

Page 4: ...Instruction Manual Supplement D104172X012 DVC6200p Digital Valve Controller November 2017 4 4 Click Next as indicated below 5 Accept the terms in the license agreement and click Next ...

Page 5: ... Manual Supplement D104172X012 DVC6200p Digital Valve Controller November 2017 5 6 Select Complete and click Next to continue with the installation 7 Click Install to begin installation of the DVC6200p Device DTM ...

Page 6: ...Instruction Manual Supplement D104172X012 DVC6200p Digital Valve Controller November 2017 6 8 Click Finish to complete the installation 9 The DVC6200p Device DTM is now installed on your machine ...

Page 7: ... D104172X012 DVC6200p Digital Valve Controller November 2017 7 Launching the DVC6200p DTM in PACTware 4 1 1 Go to All Programs and select PACTware 4 1 2 Right click on HOST PC and select Add device as shown in the following figure ...

Page 8: ...l Supplement D104172X012 DVC6200p Digital Valve Controller November 2017 8 3 Select PROFIdtm DPV1 and click OK as shown below 4 PROFIdtm is added as a project 5 Right click on PROFIdtm and select Connect as shown below ...

Page 9: ... 6 Select Parameter from the drop down menu see previous page and enter the Baud Rate Enter 93 75 k Bit s for the P F Coupler and 45 45 k Bit s for the Siemens Coupler 7 The PROFIBUS communication DTM is now connected as confirmed by the green connection status icon shown in the figure below ...

Page 10: ...uction Manual Supplement D104172X012 DVC6200p Digital Valve Controller November 2017 10 8 Right click on the PROFIdtm and select Topology Scan 9 Click the Blue Arrow in the resulting window to start the scan ...

Page 11: ...72X012 DVC6200p Digital Valve Controller November 2017 11 10 The scan is in Progress Please wait 11 After the scan is completed the device DVC6200p_DTM is added to the Scan Tree as shown below Click Close to exit the Toplogy Scan window ...

Page 12: ...ment D104172X012 DVC6200p Digital Valve Controller November 2017 12 12 Right click on DVC6200P_DTM and click Connect 13 The DVC6200p DTM is now connected denoted by the green Connection Status icon as shown in the figure below ...

Page 13: ...172X012 DVC6200p Digital Valve Controller November 2017 13 14 Right click on the device and select Parameter Online Parameterization Parameterize 15 The device DVC6200P_DTM Parameterization is now launched in PACTware4 1 as shown below ...

Page 14: ...200p Digital Valve Controller November 2017 14 Changing the Device Address 1 Confirm the PROFIBUS communication DTM is connected as indicated by the green connection status icon 2 Right click PROFIdtm and select Additional functions Show Live List ...

Page 15: ...l Supplement D104172X012 DVC6200p Digital Valve Controller November 2017 15 3 Right click the selected device in the Live List and select Set Device Station Address Type the desired address in New Address and click Set ...

Page 16: ...and conditions which are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice E 2016 2017 Fisher Controls International LLC All rights reserved Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co Emerson Automation Solutions Emerson and the Emers...