DVC6000f Digital Valve Controllers
December 2009
4-8
Table 4-2. Parameters Affected by Restart with Defaults
Index
Number
Parameter Name
Initial Value
Resource Block
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
0
spaces
0
0
5
MODE_BLK
TARGET
PERMITTED
NORMALE
Auto
Auto or Out of Service
Auto
14
18
20
GRANT_DENY
FEATURE_SEL
CYCLE_SEL
All bits: 0
Set by mfgr.
0:0
26
27
28
SHED_RCAS
SHED_ROUT
FAULT_STATE
640000
640000
1=Clear
32
33
34
37
LIM_NOTIFY
CONFIRM_TIME
WRITE_LOCK
ALARM_SUM
DISABLED
MAX_NOTIFY
640000
1=Unlocked
All bits: 0
38
39
ACK_OPTION
WRITE_PRI
Disabled
0
AO Block
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
0
spaces
0
0
5
8
9
MODE_BLK
TARGET
PERMITTED
NORMAL
SP
OUT
Out of Service
OOS+MAN+AUTO+CAS+RCAS
Auto
Dynamic
Dynamic
11
PV_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
100
0
%
2
12
14
15
XD_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
IO_OPTS
STATUS_OPTS
100
0
%
2
All off
All off
17
18
19
20
21
22
CAS_IN
SP_RATE_DN
SP_RATE_UP
SP_HI_LIM
SP_LO_LIM
CHANNEL
BAD:
NC:
const
0
+INF
+INF
100
0
1=analog valve input
−
Continued
−
Table 4-2. Parameters Affected by Restart with Defaults
(Continued)
Index
Number
Parameter Name
Initial Value
AO Block (continued)
23
24
26
27
FSTATE_TIME
FSTATE_VAL
RCAS_IN
Status
Value
SHED_OPT
0
0
BAD:
NoComm:
NoVal:
const
0 Trk
All off
PID Block Parameters
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
0
spaces
0
0
5
8
9
MODE_BLK
TARGET
PERMITTED
NORMAL
SP
OUT
Out of Service
OOS+MAN+AUTO+CAS+
RCAS+ROUT
Auto
Dynamic
Dynamic
10
PV_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
100
0
%
2
11
13
14
OUT_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
CONTROL_OPTS
STATUS_OPTS
100
0
%
2
0: Bypass enable
All off
15
16
IN
Status
Value
PV_FTIME
BAD:
NC:
const
0
0
17
18
19
20
21
BYPASS
CAS_IN
Status
Value
SP_RATE_DN
SP_RATE_UP
SP_HI_LIM
0
BAD:
NC:
const
0
+INF
+INF
100
22
23
24
25
26
27
SP_LO_LIM
GAIN
RESET
BAL_TIME
RATE
BKCAL_IN
Status
Value
0
1
+INF
0
0
BAD:
NC:
const
0
−
Continued
−
4
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...