Introduction and Specifications
December 2009
1-7
Table 1-1. Specifications (continued)
Options
Supply and output pressure gauges or
Tire
valves,
Integral mounted filter regulator,
Stainless steel housing, module base and
terminal box (valve-mounted instruments only),
Low bleed relay,
Inline 10 micron air filter
Declaration of SEP
Fisher Controls International LLC declares this
product to be in compliance with Article 3 paragraph
3 of the Pressure Equipment Directive (PED) 97 /
23 / EC. It was designed and manufactured in
accordance with Sound Engineering Practice (SEP)
and cannot bear the CE marking related to PED
compliance.
However, the product may bear the CE marking to
indicate compliance with other applicable European
Community Directives.
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1
−
Process Instrument Terminology.
1. 3-conductor shielded cable, 22 AWG minimum wire size, is required for connection between base unit and feedback unit. Pneumatic tubing between base unit output connection and actuator
has been tested to 15 meters (50 feet) maximum without performance degradation.
2. The pressure/temperature limits in this manual and any applicable code or standard should not be exceeded.
3. Gas Certified DVC6000f digital valve controllers are FM and CSA Single Seal approved for use with natural gas as the supply medium.
4. Normal m
3
/hour
−
Normal cubic meters per hour at 0
C and 1.01325 bar, absolute. Scfh
−
Standard cubic feet per hour at 60
F and 14.7 psia.
5. Values at 1.4 bar (20 psig) based on a single-acting direct relay; values at 5.5 bar (80 psig) based on double-acting relay.
6. Typical value. Not applicable for travels less than 19 mm (0.75 inch) or for shaft rotation less than 60 degrees. Also, not applicable to DVC6020f digital valve controllers in long-stroke
applications.
7 . Do not use the DVC6010fS or DVC6020fS in high vibration service where the mounting bracket uses standoffs (spacers) to mount to the actuator. Due to NAMUR mounting limitations,
do not use the DVC6030fS in high vibration service.
Table 1-2. EMC Summary Results—Immunity
Port
Phenomenon
Basic Standard
Test Level
Performance Criteria
(1)
Enclosure
Electrostatic discharge (ESD)
IEC 61000-4-2
4 kV contact
8 kV air
A
Radiated EM field
IEC 61000-4-3
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
A
Rated power frequency
magnetic field
IEC 61000-4-8
60 A/m at 50 Hz
A
I/O signal/control
Burst
IEC 61000-4-4
1 kV
A
Surge
IEC 61000-4-5
1 kV (line to ground only, each)
B
Conducted RF
IEC 61000-4-6
150 kHz to 80 MHz at 3 Vrms
A
1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering.
1
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Page 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...