Transducer Block
December 2009
4-49
Table 4-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial Value
Range
Mode
RO /
RW
Index
Number
PRESS_CAL
46
Supply Pressure Scale
SUPP_PRESS_SCALE
46.1
RW
MAN
OOS
>
0
CAL
Data Type: Float
Supply Pressure Offset
SUPP_PRESS_OFFSET
46.2
RW
MAN
OOS
0 to 16383
CAL
Data Type: Uint16
Pressure A Scale
PRESS_A_SCALE
46.3
RW
MAN
OOS
>
0
CAL
Data Type: Float
Pressure A Offset
PRESS_A_OFFSET
46.4
RW
MAN
OOS
0 to 16383
CAL
Data Type: Uint16
Pressure B Scale
PRESS_B_SCALE
46.5
RW
MAN
OOS
>
0
CAL
Data Type: Float
Pressure B Offset
PRESS_B_OFFSET
46.6
RW
MAN
OOS
0 to 16383
CAL
Data Type: Uint16
Pressure IP Bias
PRESS_IP_BIAS
46.7
RW
MAN
OOS
0
−
100%
70%
CAL
Data Type: Float
Pressure MLFB Bias
PRESS_MLFB_BIAS
46.8
RW
MAN
OOS
0
−
100%
50%
CAL
Data Type: Float
PRESS_TUNE
47
Pressure Cutoff Hi
PRESS_CUTOFF_HI
47.1
RW
MAN
OOS
−
25
−
125%,
>
CUTOFF_LO
99.50%
SETUP
Data Type: Float
Pressure Cutoff Lo
PRESS_CUTOFF_LO
47.2
RW
MAN
OOS
−
25
−
125%
<
CUTOFF_HI
0.50%
SETUP
Data Type: Float
Pressure Proportional Gain
PRESS_PROP_GAIN
47.3
RW
MAN
OOS
>
= 0,
<
32
2.2
SETUP
Data Type: Float
Proportional gain
Pressure Integral Gain
PRESS_INTEG_GAIN
47.4
RW
MAN
OOS
>
= 0,
<
32
0.1
SETUP
Data Type: Float
Integral resets per second
Pressure Rate Gain
PRESS_RATE_GAIN
47.5
RW
MAN
OOS
>
= 0,
< =
512
0
SETUP
Data Type: Float
Derivative gain
Pressure Integral Dead Zone
PRESS_INTEG_DEADZ
47.6
RW
MAN
OOS
= 0%,
<
= 2.0%
0.25%
SETUP
Data Type: Float
Integrator Deadzone, 1/2 width
Pressure Integral Limit Hi
PRESS_INTEG_HI_LIM
47.7
RW
MAN
OOS
>
= 0%,
<
= 100%,
>
INTEG_LO
20%
SETUP
Data Type: Float
Integrator limits
Pressure Integral Limit LO
PRESS_INTEG_LO_LIM
47.8
RW
MAN
OOS
<
= 0%,
>
=
−
100%,
<
INTEG_HI
−
20%
SETUP
Data Type: Float
Integrator limits
Pressure Integral IC Hi
PRESS_INTEG_IC_HI
47.9
RW
MAN
OOS
>
=
−
100%,
<
= 100%
12%
Not used by the DVC6000f
Pressure Integral IC Lo
PRESS_INTEG_IC_LO
47.10
RW
MAN
OOS
>
=
−
100%,
<
= 100%
−
12%
Not used by the DVC6000f
Pressure MLFB Gain
PRESS_MLFB_GAIN
47.11
RW
MAN
OOS
>
0,
<
= 100
35
SETUP
Data Type: Float
Temperature
TEMPERATURE
48
RO
N/A
N/A
N/A
Data Type: Float
Electronics temperature
−
Controls
AI channel 11
Target Travel
TRAVEL_TARGET
49
RO
Status
STATUS
49.1
RO
MAN
OOS
N/A
Data Type: DS-65
In Travel Control: Setpoint for valve
travel in %, post characterization.
In Pressure Control: Setpoint for
implied valve travel as a % or
pressure range, post
characterization.
Value
VALUE
49.2
RO
MAN
OOS
N/A
Input Characterization
INPUT_CHAR
50
RW
MAN
OOS
1=Linear
2=Equal %
3=Quick Opening
4=Reserved
5=Custom
1=Linear
SETUP
Data Type: Enum (Uint8)
−
Continued
−
4
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Page 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...