![Emerson Fisher FIELDVUE DVC6000f Instruction Manual Download Page 100](http://html.mh-extra.com/html/emerson/fisher-fieldvue-dvc6000f/fisher-fieldvue-dvc6000f_instruction-manual_102337100.webp)
DVC6000f Digital Valve Controllers
December 2009
4-40
Table 4-10. Output Block PV Status
FEATURE_SEL
PW Alarms Set PV Status
Transducer Mode,
Actual
Active PlantWeb
Alarms
AO / DO
PV Status
(2)
AO / DO
PV Substatus
AO/DO PV
Limit Substatus
(1)
Enabled
OOS
X
Bad
Device Failure
Constant
Man
X
Bad
Non-specific
Constant
Auto
Fail
Uncertain
Subnormal
Auto
Maintenance, no Fail
Uncertain
Non-specific
Auto
Advisory, no Fail, no
Maintenance
Good
Advisory
Auto
None
Good
Non-Specific
Not Enabled
OOS
X
Bad
Device Failure
Constant
Man
X
Bad
Non-Specific
Constant
Auto
Fail
Good
Non-Specific
Auto
Maintenance, no Fail
Good
Non-Specific
Auto
Advisory, no Fail, no
Maintenance
Good
Non-Specific
Auto
None
Good
Non-Specific
NOTES:
X
=
No Effect
1. PV limit substatus reflects only READBACK limit substatus. SP limit substatus reflects only out block rate limits.
2. Firmware Revision 1.1 and earlier will set AO/DO PV Status to Bad if Feedback Sensor has failed, ie; Travel Sensor Fail. However, if the Travel Sensor fails, and the instrument
falls back to pressure, PV Status will remain good.
Table 4-11. Limit Sub Status
Out
Block
Transducer
Mode
In Cutoff
Region
Rate
Limited
Limit
Sub-Status
AO, DO
OOS
X
X
Constant
AO, DO
MAN
X
X
Constant
AO
AUTO
High
X
High Limited
AO
AUTO
Low
X
Low Limited
AO
AUTO
X
High
High Limited
AO
AUTO
X
Low
Low Limited
AO
AUTO
None
None
Not Limited
DO
AUTO
X
High
High Limited
DO
AUTO
X
Low
Low Limited
DO
AUTO
X
None
Not Limited
NOTE: X
=
No Effect
Alert Handling
(TB
>
Configure/Setup
>
Detailed Setup
>
Alert
Handling)
PlantWeb Alert Simulate
When enabled, PlantWeb Alert Simulate
(PWA_SIMULATE [39])
allows the user to write to the
following PlantWeb and Instrument alert parameters;
Failed Active, Maintenance Active, Advise Active,
Environment Active, Travel Active, Proximity Active,
Travel History Active, Performance Active, PD Event
Active, PD Detail 1 Active, PD Detail 2 Active, PD
Detail 3 Active, PD Detail 4 Active, PD Detail 5 Active,
PD Detail 6 Active. This provides a way to simulate
these alerts for testing. In order to enable PWA
Simulate, the Aux Terminal must be jumpered.
PlantWeb Alert Simulate is cleared on a power cycle.
It can also be cleared manually, or by removing the
Aux terminal jumper.
Simulate Active Alerts
Failed Active
Permits simulating an active Failed alarm
(FAILED_ACTIVE [59]).
Maintenance Active
Permits simulating an active Maintenance alarm
(MAINT_ACTIVE [60]).
Advise Active
Permits simulating an active Advisory alarm
(ADVISE_ACTIVE -[61]).
PlantWeb Alert Handling
PlantWeb Alerts Set PV Status
When selected, PlantWeb alerts will set the PV status
according to table 4-10.
Block Error Reporting
When enabled, the AO or DO BLOCK_ERR [6]
parameter will report PlantWeb Alerts. the same as
Block Error in the resource block.
Block Error bit 6 (Device Needs Maintenance Soon)
will report any active PlantWeb Maintenance Alert.
Block Error bit 13 (Device Needs Maintenance Now)
will report any active PlantWeb Failed Alert.
4
Summary of Contents for Fisher FIELDVUE DVC6000f
Page 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Page 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Page 127: ...Transducer Block December 2009 4 67 4 ...
Page 141: ...AO Function Block December 2009 4 81 4 ...
Page 207: ...MAI Function Block December 2009 4 147 4 ...
Page 219: ...DO Function Block December 2009 4 159 4 ...
Page 231: ...DI Function Block December 2009 4 171 4 ...
Page 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Page 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Page 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Page 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Page 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Page 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...