Local Control
This procedure allows the user to manually control the
position of the valve (see figure 3-9). To enter this
procedure from the home screen, press the DOWN
(
) arrow key seven times and then press the RIGHT
(
) arrow key.
If you select ANALOG, you will return to the home
screen and the digital valve controller will respond to
the loop current. If you select MANUAL, you will move
to the screen that shows the travel setpoint and the
actual valve travel. The UP (
) and DOWN (
) arrow
keys will allow you to change the setpoint and
therefore move the valve manually. To exit the manual
mode, use the LEFT (
) arrow key to return to the
choice list. Select ANALOG.
Note
When placing the instrument back into
ANALOG, the valve will step back to
the position commanded by the input
current.
TUNING
TRAVEL = 66.8%
14.6 MA 0.92 BAR
QUICK SETUP
TRAVEL
CALIBRATION
DETAILED SETUP
ANALOG
MANUAL
MANUAL SP = XXX
TRAVEL = XXX
CONTROL
ANALOG
POSITION
TRANSMIITTER CAL
ANALOG INPUT
CALIBRATION
LOCAL
CONTROL
Only with Optional
Position Transmitter /
Limit Switches
Figure 3-9. Local Control
3
Summary of Contents for Fisher FIELDVUE DVC2000
Page 40: ...DVC2000 Digital Valve Controller July 2009 3 14 3 ...
Page 70: ...DVC2000 Digital Valve Controller July 2009 6 10 6 ...
Page 71: ...Parts July 2009 7 1 7 7 Section 7 Parts Parts Ordering 7 2 Parts Kits 7 2 Parts List 7 2 7 ...
Page 80: ...DVC2000 Digital Valve Controller July 2009 A 4 A ...
Page 104: ...DVC2000 Digital Valve Controller July 2009 Index 8 C Index ...
Page 105: ......