Introduction and Specifications
July 2009
1-5
Table 1-1. Specifications (continued)
Connections
Standard
Supply and Output Pressure: G1/4 internal
Electrical: M20 internal
Optional
Supply and Output Pressure: 1/4 NPT internal
Electrical: 1/2 NPT internal
Materials of Construction
Housing and Cover: ASTM B85 A03600 low copper
aluminum alloy
Elastomers: nitrile, fluorosilicone
Stem Travel
Minimum: 8 mm (0.3125 inch)
Maximum: 102 mm (4 inches)
Shaft Rotation
Minimum: 45
Maximum: 90
Mounting
Designed for direct actuator mounting. For
weatherproof housing capability, the vent must be
positioned at the lowest point of the instrument.
Weight
1.5 kg (3.3 lbs)
Options
Airset: 67CFR with filter
Language Packs:
Standard: English, German, French, Italian,
Spanish, Japanese, Chinese, Portuguese, Russian,
Polish, and Czech
Optional: English, German, French, Italian,
Spanish, Japanese, Chinese, and Arabic
Pipe-away vent
Limit Switches: Two isolated switches,
configurable throughout calibrated travel range
Supply Voltage: 5-30 VDC
OFF State: 0.5 to 1.0 mA
ON State: 3.5 to 4.5 mA (above 5 V)
Reference Accuracy: 2% of travel span
(5)
Transmitter: 4-20 mA output, isolated
Supply Voltage: 8-30 VDC
Fault Indication: offrange high or low
Reference Accuracy: 1% of travel span
(5)
Declaration of SEP
Fisher Controls International LLC declares this
product to be in compliance with Article 3 paragraph
3 of the Pressure Equipment Directive (PED) 97 /
23 / EC. It was designed and manufactured in
accordance with Sound Engineering Practice (SEP)
and cannot bear the CE marking related to PED
compliance.
However, the product may bear the CE marking to
indicate compliance with other applicable European
Community Directives.
1. The pressure/temperature limits in this document and any applicable standard or code limitation should not be exceeded. Note: Temperature limits vary based on hazardous area approval.
2. Normal m
3
/hour
−
Normal cubic meters per hour at 0
C and 1.01325 bar, absolute. Scfh
−
Standard cubic feet per hour at 60
F and 14.7 psia.
3. Low pressure relay: 0 to 3.4 bar (0 to 50 psig).
4. High pressure relay: 3.5 to 7.0 bar (51 to 102 psig).
5. Typical values when calibrated at temperature.
Table 1-2. EMC Summary Results—Immunity
PORT
PHENOMENON
BASIC STANDARD
TEST LEVEL
PERFORMANCE
CRITERIA
(1)
Enclosure
Electrostatic discharge
(ESD)
IEC 61000-4-2
4 kV contact
8 kV air
B
Radiated EM field
IEC 61000-4-3
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
A
Rated power frequency
magnetic field
IEC 61000-4-8
30 A/m at 50 Hz, 60 sec
A
I/O signal/control
Burst (fast transients)
IEC 61000-4-4
$
1 kV
A
Surge
IEC 61000-4-5
$
1 kV (line to ground only, each)
B
Conducted RF
IEC 61000-4-6
150 kHz to 80 MHz at 4 Vrms
A
Performance criteria is + /
−
1% effect.
1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering.
1
Summary of Contents for Fisher FIELDVUE DVC2000
Page 40: ...DVC2000 Digital Valve Controller July 2009 3 14 3 ...
Page 70: ...DVC2000 Digital Valve Controller July 2009 6 10 6 ...
Page 71: ...Parts July 2009 7 1 7 7 Section 7 Parts Parts Ordering 7 2 Parts Kits 7 2 Parts List 7 2 7 ...
Page 80: ...DVC2000 Digital Valve Controller July 2009 A 4 A ...
Page 104: ...DVC2000 Digital Valve Controller July 2009 Index 8 C Index ...
Page 105: ......