background image

F180 Series

3

components in the piping system create restrictions 

which reduce the flow rating to less than that of the 

excess flow valve rating, the valve will not give excess 

flow protection, and additional excess flow valves must 

be installed at these points.

  2.  Brass valves are not suitable for anhydrous 

    ammonia (NH

3

) applications.

  3.  Manually operate the excess flow valve’s poppet

       before installation to assure parts were not 

       damaged in shipment or blocked with dirt or 

    foreign material.

  4.  Use pipe dope on the male threads of the valve or

       the pipeline.  Polytetrafluoroethylene (PTFE) tape 

       or PTFE pipe dope compound is recommended for 

     the male threads of the larger valves such as the 

       2 and 3-inch sizes.

  5.

 

After the excess flow valve is installed, the system

       should be tested for excess flow valve operation 

       by simulating a break downstream in the system 

       at the furthermost point being protected.  To test 

       the unit, pressure the system and then open a 

       shutoff valve quickly at the farthest point in the 

       piping that the excess flow valve is intended to 

       protect.  There should be a sudden decrease in 

       flow, indicating that the valve has closed and is 

       working properly.  Because of the bleed that 

       permits the valve to equalize itself, a small amount 

       of leakage will continue after the excess flow 

       check closes.

  6.  To reopen a closed excess flow valve, close a 

       shutoff valve on either the upstream or 

       downstream piping.  When pressure is equal on 

       both sides of the valve, it will “click” open and flow 

       can be resumed by opening the shutoff valve.

!

WARNING

Trained personnel should test the 

excess flow valve in a safe location. 
Excess flow closure should be checked 

annually or on a regularly scheduled 

basis to insure that the valve is 

still functional.

Maintenance

Excess flow valves are non-repairable.  Replace 

non-functioning valves.

Troubleshooting

If the excess flow valve fails to close

 – check 

the following:

  1.  Flow direction is the same direction as

       arrow stamped on the valve.

  2.  Shut off valves on the inlet and outlet of the 

       piping are fully open.

  3.  Restrictions on the inlet or outlet of the excess 

       flow valve are restricting flow into or out of 

    the valve.

  4.  Flow capacity at point of test is not great enough 

       to close the excess flow valve.

  5.  Pipe scale, welding slag, or other debris is holding 

       the valve open.

Premature closing or valve chattering

 – check 

the following:

  1.  Surge conditions – Increase flow slowly to 

       prevent surge.  A larger excess closing flow may 

       be required.

  2.  Chattering – Normal flow conditions may be too 

       near to the closing flow rate, or flow direction is

       wrong or back flowing is occuring.

  3.  Restriction on inlet of valve.

!

WARNING

Back flowing or flowing too near to the 

excess flow valve closing rate may cause 

chattering which may result in excessive 

wear on parts and valve failure.

Summary of Contents for FISHER F180 Series

Page 1: ... standards and regulations of the applicable industries should install and service this equipment WARNING A break or leak downstream of an excess flow valve that does not allow a flow equal to the valve flow rating will not actuate the excess flow valve and could result in property damage or personal injury from a whipping hose or high volume discharge of air For this reason the operator must be f...

Page 2: ...lves is to choose a valve with a closing flow 1 5 times the maximum operating flow For surge conditions 2 times maximum flow may be required However the excess flow valve s closing flow rate must be less than the capacity of the compressed air system in which the valve is being used The flow rating of the piping fittings pump valves and hose on both the inlet and outlet of the excess flow valve mu...

Page 3: ...ck closes 6 To reopen a closed excess flow valve close a shutoff valve on either the upstream or downstream piping When pressure is equal on both sides of the valve it will click open and flow can be resumed by opening the shutoff valve WARNING Trained personnel should test the excess flow valve in a safe location Excess flow closure should be checked annually or on a regularly scheduled basis to ...

Page 4: ...egarding the products or services described herein or their use or applicability We reserve the right to modify or improve the designs or specifications of such products at any time without notice Fisher does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Fisher product remains solely with the purchaser E...

Reviews: