Instruction Manual
D104551X012
easy-Drive RPU-100
May 2021
10
Wiring
Power Requirements
Ensure a stable DC power source is available, maintaining less than 5% ripple and sufficiently surge protected for the
application. A 4 amp (minimum) power supply is required.
Wiring Instructions
1. Ensure power is turned off before connecting the wires.
2. Observe local wiring requirements for hazardous location usage.
3. Conduit seals within 450 mm (18 inches) of the enclosure port are required.
4. 18 AWG (0.52mm
2
) to 12 AWG (3.31mm
2
) wire size required.
5. Fuse system to 5A.
6. Connect enclosure and analog signal shields.
7. Be sure to tighten terminals sufficiently to ensure solid mechanical connection
.
Figure 11. Wiring - RPU-100 Front View