background image

Instruction Manual

D103363X012

26000 Valve

June 2017

2

Educational Services

For information on available courses for the Baumann 26000 valve, as well as a variety of other products, contact:

Emerson Automation Solutions
Educational Services - Registration
Phone: 1-641-754-3771 or 1-800-338-8158
E-mail: [email protected]
emerson.com/fishervalvetraining

Safety Precautions

  WARNING

Always wear protective gloves, clothing and eyewear when performing any installation operations to avoid personal
injury.
Personal injury or property damage caused by sudden release of pressure or bursting of pressure retaining parts may result
if service conditions exceed those for which the product was intended. To avoid injury or damage, provide a relief valve for
over pressure protection as required by government or accepted industry codes and good engineering practices.
Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
If installing into an existing application, also refer to the WARNING at the beginning of the Maintenance section in this
instruction manual.

CAUTION

This valve is intended for a specific range of pressures, temperatures and other application specifications. Applying
different pressures and temperatures to the valve could result in parts damage, malfunction of the control valve or loss of
control of the process. Do not expose this product to service conditions or variables other than those for which the product
was intended. If you are not sure what these conditions are you should contact your 

Emerson sales office

 or Local Business

Partner for more complete specifications. Provide the product serial numbers (shown on the nameplate) and all other
pertinent information.

  WARNING

If you move or work on an actuator installed on a valve with loading pressure applied, keep your hands and tools away
from the stem travel path to avoid personal injury. Be especially careful when removing the stem connector to release all
loading on the actuator stem whether it be from air pressure on the diaphragm or compression in the actuator springs.
Likewise take similar care when adjusting or removing any optional travel stop. Refer to the relevant actuator Maintenance
Instructions.
If hoisting the valve, take care to prevent people from being injured in case the hoist or rigging slips. Be sure to use
adequate sized hoists and chains or slings to handle the valve.

  WARNING

Personal injury could result from packing leakage. Valve packing is tightened before shipment; however, the packing
might require some readjustment to meet specific service conditions.

Summary of Contents for Fisher Baumann 26000

Page 1: ...ntain Baumann 26000 control valves without being fully trained and qualified in valve actuator and accessory installation operation and maintenance To avoid personal injury or property damage it is important to carefully read understand and follow all the contents of this manual including all safety cautions and warnings If you have any questions about these instructions contact your Emerson sales...

Page 2: ...pplication specifications Applying different pressures and temperatures to the valve could result in parts damage malfunction of the control valve or loss of control of the process Do not expose this product to service conditions or variables other than those for which the product was intended If you are not sure what these conditions are you should contact your Emerson sales office or Local Busin...

Page 3: ...uids may spray out under pressure when removing the packing hardware or packing rings or when loosening the packing box pipe plug D Check with your process or safety engineer for any additional measures that must be taken to protect against process media Note Whenever a gasket seal is disturbed by removing or shifting gasketed parts install a new gasket during reassembly This provides a good gaske...

Page 4: ...r line to the actuator loosen the hex clamp nut key 12 and turn the bonnet key 8 clockwise into the valve body key 1 This rotation will compress the packing key 17 around the plug and stem assembly key 4 and against the valve body interior Retighten the hex clamp nut key 12 and recheck for leakage Should the valve stem packing key 14 need to be adjusted turn the packing follower key 10 clockwise t...

Page 5: ...and insert the valve plug and stem assembly key 4 into the bonnet key 8 11 Screw the bonnet key 8 with the plug and stem assembly key 4 loosely into the valve body key 1 12 Push the stem all the way down until the plug is fully seated 13 Install the valve body in the test fixture or between a pair of appropriate mating line flanges 14 Apply 50 psi air pressure to the fixture or the flange connecte...

Page 6: ...IV If leakage is noted loosen the jam nuts key 27 and turn the plug and stem assembly key 4 further into the valve bonnet key 8 26 At the lowest actuator travel position the indicator disk key 58 shall be at least 0 040 inches below the zero travel position If not move the stem key 4 further into the bonnet key 8 and recalibrate the travel indicator 27 Check the valve travel for a full 1 2 inch fr...

Page 7: ...rt Cv 4 2 26532 26532 3 3 Spacer Cv 001 1 0 ONLY 26507 26507 4 Plug Stem Subassembly Cv 0 001 26520 008 999 1 Plug Stem Subassembly Cv 0 005 26520 007 999 1 Plug Stem Subassembly Cv 0 01 26520 006 999 1 Plug Stem Subassembly Cv 0 02 26520 005 999 1 Plug Stem Subassembly Cv 0 05 26520 004 999 1 Plug Stem Subassembly Cv 0 1 26520 003 999 1 Plug Stem Subassembly Cv 0 2 26520 002 999 1 Plug Stem Subas...

Page 8: ...Valve Body for Cv Ratings of 0 001 to 1 0 Class VI Seat Leakage E1287 Figure 4 Valve Body for Cv Rating of 4 2 Class IV Seat Leakage E1288 CAUTION It is highly recommended that the included PTFE encapsulated line flange adapter gaskets key 21 be utilized Figure 5 Baumann 26000 Valve Body Shown Upside Down for Assembly Procedure E1368 ...

Page 9: ... 2000 filled Polytetrafluoroethylene Table 3 Baumann 26000 Valve and Actuator Weights VALVE WEIGHT ACTUATOR WEIGHT kg lbs kg lbs 3 3 7 3 4 5 10 Figure 7 Dimensions NPS 1 26000 Valve with Baumann 32 Actuator and Dual Travel Stops 216 48 5 57 2 25 E1290 229 9 0 114 44 5 71 2 8 216 48 5 31 1 24 ADJUSTABLE OPEN CLOSED DUAL TRAVEL STOPS PROVIDED AS STANDARD 44 1 75 PTFE COVERED LINE FLANGE ADAPTOR GASK...

Page 10: ...Baumann 32 Actuator with Options 216 48 5 141 5 5 127 5 0 163 6 4 227 8 96 E1291 229 9 0 OPTIONAL FISHER 3660 3661 POSITIONER TOP MOUNTED HANDWHEEL FOR AIR TO CLOSE FAIL OPEN ACTUATION OPTIONAL FIELDVUE DIGITAL VALVE CONTROLLER TOP MOUNTED HANDWHEEL FOR AIR TO OPEN FAIL CLOSED ACTUATION 160 46 3 94 3 7 216 48 5 152 46 0 OPTIONAL FIELDVUE DVC2000 DIGITAL VALVE CONTROLLER DUAL STOPS FOR AIR TO CLOSE...

Page 11: ...Instruction Manual D103363X012 26000 Valve June 2017 11 ...

Page 12: ...lable upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice E 2009 2017 Fisher Controls International LLC All rights reserved Baumann Fisher and FIELDVUE are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co Emerson Automation Solutions Emerson and the Emerson logo ...

Reviews: