Introduction

This installation guide provides instructions for installation, 

startup, and adjustment. To receive a copy of the instruction 

manual, contact your local Sales Office or view a copy at 

www.fisher.com. For further information refer to: Type 92S 

Instruction Manual, form 5234, D100637X012.

P.E.D. Categories

This product may be used as a safety accessory with 

pressure equipment in the following Pressure Equipment 

Directive categories. It may also be used out-side of the 

Pressure Equipment Directive using sound engineering 

practice (SEP) per table below. For information on the 

current PED revision see Bulletin: 

D103053X012

.

PRODUCT SIZE

CATEGORIES

FLUID TYPE

DN 25 / 1 in.

SEP

1

DN 40, 50, 65, 80, 100 and 150 x 100 /

1-1/2, 2, 2-1/2, 3, 4 and 6 x 4 in.

II

Specifications

Main Valve Body Sizes and End Connection Styles

(1)

BODY SIZE

END CONNECTION STYLE AND RATING

DN

In.

Cast Iron Body

Steel or  

Stainless Steel Body

25, 40 and 50  1, 1-1/2 and 2

NPT

NPT

25, 40, 50, 65, 

80 and 100 

1, 1-1/2, 2, 

2-1/2, 3 and 4

CL125 FF or  

CL250 RF 

CL150 RF, CL300 RF, 

CL600 RF or 

PN 10/25/40

150 x 100

(1)

6 x 4

(1)

Not Available

CL300 RF, CL600 RF or 

PN16/25/40/64/100  

Maximum Inlet and Pilot Supply Pressure

(1)

Cast Iron Main Valve and Pilot: 

17.2 bar / 250 psig or 

body rating limit, whichever is lower

 

Steel or Stainless Steel Main Valve and Pilot:

 20.7 bar / 

300 psig or body rating limit, whichever is lower

Minimum and Maximum Differential Pressures

(1)

BODY SIZE

MINIMUM 

DIFFERENTIAL 

PRESSURE

MAXIMUM 

DIFFERENTIAL PRESSURE

DN

In.

bar

psi

bar

psi

25, 40, 50

1, 1-1/2, 2

1.0

15

13.8 bar or 

body rating 

limit, 

whichever is 

lower

200 psi or 

body rating 

limit, 

whichever is 

lower

65, 80, 100, 

150 X 200

(1)

2-1/2, 3, 4, 

6 X 4

(1)

1.4

20

12.1 bar or 

body 

rating limit, 

whichever is 

lower

175 psi or body 

rating limit, 

whichever is 

lower

Maximum Inlet and Outlet Pressures

(2)

See Table 1

Proof Test Pressure  

All Pressure Retaining Components have been proof 

tested per Pressure Equipment Directive.

Outlet (Control) Pressure Ranges

(2)

PILOT TYPE

OUTLET PRESSURE RANGES

bar

psig

6492L

0.14 to 0.41

0.34 to 1.0

0.90 to 1.7

2 to 6

5 to 15

13 to 25

6492H

0.69 to 2.1

1.7 to 5.2

4.8 to 10.3

10 to 30

25 to 75

70 to 150

6492HT

1.0 to 6.9

5.5 to 17.2

15 to 100

80 to 250

Maximum Allowable Loading Pressure for Pilot with 

Tapped Spring Case

(2)

Combination of pilot control spring setting and spring case 

loading pressure must not exceed 10.3 bar / 150 psig for 

Type 6492H pilot or 1.7 bar / 25 psig for Type 6492L pilot 

and 17.2 bar / 250 psig for Type 6492HT.

Maximum Material Temperature Capabilities

(2)

Cast Iron Construction:

 208°C / 406°F

Steel Construction:

 260°C / 500°F

High Temperature Optional Steel and Stainless steel 

Construction:

 

343°C / 650°F

PILOT TYPE

MAXIMUM ALLOWABLE INLET PRESSURE

MAXIMUM OPERATING 

OUTLET PRESSURE

MAXIMUM EMERGENCY OUTLET PRESSURE

Cast Iron

Steel or 

Stainless Steel

Cast Iron Main Valve

and Pilot Body

Stainless Steel or Steel Main 

Valve and Pilot Body

bar

psig

bar

psig

bar

psig

bar

psig

bar

psig

6492L

17.2

250

20.7

300

1.7

25

6.90

100

6.90

100

6492H

17.2

250

20.7

300

  10.3

150

17.2 bar or main 

valve body rating 

limit, whichever 

is lower

250 psig or main 

valve body rating 

limit, whichever 

is lower

20.7 bar or main 

valve body rating 

limit, whichever 

is lower

300 psig or main 

valve body rating 

limit, whichever 

is lower

6492HT

- - - -

20.7

300

17.2

250

- - - -

20.7 bar or main 

valve body rating 

limit, whichever 

is lower

300 psig or main 

valve body rating 

limit, whichever 

is lower

Table 1. 

Maximum Inlet and Outlet Pressures

(1)

1. The two-number designation indicates end connection size by trim size.

2. The pressure/temperature limits in this installation guide and any applicable standard or code limitation should not be exceeded. 

Type 92S

Installation Guide

D100637X014
English – October 2013

Summary of Contents for Fisher 92S

Page 1: ...s lower Maximum Inlet and Outlet Pressures 2 See Table 1 Proof Test Pressure All Pressure Retaining Components have been proof tested per Pressure Equipment Directive Outlet Control Pressure Ranges 2 PILOT TYPE OUTLET PRESSURE RANGES bar psig 6492L 0 14 to 0 41 0 34 to 1 0 0 90 to 1 7 2 to 6 5 to 15 13 to 25 6492H 0 69 to 2 1 1 7 to 5 2 4 8 to 10 3 10 to 30 25 to 75 70 to 150 6492HT 1 0 to 6 9 5 5...

Page 2: ...t hole in the spring case is unobstructed at all times For outdoor installations the regulator should be located away from vehicular traffic and positioned so that water ice and other foreign materials cannot enter the spring case through the vent Avoid placing the regulator beneath eaves or downspouts and be sure it is above the probable snow level Overpressure Protection The recommended pressure...

Page 3: ...linder Gasket 19 Body Gasket 20 Upper Stem 21 Cylinder Spacer 22 Stem Seal Types 6492L 6492H and 6492HT Pilots Key Description 1 Body 2 Valve Plug Guide 3 Valve Plug Spring 4 Inner Valve 5 Orifice 7 Valve Stem 8 Bellows Retainer 9 Bellows 10 Diaphragm 11 Lower Spring Seat 12 Control Spring 13 Upper Spring Seat 14 Spring Case Key Description 15 Adjusting Screw 16 Hex Nut 17 Cap Screw 18 Diaphragm G...

Page 4: ... 2018 Emerson Process Management Regulator Technologies Inc All rights reserved 07 18 The Emerson logo is a trademark and service mark of Emerson Electric Co All other marks are the property of their prospective owners Fisher is a mark owned by Fisher Controls International LLC a business of Emerson Automation Solutions The contents of this publication are presented for information purposes only a...

Reviews: