Instruction Manual
D200160X012
4195K Controllers
July 2018
93
Use the following procedures to replace the remote set point assembly. Figure 6‐23 shows the part locations. Refer to
figure 7‐6 for key number locations.
Figure 6‐23. Remote Set Point (suffix letter M) Parts and Adjustment Locations
PIVOT
ASSEMBLY A
GUIDE
FLEXURE
MOUNTING
SCREW
LINK A
ADJUSTMENT
SCREW
LINK B
LINEARITY
ADJUSTMENT
PIVOT
ASSEMBLY B
MOUNTING
SCREW
TIE BAR
REMOTE SET POINT ZERO ADJUSTMENT SCREW
ZERO ADJUSTMENT LOCKING SCREW
CAPSULES
UPPER TRAVEL
STOP
LOWER TRAVEL
STOP
DRIVE FLEXURE
SIDE VIEW
FRONT VIEW
36A9751‐C
B1668‐4
Note
Remove the supply pressure gauge before attempting to remove the capsular element assembly.
1. Decrease the remote set point pressure to 0 bar (0 psig).
2. Remove the supply pressure gauge.
3. Remove the pressure connection (key 93) at the pedestal assembly (key 105). Use two 5/16 inch wrenches.
4. Disconnect link B (key 126) from the connection hole on the set point indicator.
5. Remove the three mounting screws (keys 120 and 140) that attach the remote set point assembly to the
process/set point indicator assembly. Figure 6‐23 shows the mounting screw locations.
CAUTION
In the following step, do not lift out the remote set point assembly by holding the capsular element or linkages. These parts
may be damaged.