Section 4 4195KB Proportional‐Plus‐Reset Controllers and
4195KC Proportional‐Plus‐Reset‐Plus‐Rate Controllers
Adjustments for 4195KB and KC Controllers
This section includes descriptions of adjustments and procedures for prestartup, startup, and calibration. Adjustment
locations are shown in figures 4‐1 and 4‐3. To better understand the adjustments and overall controller operation,
refer to the Principle of Operation section and to the schematic diagrams in figures 4‐5 through 4‐9. Unless otherwise
noted, key numbers given in this section are found in figure 7‐1.
Figure 4‐1. Fisher 4195KB and KC Controller Adjustment Locations
METAL BALL
SWITCHING
ZONE
INDICATOR
LOADER KNOB
AUTO/MANUAL
SWITCH
W3679
AUTO/MANUAL STATION
(SUFFIX LETTER E)
RATE
ADJUSTMENT
RESET
ADJUSTMENT
W3599-1
4195KC RESET AND RATE ADJUSTMENTS
SET POINT
INDICATOR
TYPICAL ADJUSTMENTS
4195KB SHOWN
W6833
PROCESS POINTER
PROPORTIONAL BAND
ADJUSTMENT
ANTI‐RESET WINDUP
DIFFERENTIAL RELIEF
VALVE (SUFFIX LETTER F)
SUPPLY
PRESSURE GAUGE
RESET
ADJUSTMENT
OUTPUT PRESSURE GAUGE
Manual Set Point Adjustment
Adjust the set point by opening the controller cover and moving the set point indicator until the line on the set point
indicator is over the desired value on the process pressure scale. Move the indicator to the right to increase the set
point and to the left to decrease it. Adjusting the set point does not affect the proportional band setting.