OS Function Block
November 2010
149
(X
11
, Y
11
)
SP
Split Range
Sequencing
(X22 , Y22)
(X
12
, Y
12
)
OUT_1
OUT_2
0%
50%
100%
100%
100%
OUT_2
OUT_1
100%
0%
0%
0%
50%
(X
12
, Y
12
)
(X
22
, Y
22
)
(X
11
, Y
11
)
(X
21
, Y
21
)
(X
21
, Y
21
)
SP
X
X
Y
Y
Figure 4-18. Split Range and Sequence Operation
Table 4-46. OUT_ARRAY Coordinates
Index
Coordinate
0
Y
11
−
Value of OUT_1 at X
11
1
Y
12
−
Value of OUT_1 at X
12
2
Y
21
−
Value of OUT_2 at X
21
3
Y
22
−
Value of OUT_2 at X
22
A configuration error is set in BLOCK_ERR and the
actual mode of the block goes to Out of Service if the
X values have any of the following conditions: X
21
<
X
11
, X
12
< = X
11
, X
22
< = X
21
.
Refer to figure 4-19 for an example of LOCKVAL =
true, and figure 4-20 for an example of LOCKVAL =
false. The parameter LOCKVAL provides an option to
specify whether OUT_1 remains at its ending level
when control is switched to OUT_2, or goes to Y
11
. If
LOCKVAL is true, OUT_1 remains at its ending value
when X is greater than X
12
. If LOCKVAL is false, then
OUT_1 goes to Y
11
when X is greater than X
12
.
0%
SP
OUT
1
OUT
2
OUT
1 remains at
end point when OUT_2
is non-zero
50%
100%
Figure 4-19. OUT with LOCKVAL True
OUT
1
OUT
2
0%
SP
50%
100%
OUT_1 goes to zero
OUT_2 becomes
Figure 4-20. OUT with LOCKVAL False
Some hysteresis in the switching point may be
required because the output may change by a full
stroke of the valve. HYSTVAL [12] contains the
amount of hysteresis. If X < = X12
−
HYSTVAL,
OUT_1 may be determined by the calculated y value.
If X12
−
HYSTVAL < X < X12 and X has not reached
X12 since it was less than X12
−
HYSTVAL, OUT_1
may be determined by the calculated y value. If
X12
−
HYSTVAL < X < X12 and X has reached X12
since it was less than X12
−
HYSTVAL, OUT_1 may be
determined by the LOCKVAL setting. If X12 < X,
OUT_1 may be determined by the LOCKVAL setting.
Initialization and Back Calculation
Requirements
Refer to figure 4-21, Output Splitter Configuration,
where:
PID1 = Upstream driving controller or function block.
4
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...