Emerson EXD-U02 Operating Instructions Manual Download Page 1

 

 

Operating instructions 

Universal Driver Module EXD-U02  

for Electrical Control Valves EX4-8 / CV4-7 

   

 

Emerson Climate Technologies GmbH  

https://climate.emerson.com/en-gb

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 26.11.2019 

EXD-U02_OI_ML_R03_866919.docx 

G e n e r a l   i nf o r ma t i o n : 

EXD-U02 Universal Driver Module is for driving Emerson stepper motor driven 

electrical control valves series EX4-8 and CV4-7. Typical application of EXD-U02 

in a CO

2

 booster transcritical system is shown in Fig. 8. 

  S a f e ty   i n s tr u c t i o n s : 

 

Read operating instructions thoroughly. Failure to comply can result in device 

failure, system damage or personal injury 

 

According to EN 13313 it is intended for use by persons having the 

appropriate knowledge and skill. 

 

Before wiring disconnect all voltages from system and device. 

 

Do not operate system before all cable connections are completed. 

 

Do not apply 110/220/230V to any terminal of driver module. 

 

Entire electrical connections have to comply with local regulations. 

I n s t a l l a t i o n : 

 

EXD-U02 delivery is in two versions: as standalone or as kit with K09-U00 

electrical terminal. 

 

Mount all electrical terminals. Electrical 

terminal for analogue signal connection is 

different to other terminals in term of size and fit 

only on location (#6) as Fig. 3/4. The small 

terminals require smaller size of screw driver 

compared to other terminals. 

Fig.1

 

 

 

 

EXD-U02 is delivered with bracket suitable for 

mounting on DIN-Rail. Hang driver above DIN-

Rail and push down- and backward until it snaps 

completely and hold by DIN-Rail. 

Fig.2 

 

W i r i n g : 

 

Wiring diagram for single driver with optional backup battery ECP-024 see Fig. 3. 

Single ECP-024 can be connected to two EXD-U02 see Fig. 4 

 

It is recommended the use of prewired M12 plug and cable assembly (EXV-Mxx) 

for easy wiring between EX4-8 or CV4-7 and EXD-U02. The wires colors match 

to colors coding of stepper motor terminals (see Fig.3 & 4). 

 

24VAC digital input (#1, Fig 3 & 4) can be supplied from same source of power. 

Digital input act as ON/OFF command and it 

is only method to make sure valve 

is fully closed.

 The digital input can be controlled by potential free contact(s).  

As illustrated, external  contact 

“C”

  is a normally open contact and the 

activation/deactivation is in general parallel with compressor ON/OFF. Additional 

external contact 

“P”

 as normally close in series with contact 

“C”

 can be used for 

pump down function.  

 

It is mandatory the external grounding backside of EXD-U02 (Fig.2).  

 

Use a class II category transformer (#2) for 24 VAC power supply. Do not ground 

the 24 VAC line and install proper size of fuse (#3) 

 

Keep separate the wires for power supply, stepper motor of valve and signal. 

 

Recommended wire size Ø 0.5 … 2.5 mm

2

Special wiring for two valves/drivers from single source of analog input (Fig.4): 

 

Two valves operating simultaneously in parallel. It is intended for application that 

both valves are synchronized, equally opening or closing. In case of 4-20mA 

analog signal, see Fig.5a and in case of 0-10V signal, see Fig.5b. 

 

D i p   s w i t c h e s   s e t t i ng   ( F i g . 6 ) :  

Disconnect power supply as well as analog input signal. Set dip switches by a pencil 

or similar according table 1. The dip switches of new EXD-U02 are all set to OFF 

position (OFF: Downward / ON: Upward).

 

 

Dip Switch Number 

Valve type/ step 

recovery /analog input  

Dip switch position 

EX4-6  

OFF  OFF  OFF  ON  OFF  OFF 

CV4 

OFF  OFF  ON  OFF  OFF  OFF 

CV5-6  

OFF  OFF  ON 

ON  OFF  OFF 

EX7 

OFF  ON  OFF  OFF  OFF  OFF 

CV7  

OFF  ON  OFF  ON  OFF  OFF 

EX8 

OFF  ON 

ON  OFF  OFF  OFF 

Step Recovery – Yes 

OFF 

Step Recovery – No 

ON 

Signal: 4-20 mA  

OFF 

Signal:  0-10V  

ON 

Table 1 

V a l v e   Sy n c hr o ni z a t i o n :    

 

The EXD-U02 synchronizes the stepper motor driven valve with the Mechanical 

reference point in the fully closed position when the digital input is interrupted for 

minimum time shown in the table 2.  

S t e p   R e c o v e r y   f u n c t i o n : 

 

Step Recovery  enables to recover potentially lost steps during operation if the 

digital input has not been interrupted for a continuous operation (

for more detail 

see technical bulletin of EXD-U02

 

Warning:

  

 

Minimum analog  signal  (0VDC in case of 0-10VDC or 4 mA in case of 4-

20 mA) is not intended for driving valve to fully close position. Only digital 

input interruption is the appropriate command for driving valve to fully close 

position. 

S t a r t - u p   p r o c e d ur e : 

 

Note: EX/CV valves are delivered in partially open position. 

 

Vacuum the entire refrigeration circuit.

 

The valve can be driven to close position 

before charging the system.

 

In order to close the valve fully, disconnect the Digital 

input while keeping the 24VAC supply voltage connected for a period of time as 

shown in table 2.

 

Valve 

Closing time (sec.) 

Valve 

Closing time (sec.) 

EX4-6 

2…5 

CV4-6 

2…5 

EX7 

4…5 

CV7 

13…15 

EX8 

6…8 

Table 2 

T e c h ni c a l   d a ta :  

Power supply

 

24 VAC ±10%, 50-60 Hz

  

Note: 24 VDC supply voltage can be used but it results to lower MOPD and 

it needs to be verified/approved under system manufacturer responsibility. 

Inputs 

Analog input 4…20 mA, burden 364 

,  

or

  

Analog input 0…10 V, impedance 24 k

.  

Digital input: 24 VAC/DC (+10%, -15%), 50-60 Hz 

Outputs 

Current outputs for stepper motor of EX4-8/ CV4-7 

Uninterruptible power 

supply ECP-024 

Required power supply voltage: 24 VAC 

±

 10% 

Outputs: two individual, each +18 VDC 

Wiring Diagram 

 

(see Fig. 3,4,5a,5b)

 

(#1)  Digital input terminals/signal (0 V = OFF; 24 V = ON) 
(#2)  Transformer 

(#3)  Fuse 
(#4)  Plug cable assembly EXV-Mxx for connection to EX4-8 / CV4-7 

 

Cable color code: 

WH=White      BK=Black       

 

 

 

 

BL= Blue      BN=Brown 

(#5)  Third party controller’s analog signal supplies (4…20 mA or 0…10 V) 
(#6)  Analog input terminal/signal (4…20 mA or 0…10 V) 
(#7) 

Optional

 Uninterruptible Power Supply insures the closure of valve during 

power failure in system. 

(#8)  Terminal (EXD-U02 /ECP-024) to be connected to single source. In event of power 

interruption, ECP-024 drive automatically the valve(s) to close position. 

(C)  Normally open external potential free contact.  

 

Function:

 Interruption of digital input for synchronization purpose or fully closing 

the valve.  

(P)  Normally close external potential free contact  

 

(Pump down function) 

Dimensions 

See Fig.7 

Marking 

 

 

 

Summary of Contents for EXD-U02

Page 1: ... of 4 20mA analog signal see Fig 5a and in case of 0 10V signal see Fig 5b Di p swi tc hes se tti ng Fig 6 Disconnect power supply as well as analog input signal Set dip switches by a pencil or similar according table 1 The dip switches of new EXD U02 are all set to OFF position OFF Downward ON Upward Dip Switch Number Valve type step recovery analog input 1 2 3 4 5 6 7 8 Dip switch position EX4 6...

Page 2: ...ie Anwendung vorgesehen dass beide Ventile synchronisiert sind und sich gleichermaßen öffnen oder schließen Bei einem analogen 4 20mA Signal und siehe Fig 5a bei einem 0 10V Signal siehe Fig 5b E i nstel l ung der DIP Sc ha lte r F ig 6 Trennen Sie die Stromversorgung sowie das analoge Eingangssignal Stellen Sie die DIP Schalter mit einem Bleistift oder ähnlichem gemäß Tabelle 1 ein Die DIP Schalt...

Page 3: ... cas d un signal 0 10V voir Fig 5b P o si ti o nne me nt de s c o mmu ta te ur s Fig 6 Déconnecter l alimentation ainsi que le signal d entrée analogique Positionner les commutateurs à l aide d un crayon ou équivalent selon la table 1 Les commutateurs d un nouvel EXD U02 sont tous en position OFF OFF vers le bas ON vers le haut Tableau 1 Commutateurs DIP Vanne récupération de pas entrées analogiqu...

Page 4: ...a alimentación eléctrica y la entrada analógica Configurar los micro ruptores con una herramienta apropiada o un bolígrafo de acuerdo a la tabla 1 Los micro ruptores del nuevo EXD U02 se suministran todos en posición OFF OFF micros abajo ON micros arriba Número del micro interruptor Válvula Recuperación de pasos señal de entrada 1 2 3 4 5 6 7 8 los micro ruptores posición EX4 6 OFF OFF OFF ON OFF ...

Page 5: ...chiusura In caso di segnale analogico 4 20 mA vedere Fig 5a e in caso di segnale 0 10 V vedere Fig 5b Impo sta z io ne dei di p sw i tch F i g 6 Disconnettere l alimentazione e il segnale di ingresso analogico Impostare i dip switch con una matita o simile come in tabella 1 I dip switch del nuovo EXD U02 sono tutti in posizione OFF OFF Downward ON Upward Tabella 1 Numero Dip Switch Valvola Riprist...

Page 6: ...ро пе ре кл юч а те ле й с м Ри с 6 Таблица 1 Номер Dip переключателя Клапан Восстановление шагов Аналоговый выход 1 2 3 4 5 6 7 8 Микропереключатель положения EX4 6 OFF OFF OFF ON OFF OFF CV4 OFF OFF ON OFF OFF OFF CV5 6 OFF OFF ON ON OFF OFF EX7 OFF ON OFF OFF OFF OFF CV7 OFF ON OFF ON OFF OFF EX8 OFF ON ON OFF OFF OFF Восстановление шагов Да OFF Восстановление шагов Нет ON Сигнал 4 20 мA OFF Си...

Page 7: ...XD U02 Emerson Climate Technologies GmbH https climate emerson com en gb Am Borsigturm 31 I 13507 Berlin I Germany Date 26 11 2019 EXD U02_OI_ML_R03_866919 docx Fig Рис 3 Fig Рис 4 Fig Рис 5a Fig Рис 5b ...

Page 8: ...xpansionsventil Saugdruckventil FR Vanne gaz haute pression Vanne Bypass Vanne de récupération de chaleur Vanne de détente Vanne pression d aspiration ES Válvula de gas de alta presión Válvula bypass Válvula control recuperador de calor Válvula de expansión Válvula regulación presión de aspiración IT Valvola gas alta pressione Valvola Bypass Valvola recupero calore Valvola di espansione Valvola pr...

Reviews: