Operating instructions 

EXD-TEVI Economizer Controller with  

ModBus Communication Capability

 

 

 

 

Emerson Climate Technologies GmbH  

 

www.emersonclimate.eu

  

1/3 

Holzhauser Straße 180 I 13509 Berlin I Germany  

Date: 19.08.2014 

EXD-TEVI_OI_EN_R02_865908.docx 

General information: 

EXD-TEVI  is  a  stand-alone  controller  for  enhanced  wet  vapor  injection  in 
heating applications for Copeland tandem Scroll compressors. 
Notes: Another controller (like EC3-X33) must be used for main superheat control.  
For ModBus communication, protocol and bus topology please see technical bulletin 
of EXD-TEVI (www.emersonclimate.eu). 

 Safety instructions: 

 

Read  operating  instructions  thoroughly.  Failure  to  comply  can  result  in 
device failure, system damage or personal injury. 

 

According  to  EN  13313  it  is  intended  for  use  by  persons  having  the 
appropriate knowledge and skill. 

 

Before installation or service disconnect all voltages from system and device. 

 

Do not operate system before all cable connections are completed. 

 

Entire electrical connections have to comply with local regulations. 

 

Installation: 

The EXD-TEVI is designed to be mounted on a standard DIN rail. 

 

Electrical installation: 

 

Refer to the electrical wiring diagram for electrical connections. 

 

Important: Keep controller and sensor wiring well separated from mains wiring. 
Minimum recommended distance 30mm. 

 

EXM-125 and EXL-125 coils are supplied with fix cable and JST terminal block 
at  cable  end. Cut  the  wires  close  to  terminal  block. Remove  the  wire  insulation 
approximately  7mm  at  the  end.  It  is  recommended  to  protect  wire  ends  with 
ferrules. 

 

Color codes for connection of EXM/EXL and pressure sensor PT5: 

 

EXM/L  BR: Brown; BL: Blue; OR: Orange; YE: Yellow; WH: White 

 

PT5 

BN: Brown; WH: White 

 

Digital inputs DI1 and DI2 

The  digital  inputs  DI1  +  DI2  are  the  interface  between  EXD-TEVI  and  system 
controller  if  the  Modbus  communication  has  not  been  used.  The  digital  status  is 
dependent to operation of system’s compressor/demand. 

Operating condition 

Digital input status 

Compressor starts 

Closed (Start) 

Compressor stops 

Open (Stop) 

 

Wiring:  

Warnings: 

 

Use a class II category transformer for 24VAC power supply.  

 

Do not ground the 24VAC lines.  

 

Connecting any inputs to mains voltage will permanently damage the EXD-
TEVI. 

We  recommend  using  individual  transformers  for  EXD-TEVI  controller  and  any 
3

rd

  party  controllers  to  avoid  possible  interference  or  grounding  problems  in  the 

power supply. 
 

 
 

Lower Board 

Upper Board 

 

 

Notes: 
* 86k

 NTC Discharge Temperature sensors, see Copeland documentation 

Alarm relay, dry contact. Relay coil is not energized during alarm condition or 
power off. 
 

Display/keypad unit (LEDs and button functions): 

 

ON: Data display   

ON: alarm 
OFF: no alarm 

ON: ModBus 
communication 

 

Next 
parameter/ 
value 
(higher) 
 
Next 
parameter/ 
value 
(lower) 
 
 
Selecting/ 
confirming 

 

Parameters setting/saving 
 

 

Blinking: valve is opening 
ON: valve is fully open 

 

Blinking: valve is closing 
ON: valve is fully close 

 

 
 
 
 

 
 

 

!

Библиотека СОК  

Summary of Contents for EXD-TEVI

Page 1: ...ils are supplied with fix cable and JST terminal block at cable end Cut the wires close to terminal block Remove the wire insulation approximately 7mm at the end It is recommended to protect wire ends with ferrules Color codes for connection of EXM EXL and pressure sensor PT5 EXM L BR Brown BL Blue OR Orange YE Yellow WH White PT5 BN Brown WH White Digital inputs DI1 and DI2 The digital inputs DI1...

Page 2: ...g are applied Display System Parameters In standard mode the EVI superheat is shown at the display In case of wet vapor injection and economizer function this changes to discharge temperature To display other data of EXD TEVI Press for 3 seconds to show data To display data Press the button for 1 second until index number according to the below table appears Release the button and the next variabl...

Page 3: ...lly close Check wiring connection and measure the resistance of sensor Auto 2Ed Hot gastemp sensor2 fail Triggered Fully close Check wiring connection and measure the resistance of sensor Auto 1Π EXM EXL electrical connection error Triggered Check wiring connection and measure the resistance of winding Auto 2Π EXM EXL electrical connection error Triggered Check wiring connection and measure the re...

Page 4: ...лер и провода датчиков на расстоянии минимум 30 мм от кабелей питания Катушки у EXM 125 и EXL 125 поставляются вместе с вмонтированным кабелем и клеммной колодкой на конце кабеля Отрежьте клеммную колодку Зачистите от изоляции примерно 7 мм на концах проводов На зачищенные участки рекомендуется одеть наконечники Коды расцветок при подключении EXM EXL и датчика давления PT5 EXM L BR Коричневый BL С...

Page 5: ...ение параметров системы При впрыске пара стандартный режим на дисплее отображается перегрев а при впрыске влажного пара температура нагнетания Для отображения других данных на EXD TEVI Нажмите на 3 секунды для показа данных Показать данные Нажимайте в течение 1 секунды пока не появится индекс нужного параметра из таблицы ниже Отпустите кнопку и появится нужное значение Повторяя эту процедуру можно...

Page 6: ... сопротивление датчика Авто 2Ed Ошибка датчика2 температуры нагнетания Сигнализирует Закрыт Проверьте правильность электрических подключений и измерьте сопротивление датчика Авто 1Π Ошибка электрического подключения ЭРВ 1 Сигнализирует Проверьте правильность электрических подключений и измерьте сопротивление проводов Авто 2Π Ошибка электрического подключения ЭРВ 2 Сигнализирует Проверьте правильно...