User Manual
Chapter 3
GFK-2849A
Oct 2019
Configuration
35
Calling AP Title
This setting is according to ISO 8650-1(ACSE) and should not be used in standard cases. The
default value is 1.1.1.999
Calling AE Qualifier
This setting is according to ISO 8650-1(ACSE) and should not be used in standard cases. The
default value is 12
Called AP Title
This setting is according to ISO 8650-1(ACSE) and should not be used in standard cases. The
default value is 1.1.999.1.1
Called AE Qualifier
This setting is according to ISO 8650-1(ACSE) and should not be used in standard cases. The
default value is 12.
Maximum URCBs
The maximum number of Un-buffered Report Control Blocks (URCBs) that you can activate.
The URCBs are accessed in an order related to their importance and are analyzed for the
variables in that URCB. The more variables related to a URCB that are used, the higher the
priority for accessing this URCB. If you need to configure a specific URCB instead of relying
on this parameter, then you can select the specific URCB
using the “RCB configuration”. For
more information, see section 3.4.2,
Direct Method. The default value is 1.
Use Preconfigured TrgOps
If this option is enabled, then
the “Trigger options” as set by the IED are used by ECM850
client. Otherwise the specific trigger option values defined in the ECM850 configuration are
used. This is set to disabled by default. For more information refer to Trigger Options.
Use Authentication
This is used to enable the authentication of IED. The default value is disabled.
Authentication parameters
This is authentication parameters set for the IED, which will be validated if authentication is
enabled. The default value is not set.
IP Address (redundant)
This is a redundant IP address of the IED that you can set. Default is not set.
Note
If the IED supports a redundant IP feature and provides a redundant IP address which will be
activated on failure of the primary IP, then the ECM850 will automatically connect to the
redundant IP address on primary IP address failure.
Port (redundant)
This is a redundant port number for the IED that you can set. Default is 0.
Note
If the IED supports redundant port feature and provides a redundant port number which will
be activated on failure of primary port, then the ECM850 will automatically connect to the
redundant IP port number on primary port failure.