Operating instruction 

EC3-P32 Superheat Controller with TCP/IP 

Installation in non explosive environment 

 

 

 

Emerson Climate Technologies GmbH  

www.emersonclimate.eu

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 04.05.2017 

EC3-P32_OI_ML_R01_865918.docx 

G e n e r a l   i n f o r m a t i o n :  
EC3-P32 

is the superheat controller for systems with flammable refrigerants 

(A2L/A3) and able to drive EMERSON Valves EX4-7-…FLR  via M12 Connector 
ECV05A. 
 

Warning:

 

 

EC3-P32  has  a  potential ignition source and does  not  comply with ATEX 
requirements. Installation only in non-explosive environment. 

 

EX4-7…FLR are currently released for R290 in term of compatibility. The 
other listed refrigerants are subject to qualification at later stage. No 
warranty or product liability if EX4-7…FLR to be used with other 
refrigerants stored in software of EC3-P32. 

  S a f e t y   i n s t r u c t i o n s :  

 

Read operating instructions thoroughly. Failure to comply can result in device 
failure, system damage or personal injury. 

 

According to EN 13313 it is intended for use by persons having the 
appropriate knowledge and skill. 

 

Ensure that the system is correctly labeled with applied refrigerant type and 
a warning for explosion risk. 

 

Do not exceed the specified maximum ratings for temperature (max. +60°C), 
voltage and current. 

 

Before installation or service disconnect all voltages from system and device. 

 

Do not operate system before all cable connections are completed. 

 

Entire electrical connections have to comply with local regulations. 

Note

: The EC3-P32 series contains 

a VRLA battery = valve regulated rechargeable 

lead-acid battery. 

The battery must NOT be disposed of with other commercial waste. 

Instead, it is the user’s responsibility to pass it to a designated collection point for the 
safe recycling of batteries (harmonized directive 2012/19/EU). For further 
information contact your local environmental recycling center. 

M o u n t i n g   p o s i t i o n :  

The EC3-P32 is designed to be mounted onto a standard DIN rail. Mounting position: 
on vertical walls, with stepper motor connector on top side only. 
 

M o u n t i n g   o f   E C D - 0 0 2 :  

 

ECD-002 can be installed at any time also during operation. 

 

ECD-002 can be mounted in panels with 
71x29 mm cutout. 

 

Push controller into panel cut-out.(1) 

 

Make sure that mounting lugs are flush with 
outside of controller housing 

 

Insert Allen key into front panel holes and turn 
clockwise. Mounting lugs will turn and gradually 
move towards panel (2) 

 

Turn Allen key until mounting lug barely touches 
panel. Then move other mounting lug to the same 
position (3) 

 

Tighten both sides very carefully until keypad is 
secured. Do not over tighten as mounting lugs 
will break easily.

 

 

 

  E l e c t r i c a l   I n s t a l l a t i o n :  

 

Refer to the electrical wiring diagram for electrical connections. 

 

Do not apply voltage to the controller before completion of wiring. 

 

Ground the metal housing with a 6.3 mm spade connector. 

 

Keep controller and sensor wiring well separated from mains wiring. 
Minimum recommended distance 30 mm. 

 

Ensure that cables are not mounted near sharp edges. 

 

Use a class II category transformer for 24 VAC power supply. Do not ground the 
24 VAC lines. We recommend using individual transformers for EC3 controller(s) 
and for 3

rd

 party controllers to avoid possible interference or grounding problems 

in the power supply. Connecting any EC3 inputs to mains voltage will permanently 
damage the EC3. 

 

The use of the relay is essential to protect the system in case of power failure if the 
communications interface or the ECD-002 are not utilized. 

 

If the output relay is not utilized, the user must ensure appropriate safety pre-
cautions are in place to protect the system against damage caused by a power 
failure. 

 

In order to provide system protection in the event of power loss, it is recommended 
to change the battery annually. 

 

Digital input status is dependent to operation of compressor/thermostat 

Commander 

Operating condition 

Digital input (I) 

Compressor 

Compressor starts 

Closed / 24 V (Start) 

Compressor stops 

Open / 0 V (Stop) 

Thermostat 

Demand (compressor must be ON) 

Closed / 24 V (Start) 

No demand 

Open / 0 V (Stop) 

W i r i n g :

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

2

White wire  

4

:  Black wire 

3

:  Blue wire 

1

: Brown wire 

G

Remote control panel, system controller. 

H

Alarm relay, dry contact. Relay coil is not energized at alarm or power off. 

I

Digital input (0 V/open = Stop; 24 V/closed = Start) 

J

Transformer Class II, 24 VAC secondary / 25VA 

K

Third party controller (can use the analog output signal from EC3) 

O: 

Pump down relay, dry contact. Relay is energized during normal operation. 

 

Preparation for Start-up: 

 

Vacuum the entire refrigeration system. 

 

Note:

  EX4-7-…FLR  are delivered at half open position. Do not charge system 

before closure of valve. 

 

Apply supply voltage 24 V to EC3 while the digital input is 0 V (open). The valve 
will be driven to close position. 

 

After closure of valve, start to charge the system with refrigerant. 

 

Start the system and check the superheat and operating conditions. 

 

!

Non-explosiv 
environment 

Summary of Contents for EC3-P32

Page 1: ...ing lugs will turn and gradually move towards panel 2 Turn Allen key until mounting lug barely touches panel Then move other mounting lug to the same position 3 Tighten both sides very carefully until keypad is secured Do not over tighten as mounting lugs will break easily Electrical Installation Refer to the electrical wiring diagram for electrical connections Do not apply voltage to the controll...

Page 2: ...Main parameters must be checked and modified if necessary Code Parameter description and choices Min Max Factory setting Field setting H5 Password 1 199 12 u0 System refrigerant 0 6 0 0 R290 1 R32 2 R1234ze 3 R1234yf 4 R1270 5 R227 6 R600a uP Installed pressure sensor type PT5 30L FLR ut Installed valve type 0 3 1 0 EX4 FLR 1 EX5 FLR 2 EX6 FLR 3 EX7 FLR uu Start valve opening 5 100 10 u9 Start ope...

Page 3: ...stem components All other parameters can be modified at any time The EC3 P32 has a TCP IP Ethernet communication interface enabling the controller to be directly connected to a network or a PC via the standard Ethernet port The EC3 P32 controller has embedded WebPages to enable the user to visualize the parameter lists using real text labels To view WebPages on the PC a standard Web Browser like I...

Page 4: ...ta error display out of range Data send to the display is out of range Check temperature and pressure sensor No No data to display Check Cable and plug connection between EC3 P32 and ECD 002 No Note When multiple alarms occur the highest priority alarm is displayed until being cleared then the next highest alarm is displayed until all alarms are cleared Only then will parameters be shown again Che...

Page 5: ...start function NTC input EMERSON temperature sensor ECN Nxx 4 20 mA Analog input EMERSON PT5 30L FLR pressure Transmitter 4 20 mA Analog output Deviation from input signal For connection to any 3rd party controller with 12 24 VDC power supply and appropriate burden 8 max Output alarm relay SPDT contacts 24 VAC DC 2 Amp inductive load If L2 1 Activated During normal operation no alarm condition Dea...

Page 6: ...alterungen treten aus dem Gehäuse hervor und bewegen sich in Richtung Frontplatte 2 Imbusschraube drehen bis die erste Halterung die Frontplatte leicht berührt Dann zweite Halterung in diese Position bringen 3 Beide Seiten gleichmäßig und nicht zu fest anziehen Hinweis durch zu festes Anziehen können die Halterungen abbrechen Elektrischer Anschluss Den elektrischen Anschluss gem Verdrahtungsschema...

Page 7: ...OV möglich 1 Aktuelle TCP IP Adresse anzeigen 2 Dem Regler vorübergehend die Standard TCP IP Adresse 192 168 1 101 zuweisen falls dieser eine andere Adresse besitzt Nach dem Abschalten wird die zuvor eingestellte Adresse wieder aktiviert SEL drücken alle Parameter werden auf Werkseinstellung zurückgesetzt PRG drücken die gewählte Funktion wird aktiviert und die Betriebsart Spezial funktionen verla...

Page 8: ...rhindert die Beschädigung des Verdichters oder anderer Systemkomponenten Alle anderen Parameter können jederzeit verändert werden Der EC3 P32 kann mit seiner TCP IP Ethernet Schnittstelle direkt an den Ethernetanschluss eines PCs oder an ein lokales Netzwerk angeschlossen werden Übersichtliche Webseiten auf denen die Parameterlisten angezeigt oder geändert werden können sind bereits eingebaut Zur ...

Page 9: ...Daten nicht darstellen Einstellwert der Parameter verändern Nein Keine Daten Kabel und Steckerverbindungen zwischen EC3 P32 und ECD 002 prüfen Nein Hinweis Bei mehreren Alarmen gleichzeitig wird der Alarm mit der höchsten Priorität angezeigt nach dessen Beseitigung wird der nächsthöhere angezeigt usw bis alle Alarme beseitigt sind Danach werden wieder die Parameter angezeigt Überprüfung der Betrie...

Page 10: ...C DC zum Ein bzw Ausschalten NTC Analogeingang EMERSON Temperatursensor ECN N60 4 20 mA Analogeingang EMERSON PT5 30FLR Drucktransmitter 4 20 mA Analogausgang Abweichung vom Eingangssignal für externen Regler mit 12 24 VDC Speisespannung und geeignetem internen Widerstand 8 max Ausgang Alarmrelais Wechsler für 24 V AC DC Induktive Last 2 A wenn L2 1 Aktiviert bei Normalbetrieb kein Alarmzustand In...

Reviews: