EC2-IR__65046__R01.doc   Rev.: 01 

Replacement for  Rev.:00 

2 / 4 

20.07.2007 

 

 

 

Infrared Remote Control for EC2 

Operating Instructions 

GB 

HOW TO USE THE REMOTE CONTROL UNIT 

Access without code         

1)  HOW TO ENABLE THE CONTROLLER  TO RECEIVE THE REMOTE 
CONTROL  UNIT TRANSMISSION 

 

press the '

ENABLE

' button to operate the remote control unit;                 

 

the controller's led indicator above the digits  flashes and the first 
parameter - '/C' - is immediately displayed. If the display shows a 
code different from /C, it is necessary to introduce the access 
code (see point 5 below). 

2) MODIFYING THE MAIN PARAMETERS                  

  press either the 

 + 

or 

 - 

  key relative to the parameter you want to 

modify. The display will show the 

code of the selected 

parameter

 (see the codes of the parameters listed in the 

Instruction Sheet of the instrument). Press the button again to 
display the

 value

 associated to the selected parameter and 

 press 

+

 to increase it;        

 press 

-

  to decrease it.  

 

The section including directly accessible buttons also comprises 3 buttons 
that activate/deactivate the function they represent: 

DEFROSTING SECTION: 

START

   activates/deactivates a manual defrosting cycle;      

evap.tmp

 displays the temperature value measured by the evaporator 

probe (if present) or the value measured by the second probe 
(Thermometer EC2-000).  

 

Important: This function is always active. Consequently the 
temperature  measured by the second probe will be always 
displayed without having to press the 'START' button or 
select the access code (see point 5 below). 

CONTINUOUS CYCLE SECTION: 

C.cycle

.  activates a continuous cycle; 

 

see point 4 below to exit the programming procedure. 

3) HOW TO MODIFY THE PARAMETERS NOT DIRECTLY INDICATED 
BY A SPECIFIC BUTTON  
The other parameters - not directly associated to a specific button on the 
remote control unit - can be easily modified as follows: 

  perform the same operations described in point 1 above until the 

first parameter  '/C'  appears on the display; 

3.1  

 

press either  

 or     until the display shows the parameter you 

want to modify; 

 press 

SEL

 to display the value of the selected parameter; 

 press 

either    or  

  to increase/decrease its value; 

 press 

SEL

 to confirm temporarily the new value and display again 

the code of the parameter; 

  to modify another parameter repeat the operations described 

above starting from point  3.1; 

  see point 4 below to exit the programming procedure. 

4)  HOW TO EXIT THE PROGRAMMING PROCEDURE 

 press 

PRG

 to exit and memorize all modifications; 

 press 

ESC

 to exit without memorizing the previous 

modifications; 

  do not press any button for at least 60 seconds (TIME OUT).  

In this way the previous modifications will  be cancelled. 

Access with code 

5) HOW TO ENABLE THE CONTROLLER TO RECEIVE THE REMOTE 
CONTROL UNIT TRANSMISSION  

 press 

'ENABLE

' to operate the remote control unit;  

  all the controllers exposed to the beam of the remote control unit 

will display their own access code; 

  select the access code of the controller whose parameter you 

intend to modify using the numeric section on the remote control 
unit. Select the code correctly (if the code of the controller is 05, 
press 0 and 5). 

  the controller's led indicator above the digits flashes and, 

simultaneously, the code of the first parameter '/C' appears on the 
display.    

  perform the same operations described in point  2) or 3) 

above. 

HOW TO SELECT THE ACCESS CODE                           

SETTING THE ACCESS CODE 
All EC2 controllers have no factory-set access codes. The User can 
choose and set his own access codes by simply modifying the H3 
parameter as follows: 

 press 

'

ENABLE

' to operate the remote control unit;                  

  the controller's led indicator above the digits flashes and the first 

parameter ('/C) appears immediately.              

 press    to display the H3 parameter; 

 press 

SEL

 to display its value (default 00);                              

 press    to select  the desired value (from 01 to 199); 

 press 

SEL

  to confirm the new value and display again the H3 

code; 

 press 

PRG

 to memorize the access code and exit the 

procedure. 

REMOVING THE CODE  

  repeat the operations described above and give the H3 parameter 

the value 00 (

H3=00

). In this way you can program your 

controller/s without selecting the access code. 

WHAT TO DO IF THE REMOTE CONTROL DOESN'T WORK 

 check that the remote control is equipped with batteries aligned 

correctly; 

 replace spent or weak batteries; 

 check that there are no obstacles between controller and 

transmitter; 

 periodically clean the transmitter and the controller with a soft cloth; 

 remember that the remote control's usable range is within 3 meters 

away from the controller. 

 in case parameters are accessible but the user is not allowed to 

change values, verify "H2" parameter  (refer to the USER manual) 

 
MODELS 

There are several versions available, in different languages: 
 

Language Type 

Order 

Nr. 

 

English 

EC2- IRE 

804 345 

 

German 

EC2- IRD 

804 346 

 

French 

EC2- IRF 

804 347 

 

Spanish 

EC2- IRS 

804 348 

 

Italian 

EC2- IRI 

804 349 

Emerson Electric GmbH & Co.OHG is not to be held responsible for erroneous 
literature regarding capacities, dimensions, applications, etc. stated herein. 
Products, specifications and data in this literature are subject to change without 
notice. The information given herein is based on technical data and tests which 
ALCO CONTROLS believes to be reliable and which are in compliance with 
technical knowledge of today. It is intended only for use by persons having the 

appropriate technical knowledge and skills, at their own discretion and risk. Since 
conditions of use are outside of ALCO'S control we cannot assume any liability for 
results obtained or damages occurred due to improper application.  

This document replaces all former versions. 

Emerson Electric GmbH & Co OHG - Postfach 1251 - Heerstraße 111  -  D-71332 Waiblingen  -  Germany  -  Phone .49-(0)7151-509-0  -  Fax .49-(0)7151-509-200 
 

www.eCopeland.com/alcoliterature.cfm

 

Summary of Contents for EC2

Page 1: ...BUTTONS USED TO ACTIVATE DEACTIVATE THE USE OF THE REMOTE CONTROL UNIT The buttons shown on the left are the remote control unit ON OFF buttons They also allow you to memorize any new parameter value Note A red LED indicator will be displayed on the front panel of the controller to acknowledge that a signal is being received from the IR handset ENABLE blue zone enables the use of the remote contro...

Page 2: ...t all the controllers exposed to the beam of the remote control unit will display their own access code select the access code of the controller whose parameter you intend to modify using the numeric section on the remote control unit Select the code correctly if the code of the controller is 05 press 0 and 5 the controller s led indicator above the digits flashes and simultaneously the code of th...

Page 3: ... speichern die geänderten Werte ab Bemerkung die blinkende LED am oberen Rand des Anzeigefeldes weist darauf hin daß der EC2 von der Fernsteuerung angesprochen wird und auf weitere Eingaben wartet Parameter blauer Bereich Startet die Parametereingabe durch die Fernsteuerung PRG blauer Bereich 1 Beendet die Parametereingabe und speichert alle neueingegebenen Werte 2 Schaltet den Alarmsummer aus Vor...

Page 4: ...odes an Zugangscode des gewünschten EC2 eingeben Führende Null mit eingeben z B Zugangscode 05 Taste 0 dann 5 drücken Die LED am oberen Rand des Anzeigefeldes blinkt der erste Parameter C wird angezeigt Alle nicht gewählten Regler zeigen wieder die Temperatur am Raumsensor an Weiter wie in den Punkten 2 bis 4 beschrieben ZUGANGSCODE EINSTELLEN ZUGANGSCODE FESTSETZEN Der Zugangscode wird über den P...

Reviews: