EC1-233 Display Case and Coldroom Controller 

Operating Instructions 

GB 

Note: This document contains short form instructions for experienced users. 
Use last column in List of Parameters to document your individual settings. 

 

 

The EC1-233 is a dedicated refrigeration controller which controls air temperature 
and manages defrost and fan(s). 

S1

S5

2

3

4

2

EC1_Blockdiagr.cdr

9

7

 

 

The ECN-Sxx air temperature sensor S1(7) is used for measuring the air 
temperature and may be installed to measure either the air-in or air-out temperature 
of the evaporator to feed a signal to the controller for controlling the thermostat 
function. A relay output is used to control the refrigerant flow to the Thermo-
Expansion Valve by switching a solenoid valve (2) and / or the compressor. An 
ECN-Sxx sensor S5 (9) is used for defrost termination and may be installed in 
either the air outlet duct or inserted into the evaporator coil. The controller has 
relay outputs to control the solenoid valve / compressor (2), defrost heater (3) and 
evaporator fan (4). Please consult the technical data (right) for input and output 
ratings. Refer to the parameter list on page 3. 

!

  Safety instructions:  

 

Read installation instructions thoroughly. Failure to comply can result in 
device failure, system damage or personal injury. 

 

The product is intended for use by persons having the appropriate 
knowledge and skills.  

 

Ensure electrical ratings per technical data are not exceeded. Maximum 
current permitted through the common live terminal (pin1) is 15Amps. 

 

Mains voltage; Caution should be made when removing the electrical cover 
against electrical shock  

 

Disconnect all voltages from system before installation. 

 

Keep temperatures within nominal limits.  

 

Comply with local electrical regulations when wiring 

Technical Data

 

Power supply  

   230VAC ±10%; 50/60 Hz; Class II 

Power consumption 

3VA max. 

Communication n/a 
Connector size 

Fixed screw terminals 
wire size 0.14 … 1.5 mm

2

 

Temperature 
     storage 
     operating 

 
   -20 … +65°C 
 

0 … +60°C 

Humidity 

0…80% r.h.  non condensing 

Protection class 

IP65 (front protection with gasket) 

Output relays               (3) 

SPST contacts, AgCdO, sealed 

 Inductive 

(AC15) 

250V/2A 

 

Resistive (AC1) 250V/8A;  

!

 Max. current 15A total supply current on pin1

Mounting 

The EC1-233 can be mounted into a panel with a 71 x 29 mm cutout. See 
dimensional drawing below for space requirements including rear cable protector. 
Remove cable protector and mounting clips. (Move clip away from front side while 
pushing at point 

P

 see dimensional drawing below). 

Push controller into panel cutout (1) ensuring the gasket is positioned on the outer 
surface. 
Place the mounting clip onto the controller ensuring the spring is nearest the panel.  
Push each clip forward until the controller is firmly held in place. The spring on the 
clip should be compressed and the gasket firmly secured to prevent dust and 
moisture ingress.  

 

 

 

Electrical Installation 

Connect wires to terminals as per diagram below and replace cable protector at rear 
side

Refer to the electrical wiring diagram (below) for electrical connections. A 

copy of this diagram is mounted on the controller. Use connection wires/cables 
suitable for 90°C operation (EN 60730-1) 

 
 
 
 
 
 
 
 
 

 
 
 

EC1 analog inputs are for dedicated sensors only and should not be connected to 
any other devices. The controller has an internally mounted transformer allowing a 
“mains” 230V 50/60Hz power supplier to be connected directly.

 

Important:

 Keep controller and sensor wiring well separated from mains wiring. 

Minimum recommended distance 30mm.

  

 

Recommended Sensor Positions in Detail: 

(7) ECN-Sxx air-in temperature sensor, S1: Position centrally below the air inlet 
grille. In applications where the average ambient temperature is above 25°C, it may 
be advisable to mount the air sensor in the lower air discharge duct (air-out of the 
evaporator).  
The air temperature sensor should be mounted on spacers in the air duct so that 
there is airflow around it and it is not in contact with any surface material which 
could produce a false temperature reading. 
(9) ECN-Sxx defrost temperature sensor, S5: Position in the evaporator, 
asymmetric closer to the expansion valve or in the air-outlet duct immediately after 
the evaporator (only if S1 is mounted in the air-in duct).

 

Caution:

 The sensor cables can be extended if necessary. The connection must be 

protected against water and dust. 

Setup and Parameter Modification Using the Keypad  

The parameters can be accessed via the 4-button keypad or may be more efficiently 
programmed using a copy key. Refer to further details below. The parameters are 
arranged in two sections; user and administration allowing two levels of access. 

Security lock for parameter modification: 

Press the   and   buttons simultaneously for 10 seconds to unlock/lock the 
controller parameters. “On” (unlocked) / “OF

F

” (locked) will be displayed on the 

screen respectively. When locked, the parameters may be visualized but cannot be 
modified. 

User parameters: 

 

Press the 

Prg

 button for more than 3 seconds. When active, the “prg” LED will 

be illuminated and the first parameter “St” will be displayed. 

  To modify parameters see Parameters modification below. 

Administration parameters: 

 

Press the 

Prg

 simultaneously with the   button for more than 10 seconds. When 

active, the “prg” LED will be illuminated and the first parameter “St” will be 
displayed. 

  To modify parameters see Parameters modification below. 

 

When parameter programming has been completed, press the 

Prg

 button to revert 

back to operation mode. The Prg LED will be turned off. 

 

 