background image

©2015 EasyHeat  

www.easyheat.com

 

OPERATION INSTRUCTIONS

The GC-1 roof and gutter de-icing controller is designed 
to energize the heating cable only when moisture condi-
tions exist and there is risk of freezing. If the tempera-
ture is below 3°C (38°F) and the MSG-1 sensor detects 
moisture, the controller will apply power to the heating 
cable. The cable remains energized until 3 hours (hold 
time) after the sensor is dry. The delay is necessary to 
ensure the heated area dries. If at any time moisture 
is detected the controller restarts the de-icing cycle. 
The optional remote control allows the hold time to 
be dialed from 0.5 to 10hrs. There are 2 LED’s on the 
remote. The top LED indicates the remote is powered 
and functioning, the lower gives the status of the GC-1 
power relay (heating cables on - energized or off - 
de-energized). If the cables are off, pressing the push 
button will turn the cables on for the hold time, and 
then the control will revert to automatic operation. If 
the cables are on, pressing the push button will turn 
the cables off, only if the sensor is dry, otherwise the 

control will continue to finish the hold time in automatic 

operation.
The MSG-1 may be tested for functionality if outside 
temperature is below 3°C (38°F). Submerge 2” of the 
sensor wire in water, the GC-1 should energize the 
heating equipment in the associated zone, the green 
LED on the GC-1 will illuminate. After this test, dry the 
sensor, the heating equipment in the associated zone 
should de-energize after the pre-set hold time.
At the beginning of the heating season and monthly 
during operation inspect for and remove all leaves and 
combustible debris from roofs gutters and downspouts. 
At the beginning of the heating season the MSG-1 must 
be inspected for physical damage and the snow sensor 
surface cleaned. To clean the snow sensor surface: 
1.  Lock-out the power supply to the GC-1.
2.  Remove the MSG-1 sensor housing from the gutter.
3.   With a clean wet swab clean up the surface of the 

snow sensor.

4.  Replace the MSG-1 sensor housing in the gutter.
5.  Reconnect GC-1 to the power supply.

Figure 9

MSG-1 CONNECTION

Figure 8

MSG-1 SENSOR WIRE INSTALLATION

 GC-1 Installation Instructions     5

Summary of Contents for Easyheat GC-1

Page 1: ...es quick detection of potentially damaging roof and gutter icing conditions When moisture is detected the GC 1 activates the de icing cables Figure 1 The MSG 1 sensor operates on low voltage provided by the GC 1 control unit and includes mounting hardware and 30 of wire for connection back to the GC 1 The GC 1 automatically detects and sets up for supply volt ages between 120VAC and 277VAC no dips...

Page 2: ... around the sensor wire See Fig 8 8 Run the communication wire from the MSG 1 back to the GC 1 do not run in the gutter 9 Carefully lock the GC 1 cover into the base hinge The two pieces should easily slide together when open way 45deg WARNINGS 1 This is not a do it your self product A qualified electrician must install the GC 1 system 2 If after carefully reading these instructions you still have...

Page 3: ...ach the MSG 1 communication wire to the 3 seg ment terminal block See Fig 9 14 Tighten down the watertight connectors and form drip loops on all external wires 15 Tighten the four screws on the GC 1 cover snug Figure 3 GC 1 BASE LOCATION Figure 4 CONT GC 1 CONTROLLER WITH SINGLE DUAL PHASE LOAD LESS THAN OR EQUAL TO 24A Figure 5 CONT GC 1 CONTROLLER WITH LOAD HIGHER THAN 24A OR 3 PHASE LOADS Figur...

Page 4: ...s are on pressing the push button will turn the cables off only if the sensor is dry otherwise the control will continue to finish the hold time in automatic operation The MSG 1 may be tested for functionality if outside temperature is below 3 C 38 F Submerge 2 of the sensor wire in water the GC 1 should energize the heating equipment in the associated zone the green LED on the GC 1 will illuminat...

Page 5: ...idity environment 0 to 100 Supply requirements Power supply voltage 120VAC 208VAC 240VAC 277VAC Frequency 60 Hz Maximum power consumption 50W Output characteristics Output type relay wet contact Contact output N O max 24 Amps 277VAC MSG 1 characteristics Power supply voltage 24VAC class2 Maximum Amperage 500mA Accessories Screws coated strapping coated clips Connection Wire 30 5 GC 1 Installation ...

Page 6: ...fication or alteration use beyond rate capacity or improper installation maintenance or application To the extent that you or your agents have supplied specifications information representation of operating conditions or other data to Easy Heat in the selection or design of the Goods and the preparation of Easy Heat s quotation and in the event that actual operating conditions or other conditions ...

Reviews: