E300 Installation and Commissioning Guide
Issue Number: 1
24
Digital I/O 1
25
Digital I/O 2
26
Digital I/O 3
Terminal 24 default function
V threshold 1 output
Terminal 25 default function
Brake control output
Terminal 26 default function
V3 Speed Reference
Type
Positive or negative logic digital inputs, positive logic voltage source outputs
Input / output mode controlled by...
Parameters
F24
,
F25
and
F26
Voltage range
0 V to + 24 V
Operating as an input
Logic mode controlled by...
Parameter
F02
Absolute maximum applied voltage range
- 3 V to + 30 V
Operating as an output
Nominal maximum output current
100 mA (Digital I/O 1 & 2 combined), 100 mA (Digital I/O 3 & + 24 V User output
combined)
Maximum output current
100 mA, 200 mA (total including all Digital I/O)
27
Digital Input 4
28
Digital Input 5
Terminal 27 default function
FAST disable input
Terminal 28 default function
Direction input
Type
Negative or positive logic digital inputs
Logic mode controlled by...
Parameter
F02
Voltage range
0 V to + 24 V
Absolute maximum applied voltage range
- 3 V to + 30 V
29
Digital Input 6
Terminal 29 default function
V1 Speed Reference
Type
Negative or positive logic digital inputs
Logic mode controlled by...
Parameter
F02
Voltage range
0 V to + 24 V
Absolute maximum applied voltage range
- 3 V to + 30 V
30
0V common
Function
Common connection control terminals 21 to 31
31
Safe Torque Off (STO), Drive enable
Type
Positive logic only digital input
Voltage range
0 V to + 24 V
Absolute maximum applied voltage
+ 30 V
The Safe Torque Off (STO) function may be used in a safety-related application in preventing the drive from generating torque in the motor to a high
level of integrity. The system designer is responsible for ensuring that the complete system is safe and designed correctly according to the relevant
safety standards. If the Safe Torque Off (STO) function is not required, this terminal is the Drive enable.
41
Relay contacts
42
Default function
Drive OK indicator
Contact voltage rating
240 Vac, Installation over-voltage category II
Contact maximum current rating
2 A AC 240 V, 4 A DC 30 V resistive load, 0.5 A DC 30 V inductive load (L/R = 40 ms)
Contact minimum recommended rating
12 V 100 mA
Contact type
Normally open
Default contact condition
Closed when power applied and drive OK
Update period
4 ms