3.5 Dimensions and mounting methods
The drive can be either surface or through-panel mounted using the appropriate brackets. The following drawings show the dimensions of the drive
and mounting holes for each method to allow a back plate to be prepared. The Through-panel mounting kit is not supplied with the drive and can be
purchased separately. The relevant part numbers are shown the table below.
Table 3-2 Through-panel mounting kit part number numbers for size 3 to 7
3.5.1 Surface mounting
Figure 3-9 Drive dimensions, Surface mount (size 3 to 7)
Each mounting bracket contains 4 mounting holes. The outer holes (5.5 mm) x 2 should be used for mounting the drive to the backplate, as this
allows the heatsink fan to be replaced without removing the drive from the backplate. The inner holes (6.5 mm) x 2 are used for Unidrive SP size 1
retro fit applications.
Size
CT part number
3
3470-0053
4
3470-0056
5
3470-0067
6
3470-0055
7
3470-0079
If the drive has been used at high load levels for a period of time, the heatsink can reach temperatures in excess of 70 °C (158 °F).
Human contact with the heatsink should be prevented.
Many of the drives in this product range weigh in excess of 15 kg (33 lb). Use appropriate safeguards when lifting these models.
WARNING
WARNING
C
B
D
A
Size
A
B
C
D
mm
in
mm
in
mm
in
mm
in
3
382
15.04
365
14.37
83
3.27
200
7.87
4
391
15.39
124
4.88
5
143
5.63
202
7.95
6
389
15.32
210
8.27
227
8.94
7
508
20.0
508
20
270
10.63
279
11
NOTE