STEP 4: E2E Baud Rate Settings

Because the COM A and COM D networks of an RMCC/BEC/BCU must communicate at the same baud rate, 

all I/O boards connected to the RMCC/BEC/BCU were also set to communicate at 19200 baud. Because the 

default E2E baud rate for I/O networks is 9600 baud, you will need to change the COM2 baud rate setting. 

This must be done in the C3: Serial tab of the E2E’s General Controller Info screens.

1. Log into the E2 with Level 4 password access.
2. Press 



 

to access the 

General Controller Info 

screen.

3. Press 

+

 

(or 

two times) to access the 

C3: Serial 

tab (

Figure 2).

You will need to set two parameters in the 

C3: Serial

 tab.

Figure 1  - COM2 Port Location, E2E (Right Side Interior)

Summary of Contents for E2 Enhanced RX

Page 1: ...RS232 COM C host network to connect all units to a modem for alarm dial out E2Es may use either Echelon or Ethernet for box to box communication The existing host network wiring may not be used for E2E box to box communication you will either have to rewire using approved Echelon network wire or wire CAT 5 cable to an approved network router or switch Refer to the E2E User s Guide for more informa...

Page 2: ...CC BEC BCU I O networks Set the three jumpers to the middle I O terminated position if the port is at the end of a network segment or the hub of a star configuration and down NO unterminated if the port is in the middle of a segment There is one set of RS485 jumpers for each RS485 port COM2A 2B COM6 and COM4A B Jumpers J8 J10 are located directly above the COM2A connector port and jumpers J11 J13 ...

Page 3: ... same baud rate all I O boards connected to the RMCC BEC BCU were also set to communicate at 19200 baud Because the default E2E baud rate for I O networks is 9600 baud you will need to change the COM2 baud rate setting This must be done in the C3 Serial tab of the E2E s General Controller Info screens 1 Log into the E2 with Level 4 password access 2 Press to access the General Controller Info scre...

Page 4: ...collectively Emerson reserves the right to modify the designs or specifications of such products at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any product remains solely with the purchaser and end user 026 4157 19 FEB 2016 Emerson is a trademark of Emerson Electric Co ...

Reviews: