Document Part # 026-4157 Rev 0 19-FEB-2016
Page 3 of 4
©2016 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
STEP 4: E2E Baud Rate Settings
Because the COM A and COM D networks of an RMCC/BEC/BCU must communicate at the same baud rate,
all I/O boards connected to the RMCC/BEC/BCU were also set to communicate at 19200 baud. Because the
default E2E baud rate for I/O networks is 9600 baud, you will need to change the COM2 baud rate setting.
This must be done in the C3: Serial tab of the E2E’s General Controller Info screens.
1. Log into the E2 with Level 4 password access.
2. Press
to access the
General Controller Info
screen.
3. Press
+
(or
two times) to access the
C3: Serial
tab (
You will need to set two parameters in the
C3: Serial
tab.
Figure 1 - COM2 Port Location, E2E (Right Side Interior)