Emerson dixell XW60LT Installing And Operating Instructions Download Page 5

 

 

1592027610 XW60LT-XW60LRT GB r1.0 13.02.2012.doc 

XW60LT – XW60LRT 

5/6 

Message  Cause 

Outputs 

dA 

Door open 

Compressor and fans restarts  

EA 

External alarm 

Output unchanged. 

CA 

Serious external alarm (i1F=bAL)  All outputs OFF. 

CA 

Pressure switch alarm (i1F=PAL)  All outputs OFF 

rtC 

Real time clock alarm 

Alarm output ON; Other outputs unchanged; 
Defrosts according to par. idF Set real time clock 
has to be set. 

rtF 

Real time clock board failure 

Alarm output ON; Other outputs unchanged; 
Defrosts according to par. idF. Contact the 
service. 

15.1

 

SILENCING BUZZER / ALARM RELAY OUTPUT 

-

 

tbA=Y: the buzzer and the relay are is silenced by pressing any key.  

-

 

tbA=n:  only  the  buzzer  is  silenced  while  the  alarm  relay  is  on  until  the  alarm  condition 
recovers. 

15.2

 

ALARM RECOVERY  

Probe  alarms  P1,  P2,  P3  and  P4  start  some  seconds  after  the  fault  in  the  related  probe;  they 
automatically stop some seconds after the probe restarts normal operation. Check connections before 
replacing the probe. 
Temperature alarms HALAHA2 and LA2 automatically stop as soon as the temperature returns to 
normal values. 
Alarms EA and CA (with i1F=bAL) recover as soon as the digital input is disabled. 
Alarm CA (with i1F=PAL) recovers only by switching off and on the instrument. 

15.3

 

OTHER MESSAGES 

on 

Keyboard enabled after automatic lock. 

LOC  Keyboard automatically locked 

Pon  Keyboard unlocked. 
PoF  Keyboard locked 

noP 

In programming mode: none parameter is present in Pr1 
On the display or in dP2, dP3, dP4: the selected probe is nor enabled 

16.

 

TECHNICAL DATA 

Housing: self extinguishing ABS 
Case: 
facia 38x185 mm; depth [XW60LT: 76mm], [XW60LRT: 40mm] 
Mounting: panel mounting in a 150x31 mm panel cut-out with the 2 metal brackets supplied 
Protection: IP20 
Frontal protection: IP65 
Connections: screw terminal block 

 2.5 mm

2

 heat-resistant wiring and 6.3mm Faston 

Power supply: 230Vac or. 110Vac or 24Vac 

 10% 

Power absorption: 5VA max 
Display:
 3 digits, white LED, 14.2 mm high 
Inputs: Up to 4 NTC or PTC probes 
Digital inputs:
 2 free voltage 
Relay outputs for XW60LT models: Total current on loads MAX. 20A 

Compressor: relay SPST 20(8) A, 250Vac  
Light: relay SPST 8 or 16(3) A, 250Vac  
Fans: relay SPST 8(3) A, 250Vac 

 

Defrost: relay SPST 8(3) A, 250Vac 

Relay outputs for XW60LRT models: Total current on loads MAX. 16A 

Compressor: relay SPST 20(8)A, 250Vac  
Light: relay SPST 5A, 250Vac  
Fans: relay SPST 5A, 250Vac 

 

Defrost: relay SPST 8(3) A, 250Vac  

Other output: buzzer 
Serial output: TTL standard  
Communication protocol: Modbus - RTU 
Data storing:
 on the non-volatile memory (EEPROM) 
Internal clock back-up: 24 hours (only for model with RTC) 
Kind of action: 1B  
Pollution degree: 2  
Software class: 
Rated impulsive voltage: 2500V  
Over voltage Category: II 
Operating temperature: 
0 to 60 °C (32 to 140°F)  
Storage temperature: -30 to 85°C (-22 to 185°F).  
Relative humidity: 20 to 85% (not condensing) 
Measuring and regulation range:  

NTC probe: -40 to 110°C (-40 to 230°F) 
PTC probe: -50 to 150°C (-58 to 302°F) 

Resolution: 0.1°C or 1°C or 1°F (selectable)  
Accuracy (ambient temp. 25°C):  ±0.7°C ±1 digit 

17.

 

CONNECTIONS 

17.1

 

XW60LT 

 

 

Supply: 120Vac or 24Vac: connect to terminals 11-12 
The X-REP
 output is optional 
The light relay can be also 16(5)A according to the model 
 

17.2

 

XW60LRT 

 

 

18.

 

DEFAULT SETTING VALUES 

Label Name 

Range 

°C/°F 

Level 

Set  Set point 

LS to US 

-5.0 

- - - 

rtC*  Real time clock menu 

Pr1 

Hy  Differential 

[0.1 to 25.5°C] 

[1 to 45°F] 

2.0 

Pr1 

LS  Minimum set point 

[-55°C to SET] 
[-67°F to SET] 

-50.0 

Pr2 

US  Maximum set point 

[SET to 150°C] 
[SET to 302°F] 

110 

Pr2 

ot  Thermostat probe calibration 

[-12 to 12°C] 
[-21 to 21°F] 

0.0 

Pr1 

P2P  Evaporator probe presence 

n=not present; Y=present 

Pr1 

oE  Evaporator probe calibration 

[-12 to 12°C] 
[-21 to 21°F] 

0.0 

Pr2 

P3P  Third probe presence 

n=not present; Y=present 

Pr2 

o3  Third probe calibration 

[-12 to 12°C] 
[-21 to 21°F] 

Pr2 

P4P 

Fourth probe presence (only for 
XW60LT) 

n=not present; Y=present 

Pr2 

o4 

Fourth probe calibration (only for 
XW60LT) 

[-12 to 12°C] 
[-21 to 21°F] 

Pr2 

odS  Outputs delay at start up 

0 to 255 min 

Pr2 

AC  Anti-short cycle delay 

0 to 50 min 

Pr1 

Ac1  Second compressor start delay 

0 to 255 sec 

Pr2 

rtr  P1-P2 percentage for regulation 

0 to 100 (100=P1 , 0=P2) 

100 

Pr2 

CCt  Continuous cycle duration 

0.0 to 24h00min 

0.0 

Pr2 

CCS  Set point for continuous cycle 

[-55.0 to 150.0°C] 

[-67 to 302°F] 

-5 

Pr2 

Con  Compressor ON time with faulty probe 

0 to 255 min 

15 

Pr2 

CoF  Compressor OFF time with faulty probe 

0 to 255 min 

30 

Pr2 

CF  Temperature measurement unit 

°C to °F 

°C 

Pr2 

rES  Resolution 

in=integer; dE= dec.point 

dE 

Pr1 

Lod  Probe displayed 

P1; P2 

P1 

Pr2 

rEd

X-REP display 

P1; P2; P3; P4; SEt; dtr 

P1 

Pr2 

dLy  Display temperature delay   

0.0 to 20min00sec (10 sec) 

0.0 

Pr2 

dtr  P1-P2 percentage for display 

1 to 99 

50 

Pr2 

EdF*  Kind of interval for defrost 

rtC; in 

in 

Pr2 

tdF  Defrost type 

EL=el. heater;  in= hot gas 

EL 

Pr1 

dFP  Probe selection for defrost termination 

nP; P1; P2; P3; P4 

P2 

Pr2 

dtE  Defrost termination temperature 

-50 to 50°C 

Pr1 

idF  Interval between defrost cycles 

1 to 120 hours 

Pr1 

MdF  (Maximum) length for defrost 

0 to 255 min 

30 

Pr1 

dSd  Start defrost delay 

0 to 99min 

Pr2 

dFd  Displaying during defrost 

rt; it; SEt; DEF 

it 

Pr2 

dAd  MAX display delay after defrost 

0 to 255 min 

30 

Pr2 

Fdt  Draining time 

0 to 120 min 

Pr2 

dPo  First defrost after start-up 

n=after idF; y=immed. 

Pr2 

dAF  Defrost delay after fast freezing 

0.0 to 23h50min 

0.0 

Pr2 

Fnc  Fan operating mode 

C-n; o-n; C-y; o-Y 

o-n 

Pr1 

Fnd  Fan delay after defrost 

0 to 255 min 

10 

Pr1 

FCt 

Differential of temperature for forced 
activation of fans 

0 yo 50°C 

10 

Pr2 

FSt  Fan stop temperature 

[-50 to 50°C] 

[-55 to 122°F] 

Pr1 

Fon  Fan on time with compressor off 

0 to 15 min 

Pr2 

FoF  Fan off time with compressor off 

0 to 15 min 

Pr2 

FAP  Probe selection for fan management 

nP; P1; P2; P3; P4 

P2 

Pr2 

ACH  Kind of action for auxiliary relay  

CL; Ht 

cL 

Pr2 

SAA  Set Point for auxiliary relay 

[-55.0 to 150°C] 

[-67 to 302°F] 

0,0 

Pr2 

SHy  Differential for auxiliary relay 

[0.1 to 25.5°C] 

[1 to 45°F] 

2,0 

Pr2 

ArP  Probe selection for auxiliary relay 

nP; P1; P2; P3; P4 

nP 

Pr2 

Sdd  Auxiliary relay operating during defrost 

n(0); Y(1) 

Pr2 

ALP  Alarm probe selection  

nP; P1; P2; P3; P4 

P1 

Pr2 

ALC  Temperat. alarms configuration 

rE= related to set; 

Ab = absolute 

Ab 

Pr2 

ALU  MAXIMUM temperature alarm 

[SET to 150.0°C] 

[SET to 302°F] 

110,0 

Pr1 

ALL  Minimum temperature alarm 

[-55.0°C to SET] 

[-67°F to SET] 

-50,0 

Pr1 

AFH  Differential for temperat. alarm recovery 

[0.1 to 25.5°C] 

[1 to 45°F] 

2,0 

Pr2 

ALd  Temperature alarm delay 

0 to 255 min 

15 

Pr2 

dAo  Delay of temperature alarm at start up 

0.0 to 23h50min 

1,3 

Pr2 

AP2  Probe for temperat. alarm of condenser 

nP; P1; P2; P3; P4 

P4 

Pr2 

AL2  Condenser for low temperat. alarm 

[-55 to 150°C] 
[-67 to 302°F] 

-40 

Pr2 

AU2  Condenser for high temperat. alarm 

[-55 to 150°C] 
[-67 to 302°F] 

110 

Pr2 

Summary of Contents for dixell XW60LT

Page 1: ...or controller without RTC EdF rtC defrosts are scheduled by using a real time clock system depending on the hours set in the parameters Ld1 Ld6 during workdays and in Sd1 Sd6 during holidays Other parameters are used to control defrost cycles its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is s...

Page 2: ...owed by the HY parameter NOW THE HIDDEN MENU IS DISPLAYED 3 Select the required parameter 4 Press the SET key to display its value 5 Use UP or DOWN keys to change its value 6 Press SET to store the new value and move to the following parameter To exit press SET UP keys or wait for 15 sec without pressing any key NOTE1 if no parameters are present in Pr1 after 3 sec the noP message will be displaye...

Page 3: ...obe P3 Probe 3 display probe P4 Probe 4 Sdd Auxiliary relay off during defrost n Y n the auxiliary relay operates during defrost Y the auxiliary relay is switched off during defrost ALARMS ALP Probe selection for alarm nP P1 P2 P3 P4 nP no probe the temperature alarms are disabled P1 Probe 1 Thermostat probe P2 Probe 2 evaporator probe P3 Probe 3 display probe P4 Fourth probe ALC Temperature alarm...

Page 4: ... digital input will change the status of the auxiliary relay 9 7 INVERSION OF THE KIND OF ACTION HEATING COOLING i1F or i2F Htr This function allows to invert the regulation of the controller from cooling to heating and viceversa 9 8 ENERGY SAVING i1F or i2F ES The Energy Saving function allows to change the set point value as the result of the SET HES parameter sum This function is enabled until ...

Page 5: ... Set Set point LS to US 5 0 rtC Real time clock menu Pr1 Hy Differential 0 1 to 25 5 C 1 to 45 F 2 0 Pr1 LS Minimum set point 55 C to SET 67 F to SET 50 0 Pr2 US Maximum set point SET to 150 C SET to 302 F 110 Pr2 ot Thermostat probe calibration 12 to 12 C 21 to 21 F 0 0 Pr1 P2P Evaporator probe presence n not present Y present Y Pr1 oE Evaporator probe calibration 12 to 12 C 21 to 21 F 0 0 Pr2 P3...

Page 6: ... rtc dAY Current day Sun to SAt rtc Hd1 First weekly holiday Sun to SAt nu nu rtc Hd2 Second weekly holiday Sun to SAt nu nu rtc ILE Energy Saving cycle start during workdays 0 0 to 23h50min 0 rtc dLE Energy Saving cycle length during workdays 0 0 to 24h00min 0 rtc ISE Energy Saving cycle start on holidays 0 0 to 23h50min 0 rtc dSE Energy Saving cycle length on holidays 0 0 to 24h00min 0 rtc Ld1 1...