1592027610 XW60LT-XW60LRT GB r1.0 13.02.2012.doc 

XW60LT – XW60LRT 

1/6 

Digital controller for medium-low temperature 

refrigeration applications

 

XW60LT – XW60LRT 

1.

 

GENERAL WARNING ........................................................................................................... 1

 

2.

 

GENERAL DESCRIPTION .................................................................................................... 1

 

3.

 

CONTROLLING LOADS ....................................................................................................... 1

 

4.

 

FRONT PANEL COMMANDS ............................................................................................... 1

 

5.

 

AUTOMATIC KEYBOARD LOCK .......................................................................................... 2

 

6.

 

MAX & MIN TEMPERATURE MEMORIZATION .................................................................... 2

 

7.

 

MAIN FUNCTIONS ............................................................................................................... 2

 

8.

 

PARAMETERS ..................................................................................................................... 2

 

9.

 

DIGITAL INPUTS .................................................................................................................. 4

 

10.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS ............................................................. 4

 

11.

 

X-REP OUTPUT – OPTIONAL .............................................................................................. 4

 

12.

 

INSTALLATION AND MOUNTING ......................................................................................... 4

 

13.

 

ELECTRICAL CONNECTIONS.............................................................................................. 4

 

14.

 

HOW TO USE THE HOT KEY .............................................................................................. 4

 

15.

 

ALARM SIGNALS ................................................................................................................. 4

 

16.

 

TECHNICAL DATA ............................................................................................................... 5

 

17.

 

CONNECTIONS ................................................................................................................... 5

 

18.

 

DEFAULT SETTING VALUES ............................................................................................... 5

 

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick reference. 

 

The  instrument  shall  not  be  used  for  purposes  different  from  those  described  hereunder.  It  cannot  be 
used as a safety device. 

 

Check the application limits before proceeding. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not  expose  to  water  or moisture: use the controller only within the operating limits avoiding sudden 
temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.p.A.” (see 
address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure  that  the  wires for probes, loads and the power supply are separated and far enough from each 
other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with 
inductive loads could be useful. 

 

Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring the 
same and unchanged functionality. 

2.

 

GENERAL DESCRIPTION 

Models  XW60LT  and  XW60LRT,  format  38x185mm,  are microprocessor based controllers, suitable 
for applications on medium or low temperature ventilated refrigerating units. They have 4 relay outputs 
to  control  compressor,  fan,  defrost,  which  can  be  either  electrical  or  reverse  cycle  (hot  gas)  and  a 
fourth configurable output. They could be provided with a Real Time Clock which allows programming 
of up to 6 daily defrost cycles, divided into holidays and workdays.  A “Day and Night” function with 
two different set points is fitted for energy saving. They are also provided with up to four NTC or PTC 
probe inputs, the first one for temperature control, the second one, to be located onto the evaporator, 
to control the defrost termination temperature and to managed the fan. One of the digital inputs can 
operate  as  third  temperature  probe.  The  fourth  probe  is  used  to  signal  the  condenser  temperature 
alarm or to display a temperature. NOTE: the fourth probe is available only for XW60LT models. 
The  HOT  KEY  output  allows  to  connect  the  unit,  by  means  of  the external module XJ485-CX, to a 
network  line  ModBUS-RTU  compatible  such  as  the 

dIXEL 

monitoring  units  of  X-WEB  family.  It 

allows to program the controller by means the HOT KEY programming keyboard. 
The  instrument  is  fully  configurable  through  special  parameters  that  can  be  easily  programmed 
through the keyboard. 

3.

 

CONTROLLING LOADS 

3.1

 

COMPRESSOR 

The  regulation  is  performed  according 
to  the  temperature  measured  by  the 
thermostat  probe  with  a  positive 
differential  from  the  set  point:  if  the 
temperature increases and reaches set 
point plus differential the compressor is 
started  and  then  turned  off  when  the 
temperature  reaches  the  set  point 
value again. 

Time

Temper.

Compr.

SET

ON

 

In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through 
parameters Con and CoF

3.2

 

DEFROST  

Two defrost modes are available through the tdF parameter: defrost through electrical heater (tdF = 
EL
) and hot gas defrost (tdF = in). 
The defrost interval depends on the presence of the RTC (optional). If the RTC is present is controlled 
by means of parameter EdF:  

-

 

EdF=in: a defrost starts after elapsing the idF time (standard way for controller without RTC). 

EdF=rtC:  defrosts  are  scheduled  by  using a real time clock system, depending on the hours set in 
the parameters Ld1..Ld6, during workdays, and in Sd1…Sd6 during holidays. 

Other  parameters  are  used  to  control  defrost  cycles:  its  maximum  length  (MdF)  and  two  defrost 
modes: timed or controlled by the evaporator’s probe (P2P).  
At the end of defrost dripping time is started, its length is set in the Fdt parameter. With Fdt=0 the 
dripping time is disabled. 

3.3

 

CONTROL OF EVAPORATOR FANS 

The fan control mode is selected by means of the FnC parameter: 

-

 

FnC=C_n: fans will switch ON and OFF with the compressor and not run during defrost; 

-

 

FnC=o_n: fans will run even if the compressor is off, and not run during defrost; 

-

 

FnC=C_Y: fans will switch ON and OFF with the compressor and run during defrost; 

-

 

FnC=o_Y: fans will run continuously also during defrost. 

 
After defrost, there is a timed fan delay allowing for drip time, set by means of the Fnd parameter. 
An additional parameter FSt provides the setting of temperature, detected by the evaporator probe, 
above  which  the  fans  are  always  OFF.  This  is  used  to  make  sure  circulation  of  air  only  if  his 
temperature is lower than set in FSt

3.3.1

 

Forced activation of evaporator fans 

This function, managed by the FCt parameter, is designed to avoid short cycles of evaporator fans, 
which  could happen when the controller is switched on or after a defrost (when the room air warms 
the evaporator). If the temperature difference between the evaporator and the room probes is higher 
than  the  value  set  in  the  FCt  parameter  the  fans  are  switched  on.  With  FCt=0  this  function  is 
disabled. 

3.3.2

 

Fans cyclic activation with compressor off. 

When FnC=C-n or C-Y (fans working in parallel with the compressor), by means of the Fon and FoF 
parameters the fans can carry out on and off cycles even if the compressor is switched off. When the 
compressor is stopped the fans go on working for the Fon time. With Fon=0 the fans remain always 
off, when the compressor is off. 

3.4

 

AUXILIARY OUTPUT CONFIGURATION  

The  functioning  of  the  auxiliary  relay  can  be  set  by  the  oAx  parameters  according  to  the  kind  of 
application. In the following paragraph the possible settings are explaided. 

3.4.1

 

Auxiliary thermostat 

A  possible  use  is  the  anti  condensing  heater,  with  the  possibility  of  switching  it  on  and  off  also  by 
keyboard. 
 
Parameters involved:  

-

 

ACH:  kind of regulation for the auxiliary relay: Ht: heating; cL: cooling; 

-

 

SAA:  set point for auxiliary relay; 

-

 

SHy: differential for auxiliary relay; 

-

 

ArP: probe for auxiliary relay; 

-

 

Sdd: auxiliary output off during defrost. 

 
The differential is given by the SHy parameter. 
The auxiliary relay can be switched on also by using the AUX button. In this case it remains on till it’s 
manually switched off. 
 
NOTE: If oAx=AUS and ArP=nP (no probe for auxiliary output), the AUX relay can be activated only 
by pushing the AUX button of the keyboard.  

3.4.2

 

On/off relay – oAx = onF 

In this case the relay is activated when the controller is turned on and de-activated when the controller 
is turned off. 

3.4.3

 

Neutral zone regulation 

With oAx=db the AUX relay can control a heater element to perform a neutral zone action. 

-

 

output oAx cut in = SET-HY; 

-

 

output oAx cut out = SET.  

3.4.4

 

Second compressor  

With  oAx=CP2,  the  AUX  relay  operates  as  second  compressor:    it  is  activated  in  parallel  with  the 
relay  of  the  first  compressor,  with  a  proper  activation  delay  (set  in  the  AC1  parameter).  Both  the 
compressors are switched off at the same time. 

3.4.5

 

Alarm relay 

With oAx=ALr the AUX relay operates as alarm relay. It is activated every time an alarm happens. Its 
status depends on the tbA parameter:  

-

 

tbA=Y: the relay is silenced by pressing any key; 

-

 

tbA=n: the alarm relay remains on until the alarm condition recovers. 

3.4.6

 

Night blind management during energy saving cycles 

With  oAx=HES  the  AUX  relay  operates  to  manage  the  night blind: the relay is energised when the 
energy saving cycle is activated by digital input, frontal button or RTC (optional). 

4.

 

FRONT PANEL COMMANDS 

 

 

 

To display target set point; in programming mode it selects a parameter or 
confirm an operation. 

 

(DEF) To start a manual defrost. 

 

(UP) To see the max stored temperature; in programming mode it browses the 
parameter codes or increases the displayed value. 

 

(DOWN) To see the min stored temperature; in programming mode it browses 
the parameter codes or decreases the displayed value. 

 

(OFF) To switch the instrument off, if onF=oFF

 

(LiG) To switch the light, if oA3=Lig

 

KEY COMBINATIONS: 

Summary of Contents for dixell XW60LT

Page 1: ...or controller without RTC EdF rtC defrosts are scheduled by using a real time clock system depending on the hours set in the parameters Ld1 Ld6 during workdays and in Sd1 Sd6 during holidays Other parameters are used to control defrost cycles its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is s...

Page 2: ...owed by the HY parameter NOW THE HIDDEN MENU IS DISPLAYED 3 Select the required parameter 4 Press the SET key to display its value 5 Use UP or DOWN keys to change its value 6 Press SET to store the new value and move to the following parameter To exit press SET UP keys or wait for 15 sec without pressing any key NOTE1 if no parameters are present in Pr1 after 3 sec the noP message will be displaye...

Page 3: ...obe P3 Probe 3 display probe P4 Probe 4 Sdd Auxiliary relay off during defrost n Y n the auxiliary relay operates during defrost Y the auxiliary relay is switched off during defrost ALARMS ALP Probe selection for alarm nP P1 P2 P3 P4 nP no probe the temperature alarms are disabled P1 Probe 1 Thermostat probe P2 Probe 2 evaporator probe P3 Probe 3 display probe P4 Fourth probe ALC Temperature alarm...

Page 4: ... digital input will change the status of the auxiliary relay 9 7 INVERSION OF THE KIND OF ACTION HEATING COOLING i1F or i2F Htr This function allows to invert the regulation of the controller from cooling to heating and viceversa 9 8 ENERGY SAVING i1F or i2F ES The Energy Saving function allows to change the set point value as the result of the SET HES parameter sum This function is enabled until ...

Page 5: ... Set Set point LS to US 5 0 rtC Real time clock menu Pr1 Hy Differential 0 1 to 25 5 C 1 to 45 F 2 0 Pr1 LS Minimum set point 55 C to SET 67 F to SET 50 0 Pr2 US Maximum set point SET to 150 C SET to 302 F 110 Pr2 ot Thermostat probe calibration 12 to 12 C 21 to 21 F 0 0 Pr1 P2P Evaporator probe presence n not present Y present Y Pr1 oE Evaporator probe calibration 12 to 12 C 21 to 21 F 0 0 Pr2 P3...

Page 6: ... rtc dAY Current day Sun to SAt rtc Hd1 First weekly holiday Sun to SAt nu nu rtc Hd2 Second weekly holiday Sun to SAt nu nu rtc ILE Energy Saving cycle start during workdays 0 0 to 23h50min 0 rtc dLE Energy Saving cycle length during workdays 0 0 to 24h00min 0 rtc ISE Energy Saving cycle start on holidays 0 0 to 23h50min 0 rtc dSE Energy Saving cycle length on holidays 0 0 to 24h00min 0 rtc Ld1 1...