Digital controller for medium-low temperature 

refrigeration applications

 

XW60LH 

1.

 

GENERAL WARNING....................................................................................................................1

 

2.

 

GENERAL DESCRIPTION ............................................................................................................1

 

3.

 

CONTROLLING LOADS ................................................................................................................1

 

4.

 

FRONT PANEL COMMANDS .......................................................................................................1

 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION ..........................................................................2

 

6.

 

MAIN FUNCTIONS ........................................................................................................................2

 

7.

 

PARAMETERS...............................................................................................................................2

 

8.

 

DIGITAL INPUTS ...........................................................................................................................4

 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS ...................................................................4

 

10.

 

X-REP OUTPUT – OPTIONAL ......................................................................................................4

 

11.

 

INSTALLATION AND MOUNTING ................................................................................................4

 

12.

 

ELECTRICAL CONNECTIONS .....................................................................................................4

 

13.

 

HOW TO USE THE HOT KEY .......................................................................................................4

 

14.

 

ALARM SIGNALS ..........................................................................................................................4

 

15.

 

TECHNICAL DATA ........................................................................................................................5

 

16.

 

CONNECTIONS .............................................................................................................................5

 

17.

 

DEFAULT SETTING VALUES .......................................................................................................5

 

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick 

reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be 

used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring 

the same and unchanged functionality. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden 

temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” (see 

address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each 

other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel 

with inductive loads could be useful. 

 

Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring 

the same and unchanged functionality. 

2.

 

GENERAL DESCRIPTION 

Model XW60LH, format 38x185mm, is microprocessor based controller, suitable for applications on 

medium or low temperature ventilated refrigerating units. It has 4 relay outputs to control compressor, 

fan, defrost, which can be either electrical or reverse cycle (hot gas) and a fourth configurable output. 

They could be provided with a Real Time Clock which allows programming of up to 6 daily defrost 

cycles, divided into holidays and workdays.  A “Day and Night” function with two different set points is 

fitted for energy saving. They are also provided with up to four NTC or PTC probe inputs, the first one 

for temperature control, the  second one, to be located onto the evaporator, to control the defrost 

termination temperature and to managed the fan.  One of the digital inputs  can operate as third 

temperature probe. The fourth probe is used to signal the condenser temperature alarm or to display 

a temperature. 

The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a 

network line ModBUS-RTU compatible such as the 

dIXEL 

monitoring units of X-WEB family. It 

allows to program the controller by means the HOT KEY programming keyboard. 

The instrument is fully configurable through special parameters that can be easily programmed 

through the keyboard. 

3.

 

CONTROLLING LOADS 

3.1

 

COMPRESSOR 

The regulation is performed according 

to the temperature measured by the 

thermostat probe with a positive 

differential from the set point: if the 

temperature increases and reaches 

set point plus differential the 

compressor is started and then turned 

off when the temperature reaches the 

set point value again. 

 

In case of fault in the thermostat probe the start and stop of the compressor are timed through 

parameters Con and CoF

3.2

 

DEFROST  

Two defrost modes are available through the tdF parameter: defrost through electrical heater (tdF = 

EL) and hot gas defrost (tdF = in). 

The defrost interval depends on the presence of the RTC (optional). If the RTC is present is 

controlled by means of parameter EdF:  

-

 

EdF=in: a defrost starts after elapsing the idF time (standard way for controller without RTC). 

EdF=rtC: defrosts are scheduled by using a real time clock system, depending on the hours set in 

the parameters Ld1..Ld6, during workdays, and in Sd1…Sd6 during holidays. 

Other parameters are used to control defrost cycles:  its maximum length (MdF) and two defrost 

modes: timed or controlled by the evaporator’s probe (P2P).  

At the end of defrost dripping time is started, its length is set in the Fdt parameter. With Fdt=0 the 

dripping time is disabled. 

3.3

 

CONTROL OF EVAPORATOR FANS 

The fan control mode is selected by means of the FnC parameter: 

-

 

FnC=C_n: fans will switch ON and OFF with the compressor and not run during defrost; 

-

 

FnC=o_n: fans will run even if the compressor is off, and not run during defrost; 

-

 

FnC=C_Y: fans will switch ON and OFF with the compressor and run during defrost; 

-

 

FnC=o_Y: fans will run continuously also during defrost. 

 

After defrost, there is a timed fan delay allowing for drip time, set by means of the Fnd parameter. 

An additional parameter FSt provides the setting of temperature, detected by the evaporator probe, 

above which the fans are always OFF. This is used to make sure circulation of air only if his 

temperature is lower than set in FSt
3.3.1

 

Forced activation of evaporator fans 

This function, managed by the FCt parameter, is designed to avoid short cycles of evaporator fans, 

which could happen when the controller is switched on or after a defrost (when the room air warms 

the evaporator). If the temperature difference between the evaporator and the room probes is higher 

than the value set in  the  FCt  parameter the fans are switched on. With FCt=0  this  function is 

disabled. 
3.3.2

 

Fans cyclic activation with compressor off. 

When FnC=C-n or C-Y (fans working in parallel with the compressor), by means of the Fon and FoF 

parameters the fans can carry out on and off cycles even if the compressor is switched off. When the 

compressor is stopped the fans go on working for the Fon time. With Fon=0 the fans remain always 

off, when the compressor is off. 

3.4

 

AUXILIARY OUTPUT CONFIGURATION  

The functioning of the auxiliary relay can be set by the oAx  parameters  according to the kind of 

application. In the following paragraph the possible settings are explaided. 
3.4.1

 

Auxiliary thermostat 

A possible use is the anti condensing heater, with the possibility of switching it on and off also by 

keyboard. 

 

Parameters involved:  

-

 

ACH:  kind of regulation for the auxiliary relay: Ht: heating; cL: cooling; 

-

 

SAA:  set point for auxiliary relay; 

-

 

SHy: differential for auxiliary relay; 

-

 

ArP: probe for auxiliary relay; 

-

 

Sdd: auxiliary output off during defrost. 

 

The differential is given by the SHy parameter. 

The auxiliary relay can be switched on also by using the AUX button. In this case it remains on till it’s 

manually switched off. 

 

NOTE: If oAx=AUS and ArP=nP (no probe for auxiliary output), the AUX relay can be activated only 

by pushing the AUX button of the keyboard.  
3.4.2

 

On/off relay – oAx = onF 

In this case the relay is activated when the controller is turned on and de-activated when the 

controller is turned off. 
3.4.3

 

Neutral zone regulation 

With oAx=db the AUX relay can control a heater element to perform a neutral zone action. 

-

 

output oAx cut in = SET-HY; 

-

 

output oAx cut out = SET.  

3.4.4

 

Second compressor  

With oAx=CP2, the AUX relay operates as second compressor:  it is activated in parallel with the 

relay of the first compressor, with a proper  activation delay (set in the AC1  parameter). Both the 

compressors are switched off at the same time. 
3.4.5

 

Alarm relay 

With oAx=ALr the AUX relay operates as alarm relay. It is activated every time an alarm happens. 

Its status depends on the tbA parameter:  

-

 

tbA=Y: the relay is silenced by pressing any key; 

-

 

tbA=n: the alarm relay remains on until the alarm condition recovers. 

3.4.6

 

Night blind management during energy saving cycles 

With oAx=HES the AUX relay operates to manage the night blind: the relay is energised when the 

energy saving cycle is activated by digital input, frontal button or RTC (optional). 

4.

 

FRONT PANEL COMMANDS 

 

 

 

To display target set point; in programming mode it selects a parameter or 

confirm an operation. 

 

(DEF) To start a manual defrost. 

 

(UP) To see the max stored temperature; in programming mode it browses the 

parameter codes or increases the displayed value. 

 

(DOWN) To see the min stored temperature; in programming mode it browses 

the parameter codes or decreases the displayed value. 

 

(OFF) To switch the instrument off, if onF=oFF

 

(LiG) To switch the light, if oA3=Lig

 
 
 

1592036000 XW60LH GB r1.0 18.03.2015 

XW60LH 

1/6 

Summary of Contents for Dixell XW60LH

Page 1: ...eduled by using a real time clock system depending on the hours set in the parameters Ld1 Ld6 during workdays and in Sd1 Sd6 during holidays Other parameters are used to control defrost cycles its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping ti...

Page 2: ...is displayed NOTE2 the set value is stored even when the procedure is exited by waiting the time out to expire 6 6 2 MOVE A PARAMETER FROM Pr2 TO Pr1 AND VICEVERSA Each parameter present in the Pr2 HIDDEN MENU can be moved to the Pr1 user level by pressing both SET DOWN keys When in Pr2 hidden menu if a parameter is visible in Pr1 then the decimal point will be on 6 7 MANUALLY LOCK AND UNLOCK THE ...

Page 3: ...Thermostat probe P2 Probe 2 evaporator probe P3 Probe 3 display probe P4 Fourth probe ALC Temperature alarms configuration Ab rE Ab absolute temperature alarm temperature is given by the ALL or ALU values rE temperature alarms are referred to the set point Temperature alarm is enabled when the temperature exceeds the SET ALU or SET ALL values ALU MAXIMUM temperature alarm If ALC Ab ALL to 150 0 C ...

Page 4: ...CTION HEATING COOLING i1F or i2F Htr This function allows to invert the regulation of the controller from cooling to heating and viceversa 8 8 ENERGY SAVING i1F or i2F ES The Energy Saving function allows to change the set point value as the result of the SET HES parameter sum This function is enabled until the digital input is activated 8 9 ON OFF FUNCTION i1F or i2F onF To switch the controller ...

Page 5: ... Kind of interval for defrost rtc in in Pr2 tdF Defrost type EL el heater in hot gas EL Pr1 dFP Probe selection for defrost termination nP P1 P2 P3 P4 P2 Pr2 dtE Defrost termination temperature 50 50 C 8 Pr1 IdF Interval between defrost cycles 1 120 ore 6 Pr1 MdF Maximum length for defrost 0 255 min 30 Pr1 dSd Start defrost delay 0 99min 0 Pr2 dFd Displaying during defrost rt it SEt DEF it Pr2 dAd...

Page 6: ... probe display Pr2 dP3 Third probe display Pr2 dP4 Fourth probe display Pr2 rSE Real set actual set Pr2 rEL Software release 1 8 Pr2 Ptb Map code Pr2 Only for model with real time clock 2 Only for XW60LH with X REP output 1592036000 XW60LH GB r1 0 18 03 2015 XW60LH 6 6 ...

Reviews: