Emerson Dixell XT130C Installing And Operating Instructions Download Page 3

 

 

1592002231 XT130-131C-D GB R.1.0 25.05.2015 

XT130C – XT131C - XT130D – XT131D 

3/4 

11.

 

HOW TO USE THE HOT KEY  

11.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When  the  controller  is  ON,  insert  the  “

Hot  key

”  and  push 

o

  key;  the   

"uPL" 

message 

appears followed a by flashing 

“End”

 

3.

 

Push “

SET”

 key and the 

End

 will stop flashing. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

then turn it ON again. 

 

NOTE

: the “

Err

” message is displayed for failed programming. In this case push again 

o

 key if 

you want to restart the upload again or remove the “

Hot key

” to abort the operation. 

11.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert a 

programmed “Hot Key” into the 5 PIN receptacle 

and then turn the Controller 

ON. 

3.

 

Automatically  the  parameter  list  of  the 

“Hot  Key”

  is  downloaded  into  the  Controller 

memory, the “

doL

” message is blinking followed a by flashing 

“End”.

 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the 

“Hot Key”.

 

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and 

then on if you want to restart the download again or remove the “

Hot key

” to abort the operation. 

12.

 

DIGITAL INPUT 

The controllers have 1  free contact digital input. It is programmable in 5 different configurations 
by the “

i1F

” parameter. 

12.1

 

REMOTE ON/OFF (I1F = OFF) 

This function allows to switch ON and OFF the instrument. 

12.2

 

GENERIC ALARM (I1F = EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before signalling the 

EAL

”  alarm  message.  The  outputs  status  don’t  change.  The  alarm  stops  just  after  the  digital 

input is de-activated. 

12.3

 

SERIOUS ALARM MODE (I1F = BAL) 

When  the  digital  input  is  activated,  the  unit  will  wait  for “

did

”  delay  before signalling  the  “

bAL

” 

alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the digital 
input is de-activated. 

12.4

 

ENERGY SAVING (I1F = HES) 

The Energy Saving function allows to change the set point value as the result of the SET+ HES 
(parameter) sum. This function is enabled until the digital input is activated. 

13.

 

ALARM SIGNALS 

Message  Cause 

Outputs 

“PFo” 

Probes broken or absence  

Alarm output ON; Output according to parameter “So1”  

“PFc” 

Probe short circuited 

Alarm output ON; Output according to parameter “So1”  

“HA” 

Maximum alarm 

Alarm output ON; Other outputs unchanged. 

“LA” 

Minimum alarm 

Alarm output ON; Other outputs unchanged. 

“EAL” 

External alarm 

Output unchanged. 

“bAL” 

Serious external alarm 

Output OFF. 

13.1

 

ALARM RELAY STATUS 

Status of the instrument 

XT131C 

XT131D 

 

AS = CL

 

AS= oP  

AS = CL

 

AS= oP  

Instrument off 

5-6 closed 

5-6 closed 

23-24 closed 

23-24 closed 

Normal operating 

5-6 closed 

5-6 open 

23-24 closed 

23-24 open 

Alarm present 

5-6 open 

5-6 closed 

23-24 open 

23-24 closed 

13.2

 

SILENCING BUZZER / ALARM RELAY OUTPUT 

Once the alarm signal is detected the buzzer, if present, can be disabled by pressing any key. 

XT131C/ XT131D

: the alarm relay status depends on the tbA parameter: with 

tbA=yES

 the relay 

is  disabled  by  pressing  any  key,  with 

tbA=no

  the  alarm  relay  remains  enabled  as  long  as  the 

alarm lasts.  The display signal remains as long as the alarm condition remains.  

13.3

 

ALARM RECOVERY  

Probe alarms “

PFo

”, “

PFc

” start few seconds after the fault in the probe; they automatically stop 

few  seconds after the  probe restarts normal  operation.  Check  connections before replacing the 
probe. 
Max. and min. alarms “

HA

” and “

LA

” automatically stop as soon as the variable returns to normal 

values. Alarms “

bAL

” and 

“EAL”

 recover as soon as the digital input is disabled. 

 
 
 
 
 
 
 
 

14.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case:

 

XT130C, XT131C 

frontal 32x74 mm; depth 60mm; 

 

XT130D, XT131D

: 4 DIN modules 70x85 mm; depth 61mm. 

Mounting:

  

XT130C, XT131C 

panel mounting in a 71x29 mm panel cut-out. 

 

XT130D, XT131D

: DIN RAIL 

Protection: 

IP20.

 

Frontal protection: XT110C, XT111C

 IP65 with frontal gasket RG-C (optional). 

Frontal protection:

 IP65 with frontal gasket RG-C (optional). 

Connections: 

Screw terminal block 

 2,5 mm

2

 heat-resistant wiring. 

Power supply: 

12Vac/dc, ±10% or: 24Vac/dc 

 10%  

or 230Vac 

 10%, 50/60Hz or 110Vac, 

 10%, 50/60Hz

 

Power absorption: 

3VA max. 

Display

:

 

3 ½ digits, red LED 

Inputs

: according to the order: NTC/PTC or NTC/PTC /Pt100 /Thermocouple J, K, S or 4÷20mA/ 

0÷1V / 0÷10V

 

Relay outputs:

 

Output1:

 relay 8(3)A, 250Vac 

Output2:

 relay 8(3)A, 250Vac 

Alarm: (XT131C / XT131D)

 relay 8(3)A, 250Vac

 

Kind of action: 

1B; 

Pollution grade: 

normal, 

Software class: 

A.

 

Other output: 

buzzer (optional); 

Data storing

: on the non-volatile memory (EEPROM). 

Operating temperature: 

0÷60 °C (32÷140°F); 

Storage temperature: 

-30÷85 °C  (-22÷185°F).  

Relative humidity:

 20

85% (no condensing) 

Measuring and regulation range:

 according to the probe 

Controller Accuracy a 25°C:

 better than 

0,5% of full scale 

15.

 

CONNECTIONS 

15.1

 

XT130C – 12V AC/DC OR 24V AC/DC 

1 2 3 4 5 6

11 12

7 8 9 10

Hot-KEY

8(3)A250V

8(3)A250V

Line

Input: 4÷20mA 

0÷1V / 0÷10V 

7 8 9 10

PTC / NTC

 

Probe: Pt100

= 7 – 9 (8); 

Thermocouple J, K, S

 = 7(+); 9(-) 

24Vac/cd supply: 

11-12 

15.2

 

XT130C – 230V AC OR 115V AC 

1 2 3 4 5 6 7 8

9 10 11 12

Hot-KEY

8(3)A250V

8(3)A250V

Line

Input 4÷20mA

0÷1V / 0÷10V 

9 10 11 12

PTC / NTC

 

Pt100

=9 –11 (10); 

Thermocouple J, K, S

 = 9(+) - 11(-) 

115Vac supply: 

7-8 

 

15.3

 

XT131C – 12VAC/DC OR 24VAC/DC 

1 2 3 4 5 6

11 12

7 8 9 10

Hot-KEY

8(3)A250V

8(3)A250V

8(3)A250V

Line

LOAD 1 LOAD 2 ALARM

Input: 4÷20mA 

0÷1V / 0÷10V 

7 8 9 10

PTC / NTC

 

 

Probe: Pt100

= 7 – 9 (8); 

Thermocouple J, K, S

 = 7(+); 9(-) 

24Vac/cd supply: 

11-12 

Summary of Contents for Dixell XT130C

Page 1: ...l with DEAD BAND Relay 1 output at inverse action heating humidifying increasing pressure load 1 CUT IN is SET db load 1 CUT OUT is when the process variable reaches the set point Relay 2 output at direct action cooling de humidifying decreasing pressure load 2 CUT IN is SET db load 2 CUT OUT is when the process variable reaches the set point 5 FRONT PANEL COMMANDS LED2 E S LED1 SET To display and...

Page 2: ...rE integer large scale 999 1999 only for current or voltage input WARNING if rES is changed from irE to another value all the parameters values expressed in degrees SET db LS1 uS1 ALL ALu ALH LCi uCi LAo uAo HES have to be checked and set NOTE the decimal point selection is not available on models with thermocouple input UdM Measurement unit it depends on models for temperature C Celsius F Fahrenh...

Page 3: ...C XT131D AS CL AS oP AS CL AS oP Instrument off 5 6 closed 5 6 closed 23 24 closed 23 24 closed Normal operating 5 6 closed 5 6 open 23 24 closed 23 24 open Alarm present 5 6 open 5 6 closed 23 24 open 23 24 closed 13 2 SILENCING BUZZER ALARM RELAY OUTPUT Once the alarm signal is detected the buzzer if present can be disabled by pressing any key XT131C XT131D the alarm relay status depends on the ...

Page 4: ... Full Scale 10 0 20 Pr2 ALH Alarm recovery differential 0 Full scale 2 0 4 Pr2 ALd Alarm delay 0 999 min 15 Pr2 dAO Alarm delay at start up 0 23h 50min 1 3 Pr2 So1 Output1 status with faulty pr oFF open on closed oFF Pr2 So2 Output2 status with faulty pr oFF open on closed oFF Pr2 tbA1 Alarm relay disabling no yES yES Pr2 AS1 Alarm relay polarity CL oP oP Pr2 Lci2 Start scale with current or volta...

Reviews: