Emerson Dixell XRB60CHC Installing And Operating Instructions Download Page 2

 

XRB60CHC EN r1.1 2018.11.01.docx 

                           XRB60CHC 

2/7 

 

7.

 

When 

Aid=1

, the first day will be used to analyze the temperature behavior and to build the 

model to apply to the second day. The model will be updated every day in order to better match 

the working conditions. 

8.

 

When 

Aid=7

, the first 7 days will be used to analyze the temperature behavior and to build the 

model to apply to the next 7 days. The model will be updated every 7 days in order to better 
match the working conditions. 

9.

 

When 

Aid=7

, the first 7 days after power on will use a sub analysis base on 1-day model. 

10.

 

nCE

 is used to define the minimum duration of an energy saving interval of time 

11.

 

nCC

 is used to move the SET-POINT value from normal mode value to the energy saving 

mode value by steps (1 step = 1°C or 1°F, starting from the 

SET

 value and increasing it every 

30 min till reaching the 

SET_ES

 value) 

12.

 

Pdt

 is used to anticipate the end of the energy saving mode in order to decrease the 

temperature of the bottles before starting the normal mode interval 

13.

 

PPU

 select the probe used for automatic energy saving algorithm 

14.

 

tun

 is used to change the sensibility of the automatic energy saving algorithm. 

tun=H

 (high) is 

used for cabinet with regulation probe installed near the evaporator air outlet flow. 

tun=L

 (low) 

is used for cabinet with regulation probe installed far away from the evaporator air outlet flow. 

5

 

EXTRA COOLING FUNCTION 

 

 
The extra cooling function (named Pull Down) is active when the room temperature measured from the probe 
1 goes over the 

SET+oHt+HY

 value. In this case, a special set-point value, lower than the normal 

SET

 value, 

will  be  enabled.  As  soon  as  the  room  temperature  reaches  the 

SET+CCS

  value,  the  compressor  will  be 

stopped and the normal regulation will restart. 

N.B.:

 pull down function is disabled when 

CCS=0

 or 

CCt=0

The 

CCt

 parameter sets the maximum activation time for any pull down. When 

CCt

 expires, the pull down will 

be immediately stopped and the standard SET-POINT will be restored. 

NOTE:

 in case of energy saving mode 

active, the used values will be: 

SET_ES=SET+HES, oHE 

and 

CCS.

 

6

 

EVAPORATOR FANS 

 

 

With 

FnC

 parameter it can be selected the fans functioning: 

 

FnC=C-n 

 fans will switch ON and OFF with the compressor and

 not run

 during defrost; when 

compressor  is  OFF,  fans  will  enter  a  duty-cycle  working  mode  (see 

FoF

Fon

FF1

  and 

Fo1

 

parameters). 

 

FnC=o-n 

 fans will run even if the compressor is off, and not run during defrost; 

 

FnC=C-Y 

 

fans  will  switch  ON  and  OFF  with  the  compressor  and 

run

  during  defrost;  when 

compressor  is  OFF  all  fans  will  enter  a  duty-cycle  working  mode  (see 

FoF

Fon

FF1

  and 

Fo1

 

parameters). 

 

FnC=o-Y

 

 

fans will run continuously also during defrost. 

 

After defrost, there is a timed fan delay allowing for drip time, set by means of the 

Fnd

 parameter. 

An  additional  parameter 

FSt

  provides  the  setting  of  temperature,  detected  by  the  evaporator  probe, 

above which the fans are always OFF. By using this parameter it is possible to assure air circulation 
only if air temperature is lower than 

FSt 

value. 

6.1

 

EVAPORATOR FAN AND DIGITAL INPUT 

When the digital input is configured as door switch (

i1F=dor

), fans and compressor status will depend on the 

odC

 parameter value:  

 

odC=no

 

 normal regulation 

 

odC=FAn

 

 evaporator fan OFF 

 

odC=CPr

 

 compressor OFF 

 

odC=F-C

 

 compressor and evaporator fan OFF 

 
When 

rrd=Y

 the regulation will restart after a door open alarm. 

7

 

DEFROST 

7.1

 

DEFROST MODE 

Any defrost operation can be controlled in the following way: 

-

 

EdF=rtC

: by using an internal real time clock (only for models equipped with RTC). 

-

 

EdF=in

: timed defrost, in this case a new defrost will start as soon as the idF timer elapses. 

-

 

EdF=Aut

: automatic management, in this case the controller will start a new defrost any time a 

change from normal to energy saving mode will occur (valid if 

ErA=Aut

). 

7.2

 

TIMED OR PROBE CONTROLLED MODE 

Two  defrost  modes  are  available

:  timed  or  controlled  by  the  evaporator’s  probe.

  A  couple  of 

parameters is used to control the interval between defrost cycles (

idF

) and its maximum length (

MdF

). 

During  the  defrost  cycle  is  possible  to  select  some  different  display  indications  by  using  the 

dFd 

parameter. These modes are available with any kind of defrost type: 

-

 

tdF=EL

: electric heater defrost 

-

 

tdF=in

: hot gas defrost. 

7.3

 

AUTOMATIC DURATION DETECTION 

When  a  defrost  operation  is  performed  by  compressor  stop  (means  by  stopping  the  compressor  and  by 
activating the internal ventilators), it will be possible to use an automatic defrost mode by setting 

od2=ALt

. In 

this case the device will use the evaporator probe (which MUST to be present and properly mounted on the 
evaporator surface)  to detect the end of the actual defrost  phase. In any case, a  maximum  period  of time 
(

MdF

) and an upper evaporator temperature value will be used to stop the current defrost phase.  If 

ErA=Aut

the automatic defrost mode will activate a defrost at the beginning of any energy saving mode period.  In this 
case the 

idF

 delay is used as safety function. It forces the controller to activate a defrost operation when 

idF

 

runs. 

NOTE:

 during the defrost phase the loads (compressor and evaporator fans) will be controlled from the 

defrost algorithm. 

8

 

INTERNAL COUNTERS 

The next table shows the implemented load and function of total counters. 
 

n1H 

Number of relay output 1 activation (thousands of) 

n1L 

Number of relay output 1 activation (hundreds of) 

n2H 

Number of relay output 2 activation (thousands of) 

n2L 

Number of relay output 2 activation (hundreds of) 

n3H 

Number of relay output 3 activation (thousands of) 

n3L 

Number of relay output 3 activation (hundreds of) 

n4H 

Number of relay output 4 activation (thousands of) 

n4L 

Number of relay output 4 activation (hundreds of) 

n5H 

Number of digital input 1 activation (thousands of) 

n5L 

Number of digital input 1 activation (hundreds of) 

n6H 

Number of digital input 2 activation (thousands of) 

n6L 

Number of digital input 2 activation (hundreds of) 

oCH 

Compressor working hours (thousands of) 

oCL 

Compressor working hours (hundreds of) 

 
In this way it is possible to monitor the application and discovering bad functioning that could lead to damages. 
They are updated in EEPROM every hour. It is not possible to reset them. 
NOTE: the compressor activation counters take into account also defrost in case of inversion (hot gas) mode. 

8.1

 

AUX RELAY CONFIGURATION (PAR. oAX) 

An  auxiliary  relay  can  be  set  by  the 

oAx 

parameters,  according  to  the  kind  of  application.  In  the 

following paragraph the possible settings. 

8.1.1

 

Light relay 

With 

oAx=LiG

 the AUX relay operates as light output. 

8.1.2

 

Auxiliary relay 

a.

 

Relay  activation  by  digital  input  1  or  digital  input  2  (oAx=AUS,  i1F  or  i2F=AUS): 

with 

oAx=AUS

 and 

i1F, i2F=AUS

 the AUX relay is switched on and off by digital inputs.

 

b.

 

Auxiliary thermostat:

 anti condensing heater with the possibility of switching it on and off also 

by using the frontal keyboard.

 

Parameters involved:  

-

 

ACH:

 kind of regulation for the auxiliary relay: 

Ht 

= heating; 

CL 

=

 

cooling.

 

-

 

SAA: 

set point for auxiliary relay.

 

-

 

SHy: 

differential for auxiliary relay.

 

-

 

ArP: 

probe for auxiliary relay.

 

-

 

Sdd: 

auxiliary output off during defrost.

 

-

 

Ao1:

 output active when in energy saving mode

 

-

 

AF1:

 output not active when in energy saving mode

 

 

The differential threshold value is set by the 

SHY 

parameter.

 

 

NOTE:  

if

 oAx=AUS 

and 

ArP=nP 

(no probe for auxiliary output) the AUX relay can be activated  

-

 

by digital input if 

i1F=AUS

 or 

i2F=AUS 

-

 

by auxiliary button (if set as 

AUS

-

 

by serial command (Modbus protocol) 

-

 

by fixed interval of time if 

Ao1>0

 and 

AF1>0

 (if 

Ao1=0

 or 

AF1=0

 the auxiliary output is 

disabled) 

 

8.1.3

 

On/off relay (oAx = onF) 

When 

oAx=onF

, the  AUX  relay  is  activated  when  the  controller  is  turned  on  and de-activated  when 

the controller is turned off. 

8.1.4

 

Neutral zone regulation 

With 

oAx=db

 the AUX relay can control a heater element to perform a neutral zone action. 

 

oA1

 cut in = 

SET-HY

 

 

oA1

 cut out = 

SET

  

Summary of Contents for Dixell XRB60CHC

Page 1: ...e standard SET POINT SET is used to maintain the temperature at a certain value when the energy saving status ES is not active On the other side when the ES status is active a different SET POINT SET_ES higher than the standard one will be used The parameter HES will have to be set to change the regulation temperature according to the following formula SET_ES SET HES There are also two different d...

Page 2: ... OR PROBE CONTROLLED MODE Two defrost modes are available timed or controlled by the evaporator s probe A couple of parameters is used to control the interval between defrost cycles idF and its maximum length MdF During the defrost cycle is possible to select some different display indications by using the dFd parameter These modes are available with any kind of defrost type tdF EL electric heater...

Page 3: ...Press SET UP or wait for 15 sec without pressing any key NOTE1 if there are no parameters in L1 after 3 sec the nP label will be displayed Keep the keys pushed till the L2 message will be displayed NOTE2 the previous set value will be stored even if the programming mode is exited by waiting for the time out to expire MOVE PARAMETERS FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA Each parame...

Page 4: ...P4 nP no probe the auxiliary relay is switched only by the digital input P1 Probe 1 Thermostat probe P2 Probe 2 evaporator probe P3 do not use it P4 Probe 4 Sdd Auxiliary relay switched off during defrost n Y n the auxiliary relay operates during defrost Y the auxiliary relay is switched off during defrost btA Base Time for timed activation of auxiliary output SEC Min SEC base time is in second At...

Page 5: ... the right of the appliance card present on the Permissions webpage OTHER Adr Serial address for Modbus communication 1 to 247 bAU Baudrate 9 6 19 2 38 4 57 6 select the correct baudrate for serial communication wired LGC Light button configuration nu not used ES change working mode from normal to energy saving mode and vice versa LiG light output control AUS auxiliary output control dEF defrost c...

Page 6: ...ections Screw terminal block 2 5 mm2 wiring Power supply according to the model 230Vac 10 50 60Hz 110Vac 10 50 60Hz Power absorption 3 5VA max Display 3 digits red LED 14 2 mm high Inputs up to 4 NTC probes Digital input free voltage contact Relay outputs Compressor SPST 16 5 A or 20 8 A 250VAC Light SPDT 5 2 A 250VAC Fans SPST 8 3 A 250VAC Data storing 8 Kbytes EEPROM Kind of action 1B Pollution ...

Page 7: ...is compliant with the following standards FCC 15 247 The XRB60CHC is compliant to Part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation This device has been designed and complies with the safety requirements for p...

Reviews: