XR40C – XR40D 

2/4 

6.  MAIN FUNCTIONS 

6.1  HOW TO SEE THE SETPOINT 

 

1.  Push and immediately release the 

SET 

key: the display will 

show the Set point value; 

2.  Push  and  immediately  release  the 

SET 

key  or  wait  for  5  seconds  to  display 

the probe value again. 

6.2  HOW TO CHANGE THE SETPOINT 

1.  Push the 

SET 

key for more than 2 seconds to change the Set point value; 

2.  The value of the set point will be displayed and the 

 LED starts blinking; 

3.  To change the Set value push the 

or 

n

 arrows within 10s. 

4.  To memorise the new set point value push the 

SET

 key again or wait 10s. 

6.3  HOW TO START A MANUAL DEFROST 

 

Push  the 

DEF 

key  for  more  than  2  seconds  and  a  manual 

defrost will start. 

6.4  HOW TO CHANGE A PARAMETER VALUE 

To change the parameter’s value operate as follows: 

 

1.  Enter  the  Programming  mode  by  pressing  the  Set  and 

DOWN key for 3s (

 and 

 start blinking). 

2.  Select the required parameter. 
3. 

Press the “

SET

” key to display its value (now only the 

 

LED is blinking). 

4. 

Use “

UP

” or “

DOWN

” to change its value. 

5. 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

:  the  set  value  is  stored  even  when  the  procedure  is  exited  by  waiting  the 

time-out to expire. 

6.5  THE HIDDEN MENU 

The hidden menu Includes all the parameters of the instrument. 

6.5.1  HOW TO ENTER THE HIDDEN MENU 

 

1.  Enter  the  Programming  mode  by  pressing  the  Set  + 

n

 

key for 3s (LED 1 and 

 start blinking). 

2.  When a parameter is displayed keep pressed the Set+

n

  

for  more  than  7s.  The  Pr2  label  will  be  displayed 
immediately followed from the HY parameter.  

NOW YOU ARE IN THE HIDDEN MENU. 

3.  Select the required parameter. 
4. 

Press the “

SET

” key to display its value (Now only the 

 LED is blinking). 

5.  Use 

or 

n

 to change its value. 

6. 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + 

or wait 15s without pressing a key. 

NOTE

:  the  set  value  is  stored  even  when  the  procedure  is  exited  by  waiting  the 

time-out to expire. 
 

6.5.2  HOW  TO  MOVE  A  PARAMETER  FROM  THE  HIDDEN  MENU  TO  THE 
FIRST LEVEL AND VICEVERSA. 

Each parameter present in the HIDDEN MENU can be removed or put 

into “THE 

FIRST LEVEL” (user level) by pressing 

“SET + 

n

.  

In HIDDEN MENU when a parameter is present in First Level the decimal point is 
on. 

6.6  HOW TO LOCK THE KEYBOARD 

 

1. 

 

Keep pressed for more than 3 s the 

and 

n

 keys. 

2. 

 

The “

POF

” message will be displayed and the keyboard will be locked. At this 

point it will be possible only to see the set point or the MAX o Min temperature 
stored 

3. 

 

If a key is pressed more than 3s the “POF” message will be displayed. 

6.7  TO UNLOCK THE KEYBOARD 

Keep  pressed  together  for  more  than  3s  the 

and 

n

  keys,  till  the 

“Pon” 

message will be displayed. 

6.8  THE CONTINUOUS CYCLE 

 

When  defrost  is  not  in  progress,  it  can  be  activated  by 
holding the “

o

” key pressed for about 3 seconds. 

The  compressor operates in continuous mode for the time set through the “

CCt

” 

parameter.  The  cycle  can  be terminated before the end of the set time using the 
same activation key “

o

” for 3 seconds. 

 
 
 
 
 
 

7.  PARAMETERS 

NOTE: the parameters preceded by  dots are in the Hidden Menu. 

 

REGULATION 

Hy  Differential

:  (0,1  ÷  25,5°C  /  1÷255  °F)  Intervention  differential  for  set  point. 

Compressor  Cut  IN  is  Set Point Plus Differential (Hy). Compressor Cut OUT 
is when the temperature reaches the set point. 

 

LS    Minimum  set  point

:  (-  50°C÷SET/-58°F÷SET):  Sets  the  minimum 

acceptable value for the set point. 

 

US  Maximum  set  point

:  (SET÷110°C/  SET÷230°F).  Set  the  maximum 

acceptable value for set point. 

Ot  Thermostat probe calibration

: (-12.0÷12.0°C; 

-120÷120°F) allows to adjust possible offset of the thermostat probe. 

P2P Evaporator  probe  presence:  n

=  not  present:  the  defrost  stops  by  time; 

y=

 

present: the defrost stops by temperature. 

 

OE  Evaporator  probe  calibration

:  (-12.0÷12.0°C;  -120÷120°F).  allows  to 

adjust possible offset of the evaporator probe. 

 

OdS   Outputs  activation  delay  at  start  up: 

(0÷255min)  This  function  is 

enabled  at  the  initial  start  up  of  the  instrument  and  inhibits  any  output 
activation for the period of time set in the parameter. 

 

AC    Anti-short  cycle  delay

:  (0÷50  min)  minimum  interval  between  the 

compressor stop and the following restart. 

 

CCt  Compressor  ON  time  during  continuous    cycle

:  (0.0÷24.0h;  res. 

10min) Allows to set the length of the continuous cycle: compressor stays on 
without  interruption  for  the  CCt  time.  Can  be  used,  for  instance,  when  the 
room is filled with new products. 

 

COn  Compressor  ON  time  with  faulty  probe

:  (0÷255  min)  time  during 

which  the  compressor  is  active  in  case  of  faulty  thermostat  probe.  With 
COn=0 compressor is always OFF. 

 

COF  Compressor  OFF  time  with  faulty  probe

:  (0÷255  min)  time  during 

which the compressor is OFF in case of faulty thermostat probe. With COF=0 

compressor is always active. 

DISPLAY 

 

CF Temperature measurement unit

 

°C

=Celsius; 

°F

=Fahrenheit. 

WARNING

:  When  the  measurement  unit  is 

changed  the  SET  point  and  the  values    of  the  parameters  Hy,  LS,  US,  Ot, 
ALU and ALL have to be checked and modified if necessary). 

rES Resolution (for °C)

: (in = 1°C; dE = 0.1 °C) allows decimal point display. 

 

Lod  Display  : 

select  which  probe  is  displayed  by  the  instrument:

  P1

  = 

Thermostat probe; 

P2

 = Evaporator probe 

DEFROST 

tdF  Defrost type

: EL = electrical heater; in = hot gas 

dtE  Defrost termination temperature

: (-50÷50 °C/  

-58÷122°F) (Enabled only when EdF=Pb) sets the temperature measured by 
the evaporator probe, which causes the end of defrost. 

IdF  Interval  between  defrost  cycles

:  (0÷120h)  Determines  the  time  interval 

between the beginning of two defrost cycles. 

MdF  (Maximum) length for defrost

: (0÷255min) When 

P2P = n

, (not evaporator 

probe: timed defrost) it sets the defrost duration, when 

P2P = y

 (defrost end 

based on temperature) it sets the maximum length for defrost. 

 

dSd Start defrost delay

: ( 0÷99min) This is useful when different defrost start 

times are necessary to avoid overloading the plant.  

 

dFd    Temperature  displayed  during  defrost

:  (

rt

  =  real  temperature; 

it

  = 

temperature at defrost start; 

SEt

 = set point; 

dEF

 

= “dEF” label) 

 

dAd MAX display delay after defrost

: (0÷255min). Sets the maximum time 

between  the  end  of  defrost  and  the  restarting  of  the  real  room  temperature 
display. 

 

Fdt 

Drip  time

:  (0

120  min)  time  interval  between  reaching  defrost 

termination  temperature  and  the  restoring  of  the  control’s  normal  operation. 
This  time  allows  the  evaporator  to  eliminate  water  drops  that  might  have 
formed due to defrost. 

 

dPo  First defrost after start-up

: y = immediately; n = after the IdF time 

 

dAF  Defrost  delay  after  continuous  cycle

:  (0

23.5h)  time  interval 

between the end of the fast freezing cycle and the following defrost related to 
it. 

ALARMS 

 

ALC  Temperature alarms configuration

: (Ab; rE) 

 

Ab

=  absolute  temperature:  alarm  temperature  is  given  by  the  ALL  or  ALU 

values.   

rE

  =  temperature  alarms  are  referred  to  the  set  point.  Temperature  alarm  is 

enabled when the temperature exceeds the “SET+ALU” or “SET-ALL” values. 

ALU  MAXIMUM  temperature  alarm

:  (SET÷110°C;  SET÷230°F)  when  this 

temperature is reached  the alarm is enabled, after the “ALd” delay time. 

ALL Minimum temperature alarm

: (-50.0 ÷ SET°C;  

-58÷230°F when this temperature is reached  the alarm is enabled, after the 
“ALd” delay time. 

 

ALd    Temperature  alarm  delay

:  (0÷255  min)  time  interval  between  the 

detection of an alarm condition and alarm signalling. 

 

dAO  Exclusion  of  temperature  alarm  at  startup

:  (from  0.0  min  to  23.5h) 

time  interval  between  the  detection  of  the  temperature  alarm  condition  after 
instrument power on and alarm signalling. 

DIGITAL INPUT (IF AVAILABLE) 

i1P  Digital  input  polarity:  oP: 

the  digital  input  is  activated  by  opening  the 

contact; 

CL: 

the digital input is activated by closing the contact.

 

i1F Digital input configuration:  

EAL 

= external alarm: “EA” message is displayed; 

bAL 

= serious alarm “CA” 

message  is  displayed. 

PAL 

=  pressure  switch  alarm,  “CA”  message  is 

displayed; 

dor

 = door switch function; 

dEF

 = activation of a defrost cycle; 

LHt 

=not enabled; 

Htr 

= kind of action inversion (cooling 

– heating).

 

did

:

 

(0

255  min) 

with

 

i1F=  EAL  or  i1F  =  bAL  digital  input  alarm  delay:

  delay 

between the detection of the external alarm condition and its signalling. 

Summary of Contents for Dixell XR40D

Page 1: ... defrost termination temperature The instrument is fully configurable through special parameters that can be easily programmed through the keyboard 3 CONTROLLING LOADS 3 1 COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temperature increases and reaches set point plus differential the compre...

Page 2: ...rt up 0 255min This function is enabled at the initial start up of the instrument and inhibits any output activation for the period of time set in the parameter AC Anti short cycle delay 0 50 min minimum interval between the compressor stop and the following restart CCt Compressor ON time during continuous cycle 0 0 24 0h res 10min Allows to set the length of the continuous cycle compressor stays ...

Page 3: ...rminal block to connect cables with a cross section up to 2 5 mm2 Before connecting cables make sure the power supply complies with the instrument s requirements Separate the probe cables from the power supply cables from the outputs and the power connections Do not exceed the maximum current allowed on each relay in case of heavier loads use a suitable external relay 10 1 PROBE CONNECTION The pro...

Page 4: ... 50 58 US Maximum set point SET 110 C SET 230 F 110 230 Ot Thermostat probe calibration 12 12 C 120 120 F 0 P2P Evaporator probe presence n not present Y pres y OE Evaporator probe calibration 12 12 C 120 120 F 0 OdS Outputs delay at start up 0 255 min 0 AC Anti short cycle delay 0 50 min 1 CCt Continuos cycle duration 0 0 24 0h 0 0 COn Compressor ON time with faulty probe 0 255 min 15 COF Compres...

Reviews: