1592007231 XR40C-D GB r1.0 18.11.2015 

XR40C – XR40D 

1/4 

Digital controller with defrost management

 

XR40C 

– XR40D

 

CONTENTS 

1.

 

GENERAL WARNING  __________________________________________ 1

 

2.

 

GENERAL DESCRIPTION _______________________________________ 1

 

3.

 

CONTROLLING LOADS  ________________________________________ 1

 

4.

 

FRONT PANEL COMMANDS  ____________________________________ 1

 

5.

 

TEMPERATURE ALARM AND ITS DURATION RECORDING (HACCP) ___ 1

 

6.

 

MAIN FUNCTIONS _____________________________________________ 2

 

7.

 

PARAMETERS ________________________________________________ 2

 

8.

 

DIGITAL INPUT (IF AVAILABLE) __________________________________ 3

 

9.

 

INSTALLATION AND MOUNTING _________________________________ 3

 

10.

 

ELECTRICAL CONNECTIONS  ___________________________________ 3

 

11.

 

HOW TO USE THE HOT KEY ____________________________________ 3

 

12.

 

ALARM SIGNALS ______________________________________________ 3

 

13.

 

TECHNICAL DATA _____________________________________________ 3

 

14.

 

CONNECTIONS _______________________________________________ 4

 

15.

 

DEFAULT SETTING VALUES ____________________________________ 4

 

1.  GENERAL WARNING 

1.1  PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for 
easy and quick reference. 

 

The instrument shall not be used for purposes different from those described 
hereunder. It cannot be used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell  Srl  reserves  the  right  to  change  the  composition  of  its  products,  even 
without notice, ensuring the same and unchanged functionality. 

1.2 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not  expose  to  water  or  moisture:  use  the  controller  only  within  the 
operating limits avoiding sudden temperature changes with high atmospheric 
humidity to prevent  formation of condensation 

 

Warning:  disconnect  all  electrical  connections  before  any  kind  of 
maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must 
not be opened. 

 

In  case  of  failure  or  faulty  operation  send  the  instrument  back  to  the 
distributor or to “Dixell S.r.l.” (see address) with a detailed description of the 
fault. 

 

Consider  the  maximum  current  which  can  be  applied  to  each  relay  (see 
Technical Data). 

 

Ensure  that  the  wires  for  probes,  loads  and  the  power  supply  are  separated 
and far enough from each other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our 
mod. FT1) in parallel with inductive loads could be useful. 

2.  GENERAL DESCRIPTION 

Models 

XR40C

,  format  32  x  74  mm,  and 

XR40D

,  DIN  rail  format,  are  

microprocessor  based  controllers,  suitable  for  applications  on  medium  or  low 
temperature  refrigerating  units.  They  have  2  relay  outputs  to  control  compressor 
and  defrost,  which  can  be  either  electrical  or  reverse  cycle  (hot  gas).  It  is  also 
provided  with  two  NTC  or  PTC  probe  inputs,  one  for  temperature  control,  the 
other,  to  be  located  onto  the  evaporator,  to  control  the  defrost  termination 
temperature.  The  instrument  is  fully configurable through special parameters that 
can be easily programmed through the keyboard. 

3.  CONTROLLING LOADS 

3.1  COMPRESSOR 

The  regulation  is  performed  according  to  the  temperature  measured  by  the 
thermostat  probe  with  a  positive  differential  from  the  set  point:  if  the temperature 
increases  and  reaches  set  point  plus  differential  the  compressor  is  started  and 
then turned off when the temperature reaches the set point value again. 

 

In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor are 
timed through parameters “

COn

” and “

COF

”. 

3.2  DEFROST 

Two  defrost  modes  are  available  through  the  “

tdF

”  parameter:  defrost  through 

electrical heater (

tdF = EL

) and hot gas  defrost (

tdF = in

). Other parameters are 

used  to  control  the  interval  between  defrost  cycles  (IdF),  its  maximum  length 
(MdF) and two defrost modes: timed or controlled by the evaporator’s probe (P2P).  
At the end of defrost dripping time is started, its length is set in the FSt parameter. 
With FSt =0 the dripping time is disabled. 
 

4.  FRONT PANEL COMMANDS 

 

XR40C 

 

 

XR40D 

 

 

SET

: To display target set point; in programming mode it  selects a parameter  or 

confirm an operation. 

  (DEF) 

To start a manual defrost

 

o

  (

UP)

:  To  see  the  last  temperature  alarm  happened;  in  programming  mode  it 

browses the parameter codes or increases the displayed value. 

n

 (

DOWN

) To see the last temperature alarm happened ;in programming mode it 

browses the parameter codes or decreases the displayed value. 

KEY COMBINATIONS: 

n



To lock & unlock the keyboard

.

 

SET +

 

n

  To enter in programming mode. 

SET + 

o  

To return to the room temperature display. 

4.1  USE OF LEDS 

Each LED function is described in the following table. 

LED  MODE 

FUNCTION 

 

ON 

Compressor enabled 

 

Flashin

-Programming Phase (flashing with 

- Anti-short cycle delay enabled 

 

ON 

Defrost enabled 

 

Flashin

- Programming Phase (flashing with 

- Drip time in progress 

 

ON 

An temperature alarm happened 

5.  TEMPERATURE ALARM AND ITS DURATION 
RECORDING (HACCP) 

XR40C  signals  and  records  temperature  alarms,  together  with  their  duration  and 
max value reached. See drawing: 

 
Ex. High temperature alarm 

Set

ALu

High temp. alarm

Time

Temperature

ALL

Low temp. alarm

X

X

X

Alarm duration

Max

Temperature

Safe food zone

 

5.1  HOW TO SEE THE ALARM DURATION AND MAX (MIN) 
TEMPERATURE  

If the alarm LED is on, an alarm has taken place.  
To see the kind of alarm, the max (min) reached temperature and alarm duration 
do as follows: 
1. 

Push the Up or Down key. 

2. 

On the display the following message is shown:: 

HAL

”  for  high  temperature  alarm  (“

LAL

”  fot  the  minimum  allarm),  followed 

by the 

Maximum (minimum) temperature. 

Then  the  “

tiM

”  (

tiM

e)  message  is  displayed,  followed  by  the 

“Duration” 

in 

h.mm. 

3. 

Then the instrument displays the temperature once again. 

 

NOTE1: 

if an alarm is still occurring the “

tim

” shows the partial duration. 

NOTE2:

 the alarm is recorded when the temperature come back to normal values 

5.2  HOW TO RESET A RECORDED ALARM OR ONE THAT IS 
STILL OCCURRING 

1.  Hold  the  SET  key  pressed  for  more  than  3s,  while  the  recorded  alarm  is 

displayed. (the rSt message will be displayed) 

2. 

To  confirm  the  operation,  the  “rSt”  message  starts  blinking  and  the  normal 
temperature will be displayed. 

Summary of Contents for Dixell XR40D

Page 1: ... defrost termination temperature The instrument is fully configurable through special parameters that can be easily programmed through the keyboard 3 CONTROLLING LOADS 3 1 COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temperature increases and reaches set point plus differential the compre...

Page 2: ...rt up 0 255min This function is enabled at the initial start up of the instrument and inhibits any output activation for the period of time set in the parameter AC Anti short cycle delay 0 50 min minimum interval between the compressor stop and the following restart CCt Compressor ON time during continuous cycle 0 0 24 0h res 10min Allows to set the length of the continuous cycle compressor stays ...

Page 3: ...rminal block to connect cables with a cross section up to 2 5 mm2 Before connecting cables make sure the power supply complies with the instrument s requirements Separate the probe cables from the power supply cables from the outputs and the power connections Do not exceed the maximum current allowed on each relay in case of heavier loads use a suitable external relay 10 1 PROBE CONNECTION The pro...

Page 4: ... 50 58 US Maximum set point SET 110 C SET 230 F 110 230 Ot Thermostat probe calibration 12 12 C 120 120 F 0 P2P Evaporator probe presence n not present Y pres y OE Evaporator probe calibration 12 12 C 120 120 F 0 OdS Outputs delay at start up 0 255 min 0 AC Anti short cycle delay 0 50 min 1 CCt Continuos cycle duration 0 0 24 0h 0 0 COn Compressor ON time with faulty probe 0 255 min 15 COF Compres...