E2 Setup of Devices
ECT MODBUS Networking to E2s • 25
ter a new name for each device in the
Name
field.
6. By default, each device in the network list has a
board number of 0. To set the address and begin
communication, choose the device and press
. In the list of MODBUS devices, choose the
address number corresponding to the XR35CX ad-
dress set up through the XR35CX front display, and
press
to select it. A window will open where
you can specify the address of the controller. If a
network ID has already been selected, its name will
be shown next to the network ID in this list. If the
network ID you are trying to assign has already
been used, you must set the address on this device
to a different number that is not being used.
7. Repeat
Steps 5
and
6
until each device has a name
and address.
8. When finished, press
to return to the
Net-
work Setup
menu, then press
-
Network Sum-
mary
). Locate the devices you set up,
and look at each device’s status in the
Status
field.
You will see one of the following messages:
•
Online
- The device is communicating normally.
•
Offline
- The device is not communicating, has not
been commissioned, is not functional, or is not pow-
ered up. Verify the device is powered up, wired cor-
rectly, and has the proper network address, baud
rate, and parity.
•
Unknown
- The device is not communicating or has
not been commissioned. Verify the device is pow-
ered up, wired correctly, and has the proper network
address, baud rate, and parity.
•
No Port
- No port is set up in the E2 Serial Config-
uration Manager to be a MODBUS port.
•
Wrong FW Rev
- This message is likely caused by
the device having a firmware version older than the
minimum revision required by E2 for communica-
tion. Replace the device with a new one or a device
that has the latest version of firmware on it.