Emerson Dixell XEV20D Quick Reference Manual Download Page 1

 

1592025980 XEV20D GB r.2.7 31.07.2019 

XEV20D 

          1/5 

 

QUICK REFERENCE GUIDE 

XEV20D

 

- FW REL. 2.5 -

 

CONTENTS 

CONTENTS ____________________________________________________________________________ 1

 

1.

 

GENERAL RECOMMENDATIONS ______________________________________________________ 1

 

2.

 

COMPATIBILITY OF USE _____________________________________________________________ 1

 

3.

 

GENERAL RULES  __________________________________________________________________ 2

 

4.

 

INSTALLATION AND MAINTENANCE ___________________________________________________ 2

 

5.

 

MAXIMUM POWERS ALLOWED _______________________________________________________ 3

 

6.

 

SPECIFICATIONS  __________________________________________________________________ 3

 

7.

 

WIRING DIAGRAMS _________________________________________________________________ 3

 

8.

 

CONNECTION TO XEC SUPERCAP ____________________________________________________ 4

 

9.

 

SERIAL -- CAN BUS LINE  ____________________________________________________________ 5

 

10.

 

MEANING OF THE LED LIGHTS _______________________________________________________ 5

 

 

1.

 

GENERAL RECOMMENDATIONS  

 Please read before using this manual any further. 

 

This  manual  is  an  integral  part  of  the  product  and  must  be  kept  close  to  the 
device for quick and easy consultation. 

 

The regulator must not be used for purposes other than those described below, 
and it especially cannot be used as a safety device. 

 

Check application limits before proceeding. 

 

Dixell  S.r.l.  reserves  the  right  to  change  the  composition  of  its  products,  even 
without notice, ensuring the same and unchanged functionality. 

 

1.1    SAFETY PRECAUTIONS 

 

Symbol   

   warns the  user about  the presence of  non-insulated "dangerous 

voltage" inside the product area, which may cause electric shock. 

 

Symbol     

      warns  the  user  about  the  presence  of  important  operating  and 

maintenance  (assistance)  instructions  found  in  the  documentation  attached  to  the 
device. 

 

Dixell Srl reserves the right to vary the composition of its products without prior notice 
to the customer, ensuring the identical and unchanged features of the same. 

 

This manual is part of the product and must always be kept near the device for easy 
and quick reference. The device cannot be used as a safety device. Verify the limits 
of application before using the device. 

 

Verify that  the power supply voltage is correct before connecting the device. Do  not 
expose  it  to  water  or  humidity.  Use  the  controller  only  within  the  operating  limits, 
avoiding  sudden  temperature  changes  and  high  atmospheric  humidity,  which  may 
result in the formation of condensate.  

 

Warning:  disconnect  all  the  electric  connections  before  performing  maintenance. 
Insert the probe where it cannot be reached by the End User. The device must not be 
opened. Consider the maximum current that can be applied to each relay.  

 

Make sure that the wires for the probes, the loads and the electrical power supply are 
separated  and  sufficiently  distant  from  each  other,  without  crossing  or  intertwining 
with  each  other.  In  the  case  of  applications  in  industrial  environments,  it  may  be 
useful to use the main filters in parallel with the inductive loads. 

 

The customer shall bear full responsibility and risk for product configuration in order to 
achieve the results pertaining to installation and/or final equipment/system. Upon the 
customer's  request  and  following  a  specific  agreement,  Dixell  S.r.l.  may  be  present 
during  the  start-up  of  the  final  machine/application,  as  a  consultant,  however,  under 
no  circumstances  can  the  company  be  held  responsible  for  the  correct  operation  of 
the final equipment/system. 

 

Since 

Dixell 

products 

form 

part 

of 

high 

level 

of 

technology, 

qualification/configuration/programming/commissioning stage is required to use them 
as best as possible. Otherwise, these products may malfunction and Dixell cannot be 
held  responsible.  The  product  must  not  be  used  in  any  way  that  differs  from  that 
stipulated in the documentation. 

 

The  device  must  always  be  inserted  inside  an  electrical  panel  that  can  only  be 
accessed  by  authorized  personnel.  For  safety  purposes,  the  keyboard  must  be  the 
only part that can be reached. 

 

The device must never be hand-held while being used. 

 

It is good practice to bear the following in mind for all Dixell products: 

o

 

Prevent  the  electronic  circuits  from  getting  wet  as  contact  made  with  water, 
humidity  or  any  other  type  of  liquid  can  damage  them.  Comply  with  the 
temperature  and  humidity  limits  specified  in  the  manual  in  order  to  store  the 
product correctly. 

o

 

The  device  must  not  be  installed  in  particularly  hot  environments  as  high 
temperatures  can  damage  it  (electronic  circuits  and/or  plastic  components 
forming  part  of  the  casing).  Comply  with  the  temperature  and  humidity  limits 
specified in the manual in order to store the product correctly. 

o

 

Under no circumstances is the device to be opened - the user does not require 
the  internal  components.  Please  contact  qualified  service  personnel  for  any 
assistance. 

o

 

Prevent the device from being dropped, knocked or shaken as either can cause 
irreparable damage. 

o

 

Do  not  clean  the  device  with  corrosive  chemical  products,  solvents  or 
aggressive detergents. 

o

 

The device must not be used in applications that differ from that specified in the 
following material. 

 

 

Separate the power supply of the device from the rest of the electrical 
devices connected inside the electrical panel. The secondary circuit of 
the transformer must never be connected to the earth. 

 

1.2  PRODUCT DISPOSAL (WEEE) 

With  reference  to  Directive  2002/96/EC  of  the  European  Parliament  and  of  the 
Council of 27 January 2003 and to the relative national legislation, please note that: 

 

There  lies  the  obligation  not  to  dispose  of  electrical  and  electronic  waste  as 
municipal waste but to separate the waste. 

 

Public or private collection points must be used for disposal, in accordance with 
local  laws.  Furthermore,  at  the  end  of  the  product's  life,  it  is  also  possible  to 
return this to the retailer when a new purchase is made. 

 

This equipment may  contain hazardous substances.  Improper use or incorrect 
disposal can have adverse effects on human health and the environment. 

 

The  symbol  shown  on  the  product  or  the  package  indicates  that  the  product 
was placed on the market after 13th August 2005 and must be disposed of as 
separated waste. 

 

Should  the  product  be  disposed  of  incorrectly,  sanctions  may  be  applied  as 
stipulated in applicable local regulations regarding waste disposal. 

2.

 

COMPATIBILITY OF USE 

2.1  MAIN FEATURES 

XEV20D

 is a 

bipolar

 or 

unipolar

 motorized driver (Stepper) for electronic expansion 

valves.  This  driver  is  developed  for  use  in  combination  with  the 

ISaGRAF®

 

environment and programmable devices in the 

iPRO series.

  

 
The main features are: 

 

controlling one or two electronic expansion valves: 

 

compatibility with various valve models 

 

compatibility with various types of refrigerant 

 

manual adjustment (PID) or self-adaptive overheating 

 

4 analogue inputs  

 

Can Bus for ipro connection 

 

 

In case of 2 expansion valves they MUST HAVE the same STEP 
RATE. 

 

2.2  CONNECTIONS / INSTALLATION 

The devices must not be installed in environments where the following situations are 
present: 

 

Temperature and humidity out of the range stipulated in the instrument 
label. Frequent and sudden changes in temperature and/or humidity. 

 

Direct sunlight and weathering in general 

 

High mechanical stress (vibrations and/or impact) 

 

Sulphur and ammonia gas, smoke and salt spray that can cause 
corrosion and/or oxidation 

 

Presence of flammable or explosive gas 

 

Dust 

 

Devices that generate electromagnetic interference 

 
Place the device inside the electrical panels, paying attention to the following: 

 

the distance between the device and the electrical power components 

 

the distance between the device and the power cables 

 

sufficient space for the cooling air 

 
Always  comply  with  the  laws  and  regulations  applicable  in  the  country  where  the 
device is installed. 
Always  protect  the  device  for  it  to  always  be  accessible  solely  by  authorized 
personnel. 
In  case  of  malfunctions,  always  contact  the  relative  distributor  for  the  device  to  be 
repaired. 

Summary of Contents for Dixell XEV20D

Page 1: ...nserted inside an electrical panel that can only be accessed by authorized personnel For safety purposes the keyboard must be the only part that can be reached The device must never be hand held while being used It is good practice to bear the following in mind for all Dixell products o Prevent the electronic circuits from getting wet as contact made with water humidity or any other type of liquid...

Page 2: ...e iPro tells the driver a new value for one of the aforementioned parameters the driver itself proceeds with the complete closure of the valve The XEV20D drivers issued by Dixell are tested but not configured this means that the parameters in the flash memory are set to a default value specifically the valve type parameter 0 4 1 VALVES CONNECTIONS TABLE Read carefully the table below to learn how ...

Page 3: ...0 mA input resistance 100Ω Precision at 25 C NTC PTC PT1000 1 C 0 5V 100mV 4 20mA 0 30mA Measurement and adjustment field 50 C 110 C 58 F 230 F NTC probe 50 C 150 C 32 F 302 F PTC probe 50 C 100 C 32 F 212 F PT1000 probe 0 bar 50 bar 0 psi 302 psi pressure probe Resolution 0 1 C 1 F 0 1 bar 6 2 DIGITAL INPUTS Digital inputs can be configured via software as digital inputs Type configurable via sof...

Page 4: ...he diagram of the device used for the numbering the configuration is determined by the application 7 4 3 Pressure transducers and ratiometric pressure transducers 0 5V 3 row sensors that require 5Vdc power supply Recommendations follow the diagram of the device used for the numbering the configuration is determined by the application 8 CONNECTION TO XEC SUPERCAP The XEC device and the XEV20D drive...

Page 5: ...y the ISaGRAF software refer to the documentation on https www ipro academy website 10 MEANING OF THE LED LIGHTS The following table illustrates LED light operation LED MODE MEANING PWR ON On The instrument is powered correctly ALARM On There is an alarm TX RX Blinking CAN Bus or LAN activity communication enabled TX RX On No link OPEN V1 Blinking Valve 1 in opening mode OPEN V1 On Valve 1 fully o...

Reviews: