7.3  CONNECTION TO IPRO 

 
 

 

7.4  CONNECTION TO ANALOGUE INPUTS 

7.4.1  Temperature probes (NTC and PTC) 

2-row sensors that do not require polarity to be respected. 
Each  sensor  must  be  connected  through  one  of  the  inputs  (from  Pb1  to  Pb10)  and 
the common (PbC) as shown in the diagram below. 
 

 

 
Recommendations: 
- follow the diagram of the 
device 

used, 

for 

the 

numbering. 
-  the  configuration  is 
determined 

by 

the 

application. 
-  if  used  as  a  digital  input 
(potential  free  -  not  live), 
use  the  same  connection 
configuration  as  of  the 
sensors. 

 

 

7.4.2  Pressure transducers and current probes (4 - 20 mA) 

2-row sensors that r12Vdc power supply. 
Each  sensor  must  be  connected  through  one  of  the  inputs  (from  Pb1  to  Pb10)  and 
the power supply (+12V) as shown in the diagram below. 

 

 
Recommendations: 
-  follow  the  diagram  of 
the  device  used,  for  the 
numbering. 
-  the  configuration  is 
determined 

by 

the 

application. 
 

 

7.4.3  Pressure transducers and ratiometric pressure transducers (0 - 5V) 

3-row sensors that r5Vdc power supply. 

 

Recommendations: 
-  follow  the  diagram  of  the 
device 

used, 

for 

the 

numbering. 

the 

configuration 

is 

determined 

by 

the 

application. 

 

 

 

8.

 

CONNECTION TO XEC SUPERCAP  

The  XEC  device  and  the  XEV20D  driver  must  be  powered  by  two  different 
transformers; failure to observe this warning can cause damage to the XEC device or 
to the XEV20D driver. 
 
With a connection to the  XEV20D driver, to control two electronic expansion valves, 
two XEC modules must be used. 
For  both  XEC  modules,  observe  the  correct  power  supply  connection  sequence 
(connectors  1  of  the  XEC  modules  connected  to  the  same  pole  of  the  transformer, 
connectors 2 of the XEC modules connected to the other pole of the transformer). 
 

8.1  CONNECTION  TO  THE  XEV20D  DRIVER  WITH  JUST  ONE  CONNECTED 
VALVE 

 

 

8.2  CONNECTION TO THE XEV20D DRIVER WITH TWO CONNECTED VALVES 

 

Summary of Contents for Dixell XEV20D

Page 1: ...nserted inside an electrical panel that can only be accessed by authorized personnel For safety purposes the keyboard must be the only part that can be reached The device must never be hand held while being used It is good practice to bear the following in mind for all Dixell products o Prevent the electronic circuits from getting wet as contact made with water humidity or any other type of liquid...

Page 2: ...e iPro tells the driver a new value for one of the aforementioned parameters the driver itself proceeds with the complete closure of the valve The XEV20D drivers issued by Dixell are tested but not configured this means that the parameters in the flash memory are set to a default value specifically the valve type parameter 0 4 1 VALVES CONNECTIONS TABLE Read carefully the table below to learn how ...

Page 3: ...0 mA input resistance 100Ω Precision at 25 C NTC PTC PT1000 1 C 0 5V 100mV 4 20mA 0 30mA Measurement and adjustment field 50 C 110 C 58 F 230 F NTC probe 50 C 150 C 32 F 302 F PTC probe 50 C 100 C 32 F 212 F PT1000 probe 0 bar 50 bar 0 psi 302 psi pressure probe Resolution 0 1 C 1 F 0 1 bar 6 2 DIGITAL INPUTS Digital inputs can be configured via software as digital inputs Type configurable via sof...

Page 4: ...he diagram of the device used for the numbering the configuration is determined by the application 7 4 3 Pressure transducers and ratiometric pressure transducers 0 5V 3 row sensors that require 5Vdc power supply Recommendations follow the diagram of the device used for the numbering the configuration is determined by the application 8 CONNECTION TO XEC SUPERCAP The XEC device and the XEV20D drive...

Page 5: ...y the ISaGRAF software refer to the documentation on https www ipro academy website 10 MEANING OF THE LED LIGHTS The following table illustrates LED light operation LED MODE MEANING PWR ON On The instrument is powered correctly ALARM On There is an alarm TX RX Blinking CAN Bus or LAN activity communication enabled TX RX On No link OPEN V1 Blinking Valve 1 in opening mode OPEN V1 On Valve 1 fully o...

Reviews: