1592009520 XW260K GB r1.0 04.08.2015 

                       XW260K 

1/5 

W

ING

 

XW260K 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for  easy  and  quick 
reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be 
used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring 
the same and unchanged functionality. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not  expose  to  water  or  moisture:  use  the  controller  only  within  the  operating  limits  avoiding 
sudden temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.” 
(see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from 
each other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel 
with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION  

Model 

XW260K

 is microprocessor based controller suitable for applications on medium or low temperature 

refrigerating units. It must be connected by means of a two-wire cable (

 1mm) at a distance of up to 30 

meters to the keyboard 

T620

. It is provided with four relay outputs to control compressor, defrost - which 

can be either electrical or hot gas  - the evaporator fans and the lights. 
It is also provided with three NTC probe inputs, one for temperature control, one to control the defrost end 
temperature  of  the  evaporator  and  the  third,  optional,  for  the  display.  There  are  two  digital  inputs  (free 
contact) for the door switch and configurable by parameter. 
The  standard  TTL  output  allows  the  user  to  connect,  by  means  of  a  TTL/RS485  external  module,  a 

ModBUS-RTU 

compatible monitoring system and to programme the parameter list with the 

“Hot Key”. 

An 

optional output for 

RS485

 direct 

 

is available. 

3.

 

CONTROLLING LOADS 

3.1

 

THE COMPRESSOR 

The  regulation  is  performed  according  to  the  temperature  measured  by  the  thermostat  probe  with  a 
positive differential from the set point: if the temperature increases and reaches set point plus differential 
the compressor is started and then turned off when the temperature reaches the set point value again. 
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters 

COn

” and “

COF

”. 

3.2

 

FAST FREEZING  

When defrost is not in progress, it can be activated the keypad by holding the 

o

 key pressed for about 3 

seconds. The compressor operates in continuous mode for the time set through the “

CCt

” parameter. The 

cycle  can  be  terminated  before  the  end  of  the  set  time  using  the  same  activation  key, 

o

  for  about  3 

seconds. 

3.3

 

DEFROST 

Three defrost modes are available through the “

tdF

” parameter: defrost with electrical heater, hot gas or 

thermostatic defrost. The defrost interval is control by means of parameter “

EdF

”: (EdF=in) the defrost is 

made every “

IdF

” time, (EdF=Sd) the interval “IdF” is calculate through Smart Defrost algorithm (only when 

the compressor is ON and the evaporator temperature is bigger than “SdF” parameter). 
At the end of defrost the drip time is controlled through the “

Fdt

” parameter. 

3.4

 

CONTROL OF EVAPORATOR FANS 

The fan control mode is selected by means of the “

FnC

” parameter: 

 
C-n

 = running with the compressor, OFF during the defrost;  

C-y

 = running with the compressor, ON during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

 

An  additional  parameter  “FSt”  provides  the  setting  of  temperature,  detected  by  the  evaporator  probe, 
above  which  the  fans  are  always  OFF.  This  can  be  used  to  make  sure  circulation  of  air  only  if  his 
temperature is lower than set in “FSt”. 
 
 
 
 
 
 
 
 
 
 
 
 
 

4.

 

KEYBOARD 

 

 

 

 

To display and modify target set point; in programming mode it selects a parameter or 
confirm an operation.  
By holding it pressed for 3s when max or min temperature is displayed it will be erased. 
 

 

To  see  the  max.  stored  temperature;  in  programming  mode  it  browses  the  parameter 
codes or increases the displayed value.  
By holding it pressed for 3s the fast freezing  cycle is started. 
 

 

To  see  the  min  stored  temperature;  in  programming  mode  it  browses  the  parameter 
codes or decreases the displayed value. 
 

 

 
By holding it pressed for 3s the defrost is started. 
 

 

 
Switch ON and OFF the cold room light. 

 

 
Switch ON and OFF the instrument. 

 

KEY COMBINATIONS 

 

 

 

 

To lock and unlock the keyboard.

 

 

 

 

To enter the programming mode. 

 

 

 

 

To exit the programming mode.

 

 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

Function 

 

ON 

The compressor is running 

 

FLASHING 

- Programming Phase (flashing with LED 

- Anti-short cycle delay enabled 

 

ON 

The fan is running 

 

FLASHING 

Programming Phase (flashing with LED 

 

ON 

The defrost is enabled 

 

FLASHING 

Drip time in progress 

 

ON 

The Fast Freezing cycle is enabled 

  

ON 

- ALARM signal 
-  In  “Pr2”  indicates  that  the  parameter  is  also 
present in “Pr1” 

 
Function of the LEDs placed on the left top side of buttons: 
 

BUTTON 

MODE 

FUNCTION 

SET 

FLASHING 

The  Set  point  is  displayed  and  it  can  be 
modified  

SET 

FAST 

FLASHING 

The Energy Saving is enabled  

DEFROST 

ON 

The Manual Defrost is activated 

LIGHT 

ON 

The Light is ON 

ON/OFF 

ON 

The instrument is OFF 

 

4.2

 

HOW TO SEE THE MIN TEMPERATURE 

 

1.  

Press and release the 

n

 key. 

2.  

The  “Lo”  message  will  be  displayed  followed  by  the  minimum  temperature 
recorded. 

3. 

By pressing the 

n

 key or waiting for 5s the normal display will be restored. 

4.3

 

HOW TO SEE THE MAX TEMPERATURE 

 

1.  

Press and release the 

o

 key. 

2.  

The  “Hi”  message  will  be  displayed  followed  by  the  maximum    temperature 
recorded. 

3. 

By pressing the 

o

 key or waiting for 5s the normal display will be restored. 

4.4

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

To reset the stored temperature, when max or min temperature is displayed : 
1.

 

Press SET key until “rST” label starts blinking. 

 

N.B. After the installation RESET the temperature stored. 
 
 

 

Summary of Contents for dixell WING XW260K

Page 1: ...ough the CCt parameter The cycle can be terminated before the end of the set time using the same activation key o for about 3 seconds 3 3 DEFROST Three defrost modes are available through the tdF parameter defrost with electrical heater hot gas or thermostatic defrost The defrost interval is control by means of parameter EdF EdF in the defrost is made every IdF time EdF Sd the interval IdF is calc...

Page 2: ...rator probe P3 auxiliary probe 1r2 difference between P1 and P2 P1 P2 DEFROST tdF Defrost type rE electrical heater Compressor OFF rT thermostat defrost During the defrost time MdF the heater switches On and OFF depending on the evaporator temperature and dtE value in hot gas Compressor and defrost relays ON EdF Defrost mode in interval mode The defrost starts when the time Idf is expired Sd Smart...

Page 3: ...parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 7 INSTALLATION AND MOUNTING T620 keyboard shall be mounted on vertical panel in a 150x31 mm hole and fixed using two screws 3 x 2mm To obtain an IP65 protection grade use the front panel rubber gasket mod RG L Power module XW260K shall be mounted in a panel with two or more ...

Page 4: ...luminium protection 176x 123mm height 52mm GS case 155x114 height 70mm Self extinguishing ABS IP55 PS case 147x110 height 47mm Self extinguishing ABS IP55 UL approved Connections Screw terminal block 2 5 mm2 heat resistant wiring and 6 3mm Faston Power supply 230Vac or 110Vac 10 Power absorption 10VA max Inputs 3 NTC probes Digital inputs 2 free voltage Relay outputs Total current on loads MAX 20A...

Page 5: ...5 0 Pr2 ANALOGUE INPUTS Ot Thermostat probe calibration 12 0 12 0 C 21 21 F 0 Pr1 OE Evaporator probe calibration 12 0 12 0 C 21 21 F 0 Pr2 O3 Auxiliary probe calibration 12 0 12 0 C 21 21 F 0 Pr2 P2P Evaporator probe presence n y y Pr2 P3P Auxiliary probe presence n y n Pr2 HES Temperature increase during the Energy Saving cycle 30 30 C 22 86 F 0 Pr2 DIGITAL INPUTS Odc Open door control No Fan CP...

Reviews: